8. Critical  Settings

The following settings are essential to the successful operation of the system.

Step 1: 

Set switch setting #1 and tekmarNet

®

 system control located in the mechanical 

room to Unlock to change Access level to Installer. Return to Lock setting once installation 
has been completed.

Step 2:

 Press and hold “Home” button for 3 seconds to enter programming menus.

Step 3:

 Touch NEXT to locate the Setup Menu and touch ENTER.

Setup Menu Settings

SENSOR 1

Select to the type of sensor connected to 
auxiliary sensor input 1.
Range: OFF, ROOM, FLOR (floor), OUT 
(outdoor)
Default: OFF

SENSOR 2

Select to the type of sensor connected to 
auxiliary sensor input 2.

Range: OFF, ROOM, FLOR (floor)
Default: OFF

ROOM SENSOR

Select whether the built-in room 
temperature sensor is on or off.
Range: OFF or ON
Default: ON

W1 TERMINAL UNIT

Select the terminal unit type of the first 
stage of heat W1.
Range: CTRL, HRF1, HRF2, CONV, 
COIL, OTHR 
Default: CTRL

Setup Menu Settings

W1 PUMP

Select whether the boiler system pump 
or mix system pump on a tekmarNet

®

 

system control should operate while the 
first stage of heat W1 is operating.

Range: OFF or ON

Default: ON

W1 THERMAL MOTOR

Select whether the first stage of heat W1 
operates a thermally actuated zone valve 
(wax actuator). When set to ON, there is a 
3 minute delay before operating the pump 
and any heat sources.

Range: OFF or ON

Default: OFF

W CYCLES PER HOUR

Select the number of heating cycles 
per hour. 

Only available when the 

thermostat is not connected to a 
tekmarNet

®

 System Control.

Range: SYNC, AUTO, 2 to 12

Default: SYNC

Summary of Contents for tekmarNet 552

Page 1: ...ekmarNet Thermostat 552 Quick Setup Guide 552_Q 02 14 Zoning Replaces 12 13 1 Location 2 Remove Mounting Base 3 Install Mounting Base Exterior Wall Behind Door Interior Wall 5 feet 1 5 m 3 1 4 83 mm T...

Page 2: ...tings Setback Scene None ON ool Master 1 nlock 1 2 3 tekmarNet Thermostat 552 One Stage Heat P N2 24 V 10 1 8 VA 1051 03 Switch Settings www tekmarcontrols com Lock sed ock ON 1 2 Back of Thermostat t...

Page 3: ...S2 Com Thermostat Sensors 5 Wiring Continued Thermostat Front Push Thermostat Base Adjust the Time Adjust the Schedule Display the Floor or Outdoor temperature Away Key Turn the Heat on or Off Home B...

Page 4: ...e Setup Menu and touch ENTER Setup Menu Settings SENSOR 1 Select to the type of sensor connected to auxiliary sensor input 1 Range OFF ROOM FLOR floor OUT outdoor Default OFF SENSOR 2 Select to the ty...

Page 5: ...tallez la base de montage 3 1 4 83 mm Thermostat Base Stud Switch Box Wall Stud Thermostat Base Mur ext rieur Mur int rieur 5 pi 1 5 m Mur Base de thermostat Base de thermostat Commutateur bo te Goujo...

Page 6: ...itch Settings Setback Scene None ON ool Master 1 nlock 1 2 3 tekmarNet Thermostat 552 One Stage Heat P N2 24 V 10 1 8 VA 1051 03 Switch Settings www tekmarcontrols com Lock sed ock ON 1 2 Dos du therm...

Page 7: ...S1 S2 Com Thermostat Capteurs Pas d alimentation Base de thermostat Fa ade du thermostat Poussoir R gler l heure R gler le programme Cl distance Activer ou d activer la chaleur Afficher la temp ratur...

Page 8: ...ages du menu de configuration CAPTEUR 1 S lectionner le type de capteur reli l entr e auxiliaire du capteur 1 Gamme OFF CHAMBRE FLOR tage OUT en plein air Par d faut OFF CAPTEUR 2 S lectionner le type...

Page 9: ...base de montaje Pared exterior Pared interior 5 pies 1 5 m Wall Stud Thermostat Base Base del termostato Pared 3 1 4 83 mm Thermostat Base Stud Switch Box Base del termostato Caja de interruptor tekm...

Page 10: ...1 03 witch Settings Setback Scene None ON ool Master 1 nlock 1 2 3 tekmarNet Thermostat 552 One Stage Heat P N2 24 V 10 1 8 VA 1051 03 Switch Settings www tekmarcontrols com Lock sed ock ON 1 2 Parte...

Page 11: ...Sensores 5 Cableado continuaci n 7 Interfaz del usuario Base del termostato Frente del termostato Eempuje Ajustar hora Ajustar la programaci n Tecla de salida Prender o apagar la calefacci n Mostrar l...

Page 12: ...OR Piso Predeterminado OFF Apagado SENSOR AMBIENTE Prenda o apague el sensor integrado de la temperatura del aire en el ambiente Rango OFF Apagado o ON Encendido Predeterminado ON Encendido TIPO DE TE...

Reviews: