Mixing Control 361

D 361

03/09

The Mixing Control 361 is designed to control the supply water temperature to a hydronic system in order to provide outdoor reset or
setpoint operation. The control uses a variable speed injection pump to regulate the supply water temperature, while protecting the
boiler against flue gas condensation. The control has a Liquid Crystal Display (LCD) to view system status and operating information.

• Optional indoor sensor for room air temperature control

• Test sequence to ensure proper component operation

• Setback input for energy savings

• 120 V (ac) power supply

• CSA C US certified (approved to applicable UL standards)

Additional functions include:

• Quick Setup for easy installation and programming of control

• User comfort adjustment to increase or decrease building

space temperature

• Advanced settings to fine-tune building requirements

• Boiler Control for improved energy savings

• Powered mixing system pump output

Output

Boiler

Input

Universal Sensor

Included

Input

Outdoor

Sensor

Included

Output

Mixing System

Pump

Input

120 V (ac) Power

Supply

Input

Mixing Demand

 Signal

Input

tekmar Timer

Optional

Input

Indoor Sensor

Optional

Output

Variable Speed

Driven Pump

Input

Universal Sensor

Included

   Press the 

Item

, ,  buttons

simultaneously for 1 sec. to

enter the 

ADJUST

 menu

  Use the  ,   buttons  to

adjust the 

ROOM

 setting

To increase or decrease the

building temperature:

Mixing Control 361

Variable Speed

Mixing

Demand

50

30

10

C         US

30% Enable

Return

10% Enable

Boiler Sensor

Supply

Installer

Advanced

ROOM - Set to desired room temp.

OUTDR DSGN - Set to coldest (design)

outdoor temp.

Installer Instructions

Terminal Unit                  Set to
High Mass Radiant

Low Mass Radiant

Fan Coil

Convector

Radiator

Baseboard

1

2

3

4

5

6

Refer to brochure for more information

Made in Canada by

tekmar Control Systems Ltd.
tektra 913-01

Power:

Variable Pump:

Relays:

Demand:

120V + 10% 50/60 Hz 1650 VA

240V (ac) 2.4 A (FLA) 5 A (LRA), fuse T2.5 A

240V (ac) 10 A 1/3 hp

20 to 260 V (ac) 2 VA

Signal wiring must be

rated at least 300V.

H1188D

MIX

°

F

VIEW

Test

11 12 13 14 15 16 17

Do not apply power

UnO

Sw

Com Boil Mix Com Out Indr

9 10

Boiler

1

2

3

4

5

6

7

8

Mixing

Demand

L

N

Sys

Pmp N

Var

Pmp N

Power

Display defaults back to 

VIEW

menu after 20 sec.

% Out

Terminal

Unit

70 90

OCC

Item

 
 

Note:

Mixing demand must be
powered with 20 to 260
V (ac) before pumps will 
operate or the boiler is 
able to fire.

Dat

e Code

Meets Class B:

Canadian ICES

FCC Part 15

Summary of Contents for Mixing Control 361

Page 1: ...Demand Signal Input tekmar Timer Optional Input Indoor Sensor Optional Output Variable Speed Driven Pump Input Universal Sensor Included Press the Item buttons simultaneously for 1 sec to enter the A...

Page 2: ...ommend reading Section A General Operation of the Sequence of Operation as this contains important information on the overall operation of the control Then read the sub sections that apply to your ins...

Page 3: ...s the current status of the control s inputs outputs and operation Item Field Displays an abbreviated name of the selected item Pump Displays when the mixing system pump is in operation Burner Display...

Page 4: ...An outdoor sensor is not required during this mode of operation VARIABLE SPEED A standard wet rotor circulator is connected to the 361 on the Var Pmp and N terminals 7 and 8 The 361 increases or decr...

Page 5: ...ction B1 General Section B2 Installer Section B3 Advanced Section B1 General MIXING DEMAND A mixing demand is required in order for the 361 to provide heat A mixing demand is generated by applying a v...

Page 6: ...ET becomes the setpoint supply temperature that the control is to maintain The MIX TARGET temperature is set by the installer in the ADJUST menu An outdoor sensor is not required during this mode of o...

Page 7: ...r temperature to the heating element and the room air temperature Default values MIX DSGN 180 F 82 C MIX MAX 200 F 93 C MIX MIN OFF Radiator 5 A radiator terminal unit has a large heated surface that...

Page 8: ...ating system to satisfy this demand If the control is in setpoint mode the WWSD feature is not functional Section C Boiler Operation Section C1 General Operation Section C2 Boiler Sensor Placement Sec...

Page 9: ...temperature directly but allows the boiler to operate at its operating aquastat setting when required If this mode of operation is selected the boiler pump should either operate continuously or be op...

Page 10: ...and select those sections of the chamber with common voltages Do not allow the wiring to cross between sections as the wires will interfere with safety dividers which should be installed at a later t...

Page 11: ...oiler Contact The Boiler terminals 9 and 10 are an isolated output in the 361 There is no power available on these terminals from the control These terminals are to be used as a switch to either make...

Page 12: ...rly test the wiring and sensors Test The Sensors In order to test the sensors the actual temperature at each sensor location must be measured A good quality digital thermometer with a surface temperat...

Page 13: ...any installation or troubleshooting information supplied with the pump If the pump operates properly disconnect the power and remove the jumpers Boiler If the boiler circuit is connected to the Boiler...

Page 14: ...uick Setup The quick setup can be used for both outdoor reset and setpoint operation To enter the installer programming mode set the Advanced Installer DIP switch to Installer OUTDOOR RESET Access the...

Page 15: ...Use the or button to set the scale to F or C To exit the ADJUST menu press and release the Item button to advance to the ESC item Then either press the or button or leave the buttons alone for 20 seco...

Page 16: ...culation for the heating system OUTDR DSGN OFF 70 F to 220 F 21 to 104 C B3 The design indoor air temperature used in the heat loss calculation for the heating system OUTDR DSGN OFF 35 to 100 F 2 to 3...

Page 17: ...used to rapidly advance through the test sequence To reach the desired step repeatedly press and release the Test button until the appropriate device and segment in the display turn on Step 1 The inj...

Page 18: ...ng close attentiontothelocationofpumps checkvalves pressurebypassvalves andmixingvalves Ensurecorrect flow direction on all pumps This is also a very useful step if additional assistance is required D...

Page 19: ...IN adjustment is higher than 100 F 38 C the control operates the Boiler contact as a boiler enable see section C The boiler temperature is then limited by the operating aquastat If the BOIL MIN adjust...

Page 20: ...tekmar representative for that territory If the address of the repre sentative is not known please request it from tekmar at the telephone number listed below All speci cations are subject to change w...

Reviews: