background image

 

Ultrasonic LoRaWAN  

Installation Guide 

 
 

Thank you for purchasing the Tekelek Ultrasonic LoRaWAN waste bin 
sensor which uses ultrasonic technology to measure the contents of your 
waste bin and then communicates this data to a LoRaWAN network. 

 

 

 
 

STEP 1: Activation 
 

The Ultrasonic LoRaWAN waste bin sensor works in conjunction with a 
LoRaWAN network and a connected platform and before activation must 
first be registered with both. Access to the LoRaWAN backend server is 
required to verify that the unit has correctly joined the network. See User 
Manual for further details. 
Ensure that the LoRaWAN™ network is within

 

communication range of the 

sensor. This should occur before the sensor is physically fitted onto the 
Tank.  

 

Place the sensor as close as possible to the point of installation, 
press the button for 1 second to connect to the LoRaWAN 
network and upload a status message. 

 

The LED will stay illuminated as the sensor registers: 

 

Red

 

LED flashing = The sensor is registering & connecting for the first 

time. (Sensor is shipped in dormant state). 

 

Green

 

LED flashing = The sensor is already registered. The 

connection process will take between 20 & 40 seconds.  

 

After the connection has completed, the LED will 
flash on & off (to indicate whether the connection 
was a success or failure). 

 
 
 
 

LED Patterns

 

 

Press and hold the button for approximately 1 second, until the LED 
turns green. 

 

Wait approximately 10-20 seconds and observe if the LED flashes 
green or red. 

See the following for description of Green/Red LED flash codes. 
 

LED Radio Signal Strength Flash Codes: 

LED Pattern 

Function 

Green

 

X 3 Flashes 

Excellent signal strength 

Green

 

X 2 Flashes 

Good signal strength 

Green

 

X 1 Flash 

Adequate signal strength 

Alternate 

Green

/

Red

 

Flash 

Weak signal strength 

Weak signal strength: Try 5 times and if this response is stable then 
it’s deemed adequate. If the sensor shows some double red flashes 
during this signal strength test - then an external antenna should be 
tried. It may need to be elevated for best performance. 

 

LED Error Flash Codes: 

LED Pattern 

Function 

Red

 

X 1 Flash 

Authentication or LoRaWAN join 
request fail 

Red

 

X 2 Flashes 

No response from LoRaWAN network 

Red

 

X 3 Flashes 

General Error. Please try again. If the 
error persists, contact the supplier for 
support. 

Red

 

X 5 Flashes 

Maximum number of allowed button 
presses exceeded (up to 6 button 
presses per hour allowed). 

 
 
 
 
 

 

STEP 2: Installation 
 

The following outlines the Ultrasonic LoRaWAN waste bin sensor 
mounting options. 

 

The sensor is to be fitted on the underside (inside) of the top of 

the waste bin. 

 

The sensor must sit in a vertical position and be fitted such that 

the sensor has a clear path to the tank contents. Position it so 
that it is as close to the centre of the bin as possible and ensure 
there are no internal obstructions that may interfere with the 
ultrasonic signal. 

 

Once a suitable position has been located, fix the sensor in place 

by attaching the bracket to the waste bin using the bolt provided. 

 

 

 

 

The antenna can be mounted on glass, metallic and plastic 

surfaces. 

 

The antenna RF cable is fed via the through hole mount base to 

ensure no cable is visible when fixed and the rubber seal around 
the base protects against water ingress.  

 

 The antenna is fixed via its 22mm length screw thread and can fit 

onto panels of up to 13mm thickness. 
 

 

 
 
 
 

 

Reviews: