               ATTENTION:  

 

Read the manual carefully before starting to use the control unit. Keep the instructions for future reference. 
 
  
                Do not open the device, touching any internal components can cause electric shock. Contact with 110-240 Volts 
AC can be fatal. To reduce the risk of electric shock, do not dismantle the back of the device for any reason. Moreover its 
opening would void the warranty. B

efore connecting the device to the power supply, make sure that all the 

connections are correct.

 Always disconnect the unit from the supply before any cabling modification. 

                 Any intervention on the equipment must be entrusted to a qualified repair engineer

         Failure to comply with these instructions can cause damages, fires or electric shock, and possible serious injuries! 

 

POWER SUPPLY

 

 

The VRT600 series can be supplied by 230Vac 50/60Hz o a 12Vac –Vcc, depending on the model purchased. 
Before using it, make sure the power cable is not damaged, kinked or pinched. Do not tamper with the power cable. Never 
disconnect the unit by pulling the cable, avoid touching the pins. Do not carry out any connecting/disconnecting with wet 
hands. To disconnect the device, do not use objects such as levers. Immediately disconnect the device if you smell burning 
or see any smoke: contact technical service.  

 

LIQUIDS

 

Do not expose the equipment to splashes or drops, do not position it in places with humidity exceeding 90% and never touch 
with wet or humid hands during storms. If any liquid penetrates the control unit, disconnect it immediately and contact 
technical service. 

 
CLEANING 

Disconnect the power cable before cleaning the control unit, use a dry cloth to dust it, without any solvent or detergents, and 
compressed air. 

 
OBJECTS 

Never insert any objects into the cracks of the control unit. If this happens, disconnect the control unit and  
contact an engineer. 

 
USE RESERVED TO QUALIFIED PERSONNEL 

The purchased goods are a sophisticated electronic device that is totally unsuitable to be used by non-qualified personnel. 
Any intervention must be carried out by a specialist engineer. 

 
ACCESSORIES 

The use of non-original accessories or spare parts might damage the unit and endanger users' safety.  In the event of faults, 
contact technical service. 

 
LOCATION 

Install the control unit indoors, in a place protected from water splashes and sun rays. Do not place near heat sources 
exceeding the parameters stated in this manual. Position on a stable surface, far from any possible vibrations. Position the 
unit as far as possible from any intense magnetic fields. 

 
REPAIRS 

Do not open the control unit. For any fault, always use qualified personnel. The opening of the control unit and/or the removal 
of the series identifying label entails the automatic forfeiture of the warranty. The Warranty seal is applied to all devices, any 
attempt to open the unit would break the seal and cause the consequent automatic forfeiture of the warranty. 

 
 

TECHNICAL INFORMATION  

 

Mail: [email protected] — tel: 02/4581861

 

SAFETY REQUIREMENTS 

Summary of Contents for VRT600 SERIES

Page 1: ...h ISO9001 2008 certified quality system http www tecsystem it R 1 0 16 09 13 Translations of the original instructions ENGLISH TECSYSTEM S r l 20094 Corsico MI Tel 39 024581861 Fax 39 0248600783 VRT600 SERIES INSTRUCTION MANUAL ...

Page 2: ...ANUAL IS VALID AND COMPLETE FOR THE VRT600 AND VRT600 U VERSIONS PAGE 1 SAFETY REQUIREMENTS 3 2 ACCESSORIES 4 3 TECHNICAL SPECIFICATIONS 5 4 FRONT PANEL 7 5 INSTALLATION 8 6 ELECTRICAL CONNECTIONS 9 VRT600 BACK VRT600 U BACK 10 POWER SUPPLY 11 OPERATION HOW TO CHECK THE ALARM STATUS HOW TO RESET A MOTOR IN ALARM OPERATION WITH BAR 400 OR 600 7 PROGRAMMING 12 8 WARRANTY REGULATIONS 13 9 TROUBLESHOO...

Page 3: ...90 and never touch with wet or humid hands during storms If any liquid penetrates the control unit disconnect it immediately and contact technical service CLEANING Disconnect the power cable before cleaning the control unit use a dry cloth to dust it without any solvent or detergents and compressed air OBJECTS Never insert any objects into the cracks of the control unit If this happens disconnect ...

Page 4: ...Code 2PL0371 1 1 supply terminal 3 poles pitch 5 Code 2PL0367 2 Motor line terminal 6 poles pitch 5 Code 2PL0372 1MN0030 REV The above terminals are optional according to the configuration purchased ATTENTION always install the device using the terminals included in the pack The use of terminals other than those included with the control unit might cause malfunctions ACCESSORIES ...

Page 5: ...x Connections on extractable terminal blocks OUTPUTS 1 fault sensor or operating failure FAULT relay SPDT Output relay with 5A 250Vac res COSФ 1 contacts 6 outputs M1 M2 M3 M4 M5 M6 250Vac max 10 5A max 50 60Hz SPST DIMENSIONS 100x100 mm din43700 depth 131mm terminal block included Hole 92 x 92 mm Hole 92 x 92 mm TEST AND PERFORMANCE Construction in compliance with CE regulations Protection from e...

Page 6: ...C Humidity 90 non condensing Housing NORYL 94 _V0 Absorption 7 5VA max Electronic protection only on customer s request Polycarbonate IP65 front DISPLAY AND DATA MANAGEMENT LED s alarm undercurrent overcurrent LED s running remote local LED s prg setting cal Initial AUTO TUNING to set up motors operation Front button to START STOP motors locally Front alarm RESET button Access to programming throu...

Page 7: ...2 Current variation LED yellow 4 LED yellow warning motors M1 M2 M3 M4 M5 M6 are in under current 13 Fans local management LED yellow 5 Fixing block 14 Fans remote control LED green 6 Fans local START STOP button 15 Programming selection LED yellow In start d trip d 7 Fans control mode REM LOC button REMOTE or LOCAL 16 Monitoring delay LED yellow at start up start d 8 ENT RESET button alarm reset ...

Page 8: ...heet 2 1 3 1MN0063 REV 0 1 Control unit 2 Panel hole dimensions 0 8mm tolerance 3 Identification label Fix the unit securely with the blocks supplied 1 2 3 4 1MN0008 REV 0 1 Control unit 3 Fixing screw 2 Fixing block 4 Crosshead screwdriver 1X100mm MOUNTING ...

Page 9: ...ac 10 15 amp max 50 60Hz 6 Remote enabling contact ENABLE 3 Control unit supply 230 Vac 10 50 60 Hz 7 5 VA 7 FAULT relay fault signal 4 M1 M2 M3 fan line supply 230Vac 10 15 amp max 50 60Hz Note with the power to the unit ON the FAULT relay switches contacts 8 9 open NO and 7 9 closed NC FAULT 8 9 NC ALARM FAULT OR POWER OFF FAULT 7 9 NC POWER ON ELECTRICAL CONNECTIONS ...

Page 10: ... line supply 230Vac 10 15 amp max 50 60Hz 6 Remote enabling contact ENABLE 3 Control unit supply 12Vac dc 10 6 5VA 7 FAULT relay fault signal 4 M1 M2 M3 fan line supply 230Vac 10 15 amp max 50 60Hz Note with the power to the unit ON the FAULT relay switches contacts 8 9 open NO and 7 9 closed NC FAULT 8 9 NC ALARM FAULT OR POWER OFF FAULT 7 9 NC POWER ON ...

Page 11: ...re HOW TO CHECK THE ALARM STATUS Running LED OFF no ventilation activation control Running LED ON REMOTE or LOCAL ventilation activation Over and under current LEDs OFF motor operating correctly Over current LED ON motor stopped due to over current Under current LED ON motor working under current alarm signal Under current LED flashing motor disconnected while auto tuning Over current LED ON motor...

Page 12: ...ult 5 7 Motor start for automatic calibration CAL LED ON To perform the automatic calibration all motors must be connected as per final configuration At the START the motors are switched ON for 60 seconds the CAL LED flashes and LEDs 0 5 10 20 30 light up in sequence When the calibration is completed the control unit resets and goes into REMOTE mode N B any connection or programming errors might c...

Page 13: ...e M1 M2 M3 M4 M5 M6 under current yellow LED ON Check the condition of the fans the cables and the supply Re program the device All the LEDs are flashing Memory error press RESET and repeat the programming procedure All the LEDs are ON Likely microcontroller fault return the device to Tecsystem for repair Contact TECSYSTEM Technical Department if the problem persists European directives 2012 19 EC...

Page 14: ...14 VRT600 SERIES TECHNICAL INFORMATION ufficiotecnico tecsystem it COMMERCIAL INFORMATION info tecsystem it PRODUCT INFORMATION CATALOGUES DOWNLOAD CONTROL UNIT MANUALS ACCESSORIES USEFUL CONTACTS ...