7) MEASURE SIGNALS TRANSPORT 

 
All the transport cables of the Pt100 measure signals must absolutely: 
 

• 

be divided from the power ones 

• 

be realized with shielded cable with twisted conductors 

• 

have a section of min 0.5 mm² 

• 

be twisted if you have no shield 

• 

be firmly fixed in the terminal board 

• 

have tinned or silvered conductors 

 
All the “T” series units have the sensors linearization with a max error of 1% v.f.s.. 
 

 

8) THERMOMETRIC SENSORS DIAGNOSTIC 

 
In the event one of the thermometric sensors installed on the machine to protect is dam-
aged, the 

FAULT

 relay energizes immediately, the 

ALARM

 and 

TRIP

 LED’s of the dam-

aged channel lighten and the 

FAULT

 LED is lightening. 

The screen will automatically display a message showing the fault condition: 
 

• 

Fcc

 sensor is short circuited 

• 

Foc

 sensor is open 

 

 

9) FCD FUNCTION -  DEFECTIVE SENSORS 

 
During the unit normal operation, if the 

Fcd-YES

 function has been selected, the display will 

show 

Fcd

 indicating that a sensor is damaged and the LED corresponding to the affected 

channel will lighten. 
The 

FAULT

 relay will energize giving a signal to the operator.  

After the replacement of the damaged sensor, you can reset the alarm pushing 

RESET 

until 

the display shows the message 

rSt

 

10) TEMPERATURES DIAGNOSTIC 

 
When one of the thermometric sensors surveys a temperature exceeding by 1°C the alarm 
limit, after 4 seconds the 

ALARM

 relay will energize and the 

ALARM

 LED of the affected 

channel  will switch on. 
The same occurs when the 

TRIP

 temperature limit is detected: the 

TRIP

 relay energizes 

and the 

TRIP

 LED corresponding to the affected channel is lightening. 

When the surveyed temperature declines of 1°C below the prefixed limit for the 

ALARM

 and 

TRIP

 switching , the relays de-energize and the respective LED’s switch off.

 

TECSYSTEM srl has realised a special cable for the measure signal transport 
with all the protection requirements according  to CEI Norms: mod. CT-ES

 

Summary of Contents for T2612

Page 1: ...http www tecsystem it T2612 T2612 B T2612 C T2612 AD INSTRUCTION MANUAL TECSYSTEM S r l 20094 Corsico MI Tel 39 024581861 Fax 39 0248600783 T2612 UNI TECSYSTEM S r l R 1 3 07 09 12...

Page 2: ...upply to sensors Accuracy 1 full scale 1 digit Ambient operating temperature 20 C to 60 C Humidity 90 non condensing Housing painted steel panel frontal part in polycarbonate IP65 Burden 7VA Data stor...

Page 3: ...ays can be used for fan control or else they can be included in the conditioning circuit of the transformer box 5 THERMOMETRIC SENSORS CONNECTION Each Pt100 sensor has three conductors one white and t...

Page 4: ...it normal operation if the Fcd YES function has been selected the display will show Fcd indicating that a sensor is damaged and the LED corresponding to the affected channel will lighten The FAULT rel...

Page 5: ...es ex with HFn 001 fans are activated for 5 minutes each hour Maximum value 240 This function has the aim to periodically verify the working of the fans and their control ap paratus during long idle p...

Page 6: ...n 2 2nd cooling relay Alr alarm relay trP trip relay Use the Scroll or keys to make the selection Press the SET key to perform the test on the selected relay To reset press the RESET key and will appe...

Page 7: ...abled function 21 PRG SET Fcd appears on display 22 Enter Fcd YES or NO Fcd YES control of damaged Pt100 connected 23 PRG SET Hld appears on display HLd YES HOLD feature enabled 24 Enter HLd YES or NO...

Page 8: ...by the General Conditions of Sale Tecsystem srl RAEE This SYMBOL shown on the unit indicates that the waste must be subject to separate collection The end user must send the unit to the waste collect...

Page 9: ...r When switching the unit on off the alarm and trip relays energize Strong electrical noise is being picked up on the power line Check to ensure the shield of the sensor cable is connected to the pane...

Page 10: ...cable to be used to guarantee a correct working of the network is con cerned we suggest to follow what is provided for by EIA RS485 standard which advises the use of a 24AWG loop In order not to affec...

Page 11: ...1 Function code not present 2 Wrong data address 3 Wrong data i e length WRITING DATA CODE 16 10 Writing questions Slave addr 16 10 Starting address Hi Starting address Lo Number of registers Hi Numbe...

Page 12: ...ck Y n 00 19 00 Alarm memory bit 7 6 5 4 3 2 1 0 CH4 CH3 CH2 CH1 CH4 CH3 CH2 CH1 TRIP ALARM 31 CRC CALCULATION This protocol includes 2 byte CRC 16 in all the transmission The typical polynomial 11000...

Page 13: ...ALVANIZED SHEET IRON Thickness 1 2 mm FRONT VIEW Cut out 155 X 280 mm Screw rivet M3 x 15mm Screw rivet M3 x 15mm Screw rivet M3 x 15mm 190 mm 210 mm 150 mm 150 mm 320 mm Screw rivet M3 x 15mm Screw r...

Page 14: ...14 T2612 UNI TECSYSTEM S r l T2612 REAR CONNECTIONS CH4 CH3 CH2 CH1...

Page 15: ...15 T2612 UNI TECSYSTEM S r l T2612 FRONT PANEL...

Page 16: ...16 T2612 UNI TECSYSTEM S r l NOTES...

Reviews: