background image

13 

     NT935-4 
SERIES

 

 

 

 

 
 

 

 
 
 
 
 
 
 
 
 

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

POWER SUPPLY 

  

The NT935-4 control unit has UNIVERSAL power supply, i.e. it can be supplied by 24 to 240 Vac-Vdc, 50/60Hz irrespectively 
of polarity in Vdc (terminals 40-42).   

 

This is obtained thanks to the use of a tested power supply unit, newly designed and manufactured, that frees installers from 
worrying about the correct Vac and Vdc supply. 

  
 

The ground must always be connected to terminal 41. 

  

When  the  unit  is  supplied  directly  by  the  secondary  of  the  transformer  to  protect,  it  can  be  burnt  out  by  strong 
overvoltages. 
This happens if the main switch is closed and the transformer has no load (blank test). 
The  above-mentioned  problems  are  much  more  evident  when  the  220  Vac  voltage  is  taken  directly  from  the  transformer 
secondary bars and there is a fixed capacitor battery to phase the transformer itself. 

  
 

To  protect  the  control  unit  from  line  overvoltages,  we  suggest  using  the  PT-73-  220  electronic  discharger,  designed  by 
TECSYSTEM S.r.l. for this specific purpose. As an alternative we suggest using 110 Vac or, even better, 110 Vdc supply 
voltages. 

  
 

If  an  existing  control  unit  must  be  replaced  with  a  new  one,  to  guarantee  its  correct  and  safe  operation,  the 
sensor/relay/supply connecting terminals must be replaced with the new terminals supplied. 

  

 

ALARMS AND VENTILATION

 

  

Carry out the electrical connections on the removable terminal blocks only after disconnecting them from the unit. 
When the control unit is in one of the modes mentioned below, it does not monitor the temperature and the relays are all 
blocked, The fault contact switches and the fault LED flashes. 

 

 

 

Vis. programming display 

 

PRG programming 

 

Relay test 

  

The ALARM and TRIP relays switch only when the set temperature thresholds are exceeded. 

  
The FAULT contact, programmed in failsafe mode (default YES), opens (11-12) when the equipment is supplied only if 
the unit detects no fault on switching on, and stays in this condition until one of the following events occurs: 

  

 

Data memory fault (Ech message). 

 

Pt100 sensor fault (FCC short-circuited sensor, FOC interrupted sensor or Fcd quick temperature increase)  

 

CAL damage to the measurement circuit. 

 

Insufficient supply voltage. 

 

During the power on reset after programming (PRG), displaying the data (VIS) and test relay.   

  

The FAULT failsafe can be disabled selecting FAULT failsafe "NO" see step 30-31 programming page 15. 
 
NOTE: do not connect the FAULT relay to the transformer tripping circuit to avoid unwanted system interruptions. 

  

 

FAULT AND RESET MESSAGE SEQUENCE  

  

Find below the sequence of fault messages and RESET function condition. 

 

1) ECH         
2) CAL            
3) FCD                        
4) ERR PT       

  
 

  

 

The FAN1 and FAN2 contacts can be used to control the cooling fans, or they can be inserted in the conditioning system of 
the transformer room, see paragraph Fan control on page 18.  

  

NOTE: always disconnect the unit before performing any electrical connections. 

  
 

11  12 

FAULT  11-12 NC: ALARM FAULT OR POWER OFF 

FAULT  11-12 NO: POWER ON OR NO FAULT   

11  12   

FAULT CONTACT OPERATION (failsafe enabled) 

 

  
  

eeprom fault                                       
measurement circuit fault                                 
quick temp. increase fault                    
FCC or FOC sensor fault                        

 

  
 

erasable message 
erasable message 
resettable condition                  
non-resettable condition 

  
 

Summary of Contents for NT935-4

Page 1: ...s with ISO9001 certified quality system http www tecsystem it R 1 1 29 09 17 Translations of the original instructions ENGLISH TECSYSTEM S r l 20094 Corsico MI Tel 39 024581861 Fax 39 0248600783 NT935...

Page 2: ...GRAMMING 14 NT935 4 PROGRAMMING NOTES 16 TEMPERATURE SENSORS MEASUREMENT SIGNAL TRANSFER TEMPERATURE SENSOR DIAGNOSTICS 17 VOTING FUNCTION PROGRAMMED DATA DIAGNOSTICS TEMPERATURE DIAGNOSTICS 18 COOLIN...

Page 3: ...ET FUNCTION CODE 20 CODE 3 10 CODE 16 10 NOTES FOR REMOTE PROGRAMMING ERROR CODES 21 ILLEGAL DATA POLLING FREQUENCY MODBUS MAPPING TABLE 22 9 FAIL SAFE FUNCTION 27 10 OUTPUT 4 20mA only for NT935 4 AD...

Page 4: ...ands during storms If any liquid penetrates the control unit disconnect immediately and contact technical service CLEANING Disconnect the power cable before cleaning the control unit using a dry cloth...

Page 5: ...5Nm 1 Pt100 sensor terminal 12 poles pitch 3 81 Code 2PL0420 Screws tightening torque 0 25Nm 1 terminal 2 poles pitch 5 for 4 20mA output Code 2PL0364 or 2PL0363 Screws tightening torque 0 5Nm 1 RS485...

Page 6: ...lays ALARM AND TRIP SPDT 1 sensor or operating failure FAULT relay SPST Output relays with 10A 250Vac res COS 1 contacts 2 ventilation management relays SPST FAN 1 AND FAN 2 Modbus RTU RS485 output NO...

Page 7: ...elected channel ALARM TRIP FAULT 4 leds selection of display mode SCAN AUTO MAN T MAX 2 LEDs to display the state of FAN1 and FAN2 Temperature control from 0 C to 240 C 1 alarm thresholds for each cha...

Page 8: ...tion green LED only AD 5 FAULT red LED 16 3 digit channel display 6 FAN 1 yellow LED 17 T max mode selection red LED 7 FAN 2 yellow LED 18 Man mode selection yellow LED 8 Display mode selection key 19...

Page 9: ...the measurement circuit The temperature values displayed might be incorrect Return the control unit to TECSYSTEM for repair 4 Pt Err This message appears when it is detected that one or more PT100 se...

Page 10: ...supplied 1 Control unit 2 Panel hole dimensions 0 8mm tolerance 3 Identification label 1 Control unit 3 Fixing screw 2 Fixing block 4 Crosshead screwdriver 1X100mm MOUNTING 1 1MN0007 REV 0 2 3 1 2 3 4...

Page 11: ...ph on page 13 3 and see the opening of the fault contact ALARM CONDITION AUDIO AND VISUAL INDICATION STOP SYSTEM Pt100 CONNECTION EXAMPLE Note before connecting the sensors to the control unit read th...

Page 12: ...STOP SYSTEM ALARM CONDITION AUDIO AND VISUAL INDICATION Pt100 CONNECTION EXAMPLE Note before connecting the sensors to the control unit read the Measurement signal transfer paragraph on page 16 Note...

Page 13: ...does not monitor the temperature and the relays are all blocked The fault contact switches and the fault LED flashes Vis programming display PRG programming Relay test The ALARM and TRIP relays switc...

Page 14: ...ES FOR CH1 activation FAN1 and FAN2 are flashing info functioning fans fan cooling control section page 18 10 Select YES FAN1 FAN2 enabled flashing YES only FAN1 enabled flashing YES only FAN2 enabled...

Page 15: ...FAULT LED flashes FAULT 32 Set YES or NO Default YES For NT935 BAS version jumps to step 41 33 ADR datum is displayed Modbus address Default 001 34 Set the address From 1 to 255 35 BDR datum is displa...

Page 16: ...ouples capacitively with the conductors in particular with unscreened cables The effect of this coupling creates a signal that overlaps the signal transmitted by the nearby conductors causing incorrec...

Page 17: ...es from the redundancy concept that consists in duplicating the components of a system to increase their reliability How does VOTING work Using the redundancy principle we use the sensors installed on...

Page 18: ...of the contact FAN1 in relation to the threshold ON OFF programmed to FAN1 YES only FAN2 enabled flashing The selected channel CHn enable the switching of the contact FAN2 in relation to the threshol...

Page 19: ...hen in the following modes display programming and relay test RS485 ELECTRICAL CONNECTIONS As far as the signal cable to be used in order to ensure the correct network operation is concerned we recomm...

Page 20: ...ou try to set these thresholds wrongly the NT935 AD monitoring unit won t proceed with programming and data storage therefore in the following readings you will read the data relevant to the previous...

Page 21: ...set equal to 0 that is NO_VOTING GENERAL UNIT NOTE The models of the unit can be equipped with different options to avoid disruption of production their existence is defined by Fw indicated power with...

Page 22: ...ions see note Options see note R 7 00 Wrong datum received R see tab 8 00 Info various causes R see tab 9 00 Commands W see tab SYSTEM Setting and Status Address LO 10 Data HI Data LO Note 1 Note 2 R...

Page 23: ...Address LO 10 Data HI Data LO Note 1 Note 2 R read W write RW read write 25 2 compl sign 2 compl Ch1 temper 10 C 240 C 48 C 200 C R 26 2 compl sign 2 compl Ch1 max temperat 0 C 240 C 0 C 200 C R 27 2...

Page 24: ...200 C R 38 2 compl sign 2 compl Ch4 max temperat 0 C 240 C 0 C 200 C R 39 2 compl sign 2 compl Ch4 temper alarm set point 1 C 240 C 1 C 200 C As AL RW 40 2 compl sign 2 compl Ch4 temper trip set point...

Page 25: ...60 00 Ch4 Setting See Note CHx RW 61 00 00 R 62 00 00 R 63 00 00 R 64 00 00 R CHANNELs 1 4 Status Address LO 10 Data HI Data LO Note 1 Note 2 R read W write RW read write 65 Ch1 story Ch1 status See...

Page 26: ...TATUS CHn STORY BIT 7 BIT 6 BIT 5 BIT 4 BIT 3 BIT 2 BIT 1 BIT 0 TRIP ALARM FOC FCC RELAY STATUS coil energizing status BIT 7 BIT 6 BIT 5 BIT 4 BIT 3 BIT 2 BIT 1 BIT 0 FAULT relay 1 ON TRIP relay 1 ON...

Page 27: ...mA 0 2 mA Note We recommend you use a screened and twisted cable connect the twisted pair taking polarities into account and lay the network avoiding narrow bends or ring windings Always position the...

Page 28: ...easurement signal transfer on page 16 Identification of a sensor fault or faulty connection In case of a faulty connection or sensor fault a quick positive or negative variation in temperature might o...

Page 29: ...check the instructions given in the paragraphs measurement signal transfer and temperature sensor diagnostics on page 16 Activate the FCD function FCD warning See the FCD function on page 28 Contact...

Page 30: ...F THE EQUIPMENT 0 45 Kg INPUT SUPPLY 24 240 Vac Vdc 10 50 60 Hz 7 5VA max PROTECTION External switch or circuit breaker OUTPUTS RELAYS 5 relay Output 10A 250Vac res COS 1 OPTIONAL PORTS AD RS485 4 20m...

Reviews: