![TECSYSTEM FO 935 Instruction Manual Download Page 7](http://html1.mh-extra.com/html/tecsystem/fo-935/fo-935_instruction-manual_1072991007.webp)
7
FO 935
TECHNICAL SPECIFICATIONS
FO 935 BASIC
FO 935 D
TESTS AND PERFORMANCE
●
●
Construction in compliance with the EC regulations
●
●
Protection from electrical interferences EN 61000-4-4
●
●
Dielectric strength 1500 VAC for 1 min. between output relay and FO
IN input, relay and power supply, and FO IN input and power supply
●
●
Reading range: -35°C to +195°C
●
●
Interface precision1% vfs, ±1 digit
●
●
Ambient operating temperature from
–20°C to +60°C
●
●
Permitted humidity 90% without condensate
●
●
Polycarbonate frontal film IP65
●
●
Container NORYL 94 _V0
●
●
Absorption 7.5VA
●
●
Self-diagnostic circuit
●
●
Electronic part protective treatment
Optional
Optional
DISPLAY AND DATA MANAGEMENT
2 x 13 mm displays with 3 digits to display temperatures, messages
and channels
●
●
3 LEDs to display the state of the alarms of the selected channel
(ALARM-TRIP-FAULT)
●
●
4 LEDS selection of display mode
(SCAN-AUTO-MAN-T.MAX)
●
●
2 LEDs to display the state of FAN1 and FAN2
●
●
Temperature control from 1°C to 190°C (alarms)
●
●
2 alarm thresholds for channels 1-2-3
●
●
2 alarm channels for channel 4
●
●
2 ON-OFF thresholds FAN 1 and FAN 2 ventilation
●
●
FO sensor diagnostics (FCC-FOC-FLT)
●
●
Data memory diagnostics (Ech)
●
●
Communication diagnostics FO 935 to CFO 521 (TEC)
●
●
Access to programming through front keyboard
●
●
Automatic exit from programming, display and relay test after 1
minute of inactivity
●
●
Incorrect programming warning
●
●
Selection between channels automatic scanning, hottest channel or
manual scanning (SCAN-AUTO-MAN)
●
●
Storage of maximum temperatures reached by channels and alarm
status (TMAX)
●
●
Front key to reset the alarms
●
●