6
NT935 ETH
TECHNICAL SPECIFICATIONS
NT935 ETH
POWER SUPPLY
Supply rated values
85-260 Vac-Vdc
50/60HZ
Vdc with reversible polarities
●
INPUTS
4 inputs for RTD sensors, Pt100 type with 3 wires (max section 1.5mm²)
●
Connections on removable terminal strips
●
Input channels protected against electromagnetic interference
●
Cable compensation for thermistors
500m (1mm²)
OUTPUTS
2 alarm relays (ALARM AND TRIP) SPDT
●
1 sensor or operating failure (FAULT) relay SPST
●
Output relays with 10A-250Vac-res
COSФ=1 contacts.
●
2 ventilation management relays SPST FAN 1 AND FAN 2
●
Ethernet output 10Base T / 100Base-TX Modbus TCP slave.
●
DIMENSIONS
100x100 mm
– din43700-depth 131mm (terminal block included)
Hole 92 x 92 mm
TESTS AND PERFORMANCE
Construction in compliance with CE regulations
●
Protection from electrical interference EN 61000-4-4
●
Dielectric strength 1500 Vac for a min. between output relays and sensors, relays and power
supply, power supply and sensors
●
Accuracy ±1% vfs, ±1 digit
●
Ambient operating temperature from
–20°C to +60°C
●
Humidity 90% non-condensing
●
Frontal film polycarbonate IP65
●