Infrared pir motion sensor switch installation
Connection-weir sketch diagram
•
Switch off the power.
•
Please moving the upper cover with anti-clockwise whirl as per the diagram in
the crust.
•
Fix the bottom on the selected position with the inflated screw
•
Connecting the power and the load to sensor as per the connection-wire
sketch diagram.
•
Buttoning the upper cover on the sensor, whirling the cover with clockwise
Test
•
Turn the LUX knob clockwise on the maximum(sun), turn the TIME knob anti-clockwise
on the minimum, turn the SENS knob clockwise on the maximum.
•
When you switch on the power, the controlled load and indication lamp are both not
working. Preheat 30 seconds later, the load and the indicator lamp are turned on syn-
chronization, in the absence of no inductor signals, the load should be stopped working
within 5-30sec, the indicator lamp is turned off.
•
After the first is out, make it sense again after 5~10sec. The load should work. When
there is no inductor signals in the indicator lamp, the load should be stopped working
within 5-15sec.
•
Turn ambient light knob anti-clockwise on the minimum. If it is adjusted in the less than
3LUX, the inductor load should not work after load stop working. If you cover the detec-
tion window with the opaque objects (towel etc), the load work .under no induction signal
condition, the load should stop working within 5-15sec.