MONARCH SINGLE PHASE INDUCTION MOTORS 

INSTRUCTIONS FOR HANDLING, INSTALLATION AND MAINTENANCE

 

 

 

 

 

Kind of Fault 

Symptom 

Cause 

Remedy 

Insufficient capacity of 
switch 

Replace switch 

Switch overheat 

High load 

Lighten load 

Misalignment between 
motor and load 

Re-align 

Overload after 
Start 

Bearing Overheat 

High bearing noise 

Replace damaged 
bearing 
Reduce load 
Increase power supply 
Decrease extension lead 
length 
Increase current carrying 
capacity of extension 
lead 

Motor does 
not start 

Motors hums and / 
or does not 
accelerate 

Load too great 
Power supply is not 
sufficient 
Extension lead used 

Move power supply 
towards motor. 

Occurrence from first 
operation 

Check noise not normal 

Electro-magnetic 
noise induced by 
electricity 

Sudden sharp noise and 
smoking 

Short circuit of windings. 
Repair. 

Bearing noise 

Excessive noise 

Replace the damaged 
bearing 

Loose belt sheaf 

Adjust key and lock the 
screw 

Loose coupling 

Adjust the position of 
couplings and tighten 

Loose screw 

Tighten screw 

Mechanical noise 
caused by 
machinery 

Fan rubbing 

Adjust fan position 

Rubbing as a result of 
ingress of foreign matter 

Clean motor interior and 
ventilation ducts 

Wind noise 

Noise induced by air 
flowing through 
ventilation ducts 

Noise 

Mechanical noise 
caused by 
machinery 

Induced by conveyance 
machine 

Repair machine 

Short circuit of windings 

Repair 

Electro-magnetic 
vibration 

Open circuit of rotor 

Repair 

Unbalanced rotor 

Repair 

Vibration 

Unbalanced fan 

Repair 

Broken fan blade 

Replace fan 

Un-symmetrical centres 
between belt sheaf 

Align central points 

Central points of 
couplings do not lie on the 
same level 

Adjust the central points 
of couplings on the same 
level 

Improper mounting 
installation 

Lock the mounting screw 

Vibration 

Mechanical 
vibration 

Motor mounting bed is not 
strong  

Reinforce mounting bed 

 

 
 
 
 
 
 
 

 

 

Summary of Contents for MONARCH ML Series

Page 1: ...MONARCH Single Phase Induction Motors 0 18 kW to 3 kW MON SP Mk II 042004 TECO Australia Pty Ltd...

Page 2: ...esigned in such a way that vibration is avoided when the motor and the driven machine are running coupled Care should be taken to ensure that any condensate drain plugs are located at the lowest point...

Page 3: ...ECTION ANTI CLOCKWISE DIRECTION V2 Z2 U2 V2 U1 V1 Z1 U1 V1 Z1 240 VOLTS 240 VOLTS MY ML 1 1 KW AND SMALLER U2 V2 U2 V2 Cs Cs C S Cr C S Cr W2 W3 U3 V3 2 W3 U1 V1 W1 U1 V1 W1 240 VOLTS 240 VOLTS U2 V2...

Page 4: ...ompany Switch off Switch on No fuse Install fuse Broken wires Check wires and repair Broken lead Check leads and repair Motionless And soundless Faulty winding Check winding and repair Overload trippe...

Page 5: ...ise Excessive noise Replace the damaged bearing Loose belt sheaf Adjust key and lock the screw Loose coupling Adjust the position of couplings and tighten Loose screw Tighten screw Mechanical noise ca...

Page 6: ...8 5 7 9 5 1 5 90S 8 7 2800 76 0 95 2 5 1 8 5 8 12 5 2 2 90L 12 5 2800 77 0 95 2 5 1 8 5 8 14 3 100L 16 7 2800 79 0 95 2 5 1 7 6 0 20 5 4 Pole 1500 RPM Rated Power kW Frame Size Current Amps IN Speed...

Page 7: ...MONARCH SINGLE PHASE INDUCTION MOTORS INSTRUCTIONS FOR HANDLING INSTALLATION AND MAINTENANCE NOTES 7...

Page 8: ...71 0 95 0 32 1 7 4 0 13 1 5 90L 9 0 1400 73 0 95 0 3 1 7 4 6 16 Dimensions Capacitor Start Run MY series Bolt on feet Multi mount construction TECO Australia Pty Ltd www teco com au email emd teco com...

Reviews: