28
Getting Started
5.3
Remote control
In this example external signals are used to control the
VSD/motor.
A standard 4-pole motor for 400 V, an external start
button and a reference value will also be used.
5.3.1 Connect control cables
Here you will make up the minimum wiring for starting.
In this example the motor/VSD will run with right rota-
tion.
To comply with the EMC standard, use screened control
cables with plaited flexible wire up to 1.5 mm
2
or solid
wire up to 2.5 mm
2
.
3. Connect a reference value between terminals 7
(Common) and 2 (AnIn 1) as in Fig. 36.
4. Connect an external start button between terminal
11 (+24 VDC) and 9 (DigIn2, RUNR) as in Fig. 36.
Fig. 36 Wiring
5.3.2 Switch on the mains
Close the door to the VSD. Once the mains is switched
on, the internal fan in the VSD will run for 5 seconds.
5.3.3 Set the Motor Data
Enter correct motor data for the connected motor. The
motor data is used in the calculation of complete oper-
ational data in the VSD.
Change settings using the keys on the control panel.
For further information about the control panel and
menu structure, see the chapter 9. page 41.
Menu [100], Preferred View is displayed when started.
1. Press
to display menu [200], Main Setup.
2. Press
and
then to display menu [220], Motor
Data.
3. Press
to display menu [221] and set motor volt-
age.
4. Change the value using the
and
keys. Con-
firm with
.
5. Set motor frequency [222].
6. Set motor power [223].
7. Set motor current [224].
8. Set motor speed [225].
9. Set power factor (cos
ϕ
) [227].
10.Select supply voltage level used [21B]
11.[229] Motor ID run: Choose Short, confirm with
and give start command
.
The VSD will now measure some motor parameters.
The motor makes some beeping sounds but the
shaft does not rotate. When the ID run is finished
after about one minute ("Test Run OK!" is displayed),
press
to continue.
12.Use AnIn1 as input for the reference value. The
default range is 4-20 mA. If you need a 0-10 V refer-
ence value, change switch (S1) on control board
and set [512] Anln 1 Set-up to 0-10V.
13.Switch off power supply.
14.Connect digital and analogue inputs/outputs as in
15.Ready!
16.Switch on power supply.
5.3.4 Run the VSD
Now the installation is finished, and you can press the
external start button to start the motor.
When the motor is running the main connections are
OK.
X2
X3
X1
1
12
22
11
41
42
43
31
32
33
51
52
2
3
4
5
6
7
8
9
10
13
14
15
16
17
18
19
20
21
Start
Reference
4-20 mA
+
0V
NEXT
ENTER
ENTER
NEXT
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
RESET
Summary of Contents for F33 Series
Page 1: ...TECO F33 Variable Speed Drive Instruction manual English Software version 4 2X...
Page 3: ......
Page 33: ...30 Getting Started...
Page 51: ...48 Main Features...
Page 53: ...50 EMC and Machine Directive...
Page 59: ...56 Operation via the Control Panel...
Page 65: ...62 Serial communication...
Page 159: ...156 Troubleshooting Diagnoses and Maintenance...
Page 165: ...162 Options...
Page 179: ...176 Technical Data...
Page 187: ...184 Menu List...