INTRODUCTION
Wind speed measurement series is composed of the three instrument: Type A(Temperature/Vane
anemometer).
It is normally used to measure air speed and temperature.
•
To guarantee correct readings: position instrument so that flow impacts at the rear.
• Do not press the vane sensor.
•
The vane sensor should aim at the wind direction.
• When performing the temperature and humidity measurenment, in order to ensure the accuracy
of the measurement readings, all the interference sources which may affect the measurement
result about temperature and humidity (such as the hand) must be away from the sensor.
DURING USE
FEATURES
1.
Display: the top display line always shows the velocity or volume, the bottom display line
always show the temperature or humidity.
2. Parameters:
Velocity: m/s,km/h,fpm,mph,kts,Beaufort
Temperature: °C,°F
3. Resolution:
Velocity: 0.1m/s, fpm
Temperature: 0.1°C 0.1°F
4. Range:
Velocity: 0.4 ~ 20m/s, 80 ~ 4000fpm
Temperature: -10 ~ 50°C, 14 ~ 122°F
5. Accuracy:
Velocity: ± (2% of r 0.3m/s)
± (2% of r 60fpm)
Temperature: ±1°C ±1.8°F
6. Sample rate: 2 time /sec
7. Operating environment:
-10°C ~ 50°C(14°F~122°F), 0~80%RH
8. Storage environment:
-20°C ~ 60°C(-4°F~140°F),0 ~ 80%RH