Tecnologic TLZ 11 P Operating Instructions Manual Download Page 4

It is also possible to prevent activation of the output after the
instrument is turned on, for the time set in the parameter 

“od”

.

The function is disabled by “od” = OFF.

During the power on delay phase, the display shows the indication

od,

 alternating with the normal programmed visualisation.

4.4 - ALARM FUNCTIONS

The alarm functions of the instrument work on the led AL, on the
internal buzzer (if present) and on the output AL (if present)

The buzzer are activated in alarm conditions and can be disabled
(alarm silencing) manually by pressing any key of the instrument .

Any active alarm is shown on the instrument display with the
lighting up of the AL led .

Any silenced alarm status is shown by the  AL led flashing .
The output AL are activated in alarm status but cannot be disabled

manually and are therefore only disabled when the alarm status
ceases.

The alarm conditions of the instrument are:
- Probe errors “E1”, “-E1”

- temperature alarms “HI” and  “LO” 
- External alarms “AL”

4.4.1 -  TEMPERATURE ALARMS

The temperature alarms, that are relative type, work according to

the probe measurement, the alarm thresholds set in parameters

“HAL”

 (maximum alarm) and 

“LAL”

 (minimum alarm) and the

relative differential 

“dAL”.

Using some  parameters  it is also possible to delay the

enablement and the intervention of these alarms.
These parameters are:

“PAL”

 - is the temperature alarm exclusion time on switching on

the instrument if the instrument is in alarm status when it is
switched on.

“ALd”

 - is the temperature alarm delay activation time

The temperature alarm is enabled at the end of exclusion time and
is enabled after the “ALd” time when the temperature measured  by

the probe exceeds the value  [”SP”+”HAL”] or or goes below the
value [”SP”-”LAL”].

The maximum and minimum temperature alarms can be disabled
by setting the relative parameters "HAL" and "LAL" = OFF. 

At the same time as the signalling of the alarm device (buzzer and
output AL), the instrument signals the alarm by turning on the led

light AL, and visualises on the display:
- Alternately 

HI

 and the measured temperature for maximum alarm 

- Alternately 

LO

 and the measured temperature for the minimum

alarm

tim e

d A L

d A L

A L

o ff

O N

H I

L A L

S P

H A L

T e m p .

L O

o ff

o ff

O N

4.4.2 - EXTERNAL ALARM

The instrument can signal an external alarm by activating the digital

input with the function programmed as  “diF” = 3 (see par. 4.5).
At the same time as the signalling of the alarm (buzzer and/or

output), the instrument signals the alarm by turning on the led AL
and visualising 

AL

 and the measured temperature alternately on

the display.

4.5 - DIGITAL INPUT

The digital input present on the instrument accepts contacts free of
voltage, the function carried out is defined by the parameter 

“diF”

.

The parameter “diF” can be configured for the following functions:

= 0 , = 1, = 2, = -1, = -2

 - Digital input not active

= 3

 - External alarm signal with contact normally open: on  closing

the input the alarm is activated and the instrument visualises 

AL

and the measured temperature alternately on the display.

= -3

 - External alarm signal with contact normally closed : similar to

“diF”=3 but with function logic reversed.

4.6 - FUNCTIONING OF KEY “U”

The U key function can be defined by the parameter 

“USrb”

 and

can be configured for the following functions:

= OFF

 - The key U carries out no function.

= 1

 - Pressing the key for at least 1 second, it is possible to switch

the instrument from the ON status to Stand-by status and vice
versa.

4.7 - PARAMETERS CONFIGURATION BY “KEY01”

The instrument is equipped with a connector that allows the

transfer from and toward the instrument of the functioning
parameters through the device 

TECNOLOGIC KEY01

 with 

5 poles

connector.

This device it’s mainly useable for the serial programming of the
instruments which need to have the same parameters configuration

or to keep a copy of the programming of an instrument and allow its
rapid retransmission.

To use the device KEY01 it’s necessary that the device or
instrument are being supplied.

Instrument supplied and device not supplied

SUPPLY

Instrument supplied from the device

SUPPLY ADAPTER

12 VDC

AC SUPPLY 

For additional info, please have a look at the KEY01 instruction
manual.

5 - PROGRAMMABLE PARAMETERS TABLE

Here below is a description of all the parameters available on the
instrument. Some of them may not   be present, either due to the

fact they  depend on the type of instrument or because they are
automatically disabled as unnecessary.

2.0

0.0 ÷ 30.0

°C/°F

Differential

HSEt

8

2.0

OFF ÷ 20.0

sec

Measurement filter

FiL

7

On

On - OFF

Decimal point

dP

6

°C

°C - °F

Unit of measurement

Unit

5

0.0

-30.0 ÷ 30.0

°C/°F

Probe  Calibration

OFS

4

Pt10

Pt10 - Entc

Probe Type:
Pt10= Pt1000

Entc= NTC (PT-24C2)

SEnS

3

500.0

SPLL ÷ 932.0

Maximum Set Point 

SPHL

2

-99.0

-99.9 ÷ SPHL

Minimum Set Point 

SPLL

1

Note

Def.

Range

Description

Par.

TECNOLOGIC spa - TLZ 11

 

P

 

- OPERATING INSTRUCTIONS - Vr.01  - 09/05 - ISTR 06947 - PAG. 4

Summary of Contents for TLZ 11 P

Page 1: ...UNCTION OF KEY U 4 6 DIGITAL INPUT 4 5 EXTERNAL ALARM 4 4 2 TEMPERATURE ALARMS 4 4 1 ALARM FUNCTIONS 4 4 COMPRESSOR PROTECTION FUNCTION AND DELAY AT POWER ON 4 3 TEMPERATURE CONTROL 4 2 MEASURING AND VISUALIZATION 4 1 FUNCTIONS 4 ELECTRICAL WIRING DIAGRAM 3 4 ELECTRICAL CONNECTIONS 3 3 MECHANICAL MOUNTING 3 2 PERMITTED USE 3 1 INFORMATION ON INSTALLATION AND USE 3 ON STAND BY FUNCTION 2 5 PARAMETE...

Page 2: ...first parameter and it will be possible to set the parameters of the instrument using the same programming procedure described previously Once the parameter has been selected and the SET is on it means that the parameter can be programmed even on the first level visible If the LED is off it means that the parameter can only be programmed on this level i e hidden To change the visibility of the par...

Page 3: ... mode programmed on the parameter Func the differential is automatically considered by the regulator with positive values for a Refrigeration control Func CooL or with negative values for a heating control Func HEAt In the event of probe error it is possible to set the instrument so that that the output OUT continues to work in cycles according to the times programmed in the parameter tonE activat...

Page 4: ... as diF 3 see par 4 5 At the same time as the signalling of the alarm buzzer and or output the instrument signals the alarm by turning on the led AL and visualising AL and the measured temperature alternately on the display 4 5 DIGITAL INPUT The digital input present on the instrument accepts contacts free of voltage the function carried out is defined by the parameter diF The parameter diF can be...

Page 5: ... is limited to repairs or to the replacement of the instrument The eventual opening of the housing the violation of the instrument or the improper use and installation of the product will bring about the immediate withdrawal of the warranty s effects In the event of a faulty instrument either within the period of warranty or further to its expiry please contact our sales department to obtain autho...

Page 6: ...racy Pt1000 0 5 fs 1 digit NTC PT 24C2 1 fs 1 digit Sampling rate 130 ms Display 4 Digit Red h 12 mm Compliance ECC directive EMC 89 336 EN 61326 ECC directive LV 73 23 and 93 68 EN 61010 1 7 5 INSTRUMENT ORDERING CODE TLZ 11 a b c d ee P a POWER SUPPLY H 100 240 VAC L 24 VAC VDC F 12 VAC VDC b OUTPUT OUT TYPE S Relay SPDT 16A AC1 R Relay SPST NO 16A AC1 c ALARM OUTPUT R Relay None d INTERNAL BUZZ...

Reviews: