FOREWORD

This manual contains the information
necessary for the product to be installed
correctly and also instructions for its
maintenance and use; we therefore recommend
that the utmost attention is paid to the following

instructions and to save it.
This document is the exclusive property of TECNOLOGIC
S.p.A. which forbids any reproduction and divulgation , even
in part, of the document, unless expressly authorized. 
TECNOLOGIC S.p.A. reserves the right to make any formal or
functional changes at any moment and without  any notice.
Whenever a failure or a malfunction of the device may cause
dangerous situations for persons, thing or animals, please
remember that the plant has to be equipped with additional
devices which will guarantee safety.
Tecnologic S.p.A. and its legal representatives do not assume
any responsibility for any damage to people, things or animals
deriving from violation, wrong or improper use or in any case
not in compliance with the instrument’s features.

INDEX

INSTRUMENT ORDERING CODE

7.5

FUNCTIONAL DATA

7.4

MECHANICAL DIMENSIONS, PANEL CUT-OUT AND
MOUNTING

7.3

MECHANICAL DATA

7.2

ELECTRICAL DATA

7.1

TECHNICAL DATA

7

GUARANTEE AND REPAIRS

6.3

CLEANING

6.2

SIGNALLING

6.1

PROBLEMS , MAINTENANCE AND GUARANTEE

6

PROGRAMMABLE PARAMETERS TABLE

5

PARAMETERS CONFIGURATION BY KEY01

4.7

FUNCTION OF KEY “U”

4.6

DIGITAL INPUT

4.5

EXTERNAL ALARM

4.4.2

TEMPERATURE ALARMS

4.4.1

ALARM FUNCTIONS

4.4

COMPRESSOR PROTECTION FUNCTION AND DELAY

AT POWER-ON

4.3

TEMPERATURE CONTROL

4.2

MEASURING AND VISUALIZATION

4.1

FUNCTIONS

4

ELECTRICAL WIRING DIAGRAM

3.4

ELECTRICAL CONNECTIONS

3.3

MECHANICAL MOUNTING

3.2

PERMITTED USE

3.1

INFORMATION ON INSTALLATION AND USE 

3

ON / STAND-BY FUNCTION

2.5

PARAMETERS PROGRAMMING LEVEL

2.4

PARAMETER PROTECTION USING THE PASSWORD

2.3

PARAMETERS PROGRAMMING

2.2

PROGRAMMING OF SET POINT 

2.1

PROGRAMMING

2

FRONT PANEL DESCRIPTION

1.2

GENERAL DESCRIPTION

1.1

INSTRUMENT DESCRIPTION

1

1 - INSTRUMENT DESCRIPTION

1.1 - GENERAL DESCRIPTION

TLZ 11 P is a digital microprocessor based thermocontroller for

Heating or Cooling applications and ON/OFF control mode. 
The instrument has up to 2 relay outputs, one input for Pt1000 or

NTC (PT-24C2 up to 300°C)  temperature probes and a digital
input, that can be configured.

The 2 outputs can be used for controlling the temperature control
device (OUT) and an alarm (AL).

The instrument is equipped with 4 programme keys, a 4-digit
display and 2 LED signals, in addition to an internal buzzer that is

the sound system for alarms.
Other important characteristics of the instrument are: programme

parameters protection using personalised password, switching on
and off (stand-by) of the instrument using the “U” front key,

configuration of parameters via the KEY 01 device and the
possibility of power supply in the range 100 ... 240 VAC.

1.2 - FRONT PANEL DESCRIPTION

TLZ 11

1

5

2

3

4

Out

AL

7

6

1 - Key P

 : Used for setting the Set point and for programming the

function parameters

2 - Key DOWN

 : Used for decreasing the values to be set and for

selecting the parameters.

TECNOLOGIC spa - TLZ 11

 

P

 

- OPERATING INSTRUCTIONS - Vr.01  - 09/05 - ISTR 06947 - PAG. 1

Summary of Contents for TLZ 11 P

Page 1: ...UNCTION OF KEY U 4 6 DIGITAL INPUT 4 5 EXTERNAL ALARM 4 4 2 TEMPERATURE ALARMS 4 4 1 ALARM FUNCTIONS 4 4 COMPRESSOR PROTECTION FUNCTION AND DELAY AT POWER ON 4 3 TEMPERATURE CONTROL 4 2 MEASURING AND VISUALIZATION 4 1 FUNCTIONS 4 ELECTRICAL WIRING DIAGRAM 3 4 ELECTRICAL CONNECTIONS 3 3 MECHANICAL MOUNTING 3 2 PERMITTED USE 3 1 INFORMATION ON INSTALLATION AND USE 3 ON STAND BY FUNCTION 2 5 PARAMETE...

Page 2: ...first parameter and it will be possible to set the parameters of the instrument using the same programming procedure described previously Once the parameter has been selected and the SET is on it means that the parameter can be programmed even on the first level visible If the LED is off it means that the parameter can only be programmed on this level i e hidden To change the visibility of the par...

Page 3: ... mode programmed on the parameter Func the differential is automatically considered by the regulator with positive values for a Refrigeration control Func CooL or with negative values for a heating control Func HEAt In the event of probe error it is possible to set the instrument so that that the output OUT continues to work in cycles according to the times programmed in the parameter tonE activat...

Page 4: ... as diF 3 see par 4 5 At the same time as the signalling of the alarm buzzer and or output the instrument signals the alarm by turning on the led AL and visualising AL and the measured temperature alternately on the display 4 5 DIGITAL INPUT The digital input present on the instrument accepts contacts free of voltage the function carried out is defined by the parameter diF The parameter diF can be...

Page 5: ... is limited to repairs or to the replacement of the instrument The eventual opening of the housing the violation of the instrument or the improper use and installation of the product will bring about the immediate withdrawal of the warranty s effects In the event of a faulty instrument either within the period of warranty or further to its expiry please contact our sales department to obtain autho...

Page 6: ...racy Pt1000 0 5 fs 1 digit NTC PT 24C2 1 fs 1 digit Sampling rate 130 ms Display 4 Digit Red h 12 mm Compliance ECC directive EMC 89 336 EN 61326 ECC directive LV 73 23 and 93 68 EN 61010 1 7 5 INSTRUMENT ORDERING CODE TLZ 11 a b c d ee P a POWER SUPPLY H 100 240 VAC L 24 VAC VDC F 12 VAC VDC b OUTPUT OUT TYPE S Relay SPDT 16A AC1 R Relay SPST NO 16A AC1 c ALARM OUTPUT R Relay None d INTERNAL BUZZ...

Reviews: