OPERATIONAL DESCRIPTION 

The catalytic Pellistor sensor is practically insensitive to humidity and temperature variations. The calibration is car-
ried out for the specific gas to be detected. Anyway, it can contemporaneously detect any other flammable gas that 
should be present in the same environment. 

Preheating

: when powered, the sensor needs a time of preliminary heating of about 60 seconds. During this peri-

od the yellow LED “

FAULT

” flashes. After this period, the yellow LED light off, the green LED “

ON

” illuminates to in-

dicate normal functioning. After this period the unit is able to detect gas even if it attains the optimum stability con-
ditions after about 4 hours continual functioning.  

Normal operation

: the green LED “ON” should be light on. 

The 1st° Red LED

 (

ALARM 1

) illuminates when the Gas concentration attains 1st alarm level and after about 12 

seconds, the “ALARM 1" relay will activate. 

The 2nd Red LED

 (

ALARM 2

) illuminates when the Gas concentration attains 2nd alarm level and after about 30 

seconds, the “ALARM 2" relay will activate. 

The 3rd Red LED

 (

ALARM 3

) illuminates  when the Gas concentration attains 3rd alarm level and after about 60 

seconds, the “ALARM 3" relay will activate. 

Faults

the instrument signal different kind of failures, as listed below. The Yellow LED illuminates, the "

S

" output 

falls down to 0mA and the “

FAULT

 normally activated relay deactivate. The "

FAULT

" relay, if necessary, can be used 

both to signal remotely an occurred damage and to signal the absence of power to the instrument. 

Yellow LED illuminates each 4 seconds (

with Green LED activate

):

 

this happens when the “

Cartridge Sensor

” has 

overcome its period of life (about 5 years) and its correct operation is no longer guaranteed. The detector keeps on 
operating  normally  but  it  is  necessary  to  replace,  as  soon  as  possible,  the  “

Cartridge  Sensor

”  with  a  new  one.  The 

type to be required is listed in 2

nd

 column 

Table 4

. The replacement procedure is described in the attached manual. 

Yellow  LED  activates,  Green  LED  off  (

FAULT  relays  activate  and  0mA  output  signal

):

 

this  signal  different  kind  of 

faults. 

1)

  The  Dip  Switch  set  up  is  wrong,  please  verify  (

see  Table  2-3

). 

2)

  The  “

Cartridge  Sensor

”  is  not  working, 

please  replace  with  new  one. 

3)

 

If  a  new

 

Cartridge  Sensor

”  is  installed  or  it  is  not  correctly  connected  or  a  not 

compatible one is mounted. Please check the cartridge connections and compatibility (

see Table 4

) these checks are 

made connecting and disconnecting the device.

 

If the condition does not change, it will be necessary to replace the 

unit and/or send it back to the supplier to repair. 

Yellow and Green LED activates (

FAULT relays activate and 0mA output signal

):

 

this happens when the “

Cartridge 

Sensor

” is not working. First try to perform the procedure of “

ZERO

” as described in the section

 “Test and Calibra-

tion  >  Zero  adjust”

 

then  disconnect  and  connect  the  unit,  finally  try  to  replace  a  new 

“Cartridge  Sensor

”.  If  the 

condition is not change, it will be necessary to replace the unit and/or send it back to the supplier to repair. 

All LED activate (

FAULT relays activate and >24mA output signal

):

 

this happens  when the “

Cartridge Sensor

”  is not 

working or gas concentration is out of scale (higher than 100%LEL) If there are not any gas leaks and the condition 
is not change, it will be necessary to replace the unit and/or send it back to the supplier to repair. 

INSTALLATION 

The detector must be accurately installed according to the national dispositions in force on the safety of the plants 
and installation of electric devices in areas with danger of explosion. 

Mounting

: The 

Fig. 2

 shows the instrument size. The unit must be positioned vertically with the sensor downwards. 

Models SE237PG 

should be fixed at 20-30 cm from the floor (LPG and Petrol vapours are heavier than air). 

Models SE237PM

 should be fixed at 20-30 cm from the ceiling (Methane and Hydrogen are lighter than air). 

Models SE237PI

 should be fixed at 20-30 cm from the ceiling (Methane and Hydrogen are lighter than air). 

Models SE237PB 

should be fixed at 20-30 cm from the floor (LPG and Petrol vapours are heavier than air). 

Models SE237PX 

should be fixed in high position with a gas Vapour Density less than 1 (the gas is lighter than air) 

or in bottom position with a density greater than 1, (the gas is heavier than air) 

(

see Table 4 column 4

).

 

Electrical Connection (

see Fig.2

)

: the maximum distance to install each detector from the power supply show in the 

Table 1

. If more than one detector is to be powered in parallel, it is necessary to consider the voltage drop across 

the supply cable. Normally use a two wire cable (

not shielded

) for power  the conductors for output relay. 

If 

the output signal is used in mA, please use 3 conductors screened  conductors for relay output. The max 
load resistor is 50 ohm with 12Vdc 

(-10%

) power supply, while is 500 ohm with 24Vdc 

(-10%

) power supply (

see fig.4

). 

Power Supply terminals, on the main board, are plug-in type, it is necessary to extract them to make the connection. 
Pay attention when you insert them again, being polarized. The relays terminals, on outputs board, are fixed.

 

The 

sealed relays are

 

tension free 

SPST (

S

ingle 

P

ole 

S

ingle 

T

hrow)

 

contacts and should be set NO (Normally Open) or NC 

(Normally Closed) by positioning the 4th Dip-Switch (

see Table 3

). With the

 

Dip-Switches from 1 to 3 the concentra-

tion for alarm activations is determined. 

Note: Dip-Switch should be set with instrument powered off. Dip-Switch settled in reserved position acti-

vate Fault indications (see “Operational Description > Faults”). 

Important

:

  Once  installation  is  completed,

  power  up  the  unit, 

wait  about  20÷30  minutes  and  then, 

only  if  it  is 

necessary

to adjust the sensor to the environment conditions,

 carry out the 

Zero Adjust 

(

see 

Test and Calibration

)

.

 

WARNING 

Average life

: The sensitive element used in this detector has an excellent stability in time. In fresh air and in nor-

mal working condition the sensor's life is about 5 years from the date of installation. After this period the yellow LED 

FAULT

” flashes every 4 seconds, is necessary replacing the “

Cartridge Sensor

”. 

Summary of Contents for SE237P Series

Page 1: ... relays relais 24V 1A SPST 4 20 mA Lineare Linear linéaire Campo di misura Standard Range Champ de mesure 0 100 LIE LEL Limite Scala Limits Limite échelle 100 LIE LEL Vita media in aria pulita Average Life in fresh air Vie moyenne en air pur 5 anni years ans Tempo di risposta Response Time Temps de réponse T90 60 secondi seconds secondes Ripetibilità Repeatability Répétabilité 5 del segnale signal...

Page 2: ...ULT Dopo circa 60 secondi il Led giallo si spegne e si accende il Led verde ON che indica il normale funzionamento Dopo questo tempo il sensore è in grado di rilevare il gas ma raggiunge le condizioni di stabilità ottimali dopo circa 4 ore di funzionamento continuo Funzionamento Normale deve essere acceso il solo Led Verde ON Il 1 Led Rosso ALARM 1 si accende se la concentrazione di Gas supera la ...

Page 3: ...le in cui è installato o all interno dei muri o sotto il pavimento Importante Il sensore catalitico Pellistor funziona solo in presenza d Ossigeno Non usare gas puri o l accendino direttamente sul sensore che potrebbe essere irrimediabilmente danneggiato ATTENZIONE Considerare che in ambienti particolarmente inquinati o con vapori di sostanze infiammabili in par ticolare i solventi la vita utile d...

Page 4: ...isultato è diverso è opportuno eseguire la Calibrazione Terminata la Verifica chiudere la bombola togliere il TC011 NOTA In aggiunta a quanto sopra se si usa anche l uscita in mA controllare anche con i puntali del voltmetro sui Test Point TESTmA vedi Fig 2 si raggiunga il valore in mV indicato in Tabella 4 Colonna 6 ovvero che l uscita in mA au menti fino a circa il valore indicato nella Colonna ...

Page 5: ...e unit finally try to replace a new Cartridge Sensor If the condition is not change it will be necessary to replace the unit and or send it back to the supplier to repair All LED activate FAULT relays activate and 24mA output signal this happens when the Cartridge Sensor is not working or gas concentration is out of scale higher than 100 LEL If there are not any gas leaks and the condition is not ...

Page 6: ...2 this function is to adjust the Zero sensor and can be done in clean air only environment without the presence of gas or other pollutants Immediately after having inserted the Zero Code as a confirmation of the operation carried out there will be 1 flash of the 1 red Led and the output will be come 4 0 mA We suggest performing this operation only if the 1st Red LED is on or output is different fr...

Page 7: ...r est 1 56 pour le Propane et 2 05 pour le butane la LIE est 1 7 v v pour le propane et 1 4 v v pour le butane Les étalonnages pour GPL doi vent être exécutés pour gaz butane qui est l élément le plus présent dans le GPL Le SE237PI permet de détecter l hydrogène H2 qui est le plus léger gaz existant il est inodore sans couleur ex trêmement inflammable Sa densité relative à l air est 0 07 et sa LIE...

Page 8: ...t nécessaire de calculer la chute de tension sur les portions communes des câbles Un câble sans écran est normalement utilisé avec 2 conducteurs pour l alimentation les conducteurs pour les sorties relais Dans le cas ou l on utilise également le signal de sortie en 4 20 mA il convient d utiliser du câbles à écran à 3 conducteurs les conducteurs pour les sorties relais Si l on utilise une alimentat...

Page 9: ...Code de Etalonnage F2 F2 F2 F1 F2 F1 cette fonction permet l étalonnage du capteur Durant la procédure une rare possibilité existe que la LED Jaune clignote chaque 8 secondes dans ce cas inter rompre la procédure puis exécutez le contrôle en coupant et en rétablissant l alimentation du détecteur En cas de persistance il sera nécessaire de remplacer et ou renvoyer le détecteur au fournisseur pour r...

Page 10: ...ella 4 Table 4 Tableau 4 ZSP IP Cartuccia Sensore Cartridge Sensor Cartouche Capteur 1 2 3 4 5 6 7 8 Modello e Gas Rilevato Model and detected Gas Modèle et Gaz détecté K LIE LEL v v Densità Densité Aria Air 1 NOTA 1 NOTE 1 REMARQUE 1 20 LIE LEL v v TESTmA TP1 TP2 mV Uscita Output Sortie mA LIE LEL SE237PM Metano Methane Méthane 1 4 4 0 55 0 88 72 7 2 20 SE237PG Butano Butane Butane 1 43 1 4 2 05 ...

Page 11: ...gamento Wiring diagram Schéma TESTmV TP2 TP1 Scheda Uscite Relé Relays Output Board Sortie sur Realis S 12 24V mA 12 24Vdc Alimentazione Power Supply Alimentation Fig 3 Tester di calibrazione Calibration Tester Kit de Calibration 0 3L min F1 F2 Tasti Key Touches TC011 TC014 Alimentazione Power Supply Alimentation 100 300 400 500 50 0 5 200 Vdc RL Resistenza di carico Load resistor Resistance de ch...

Reviews: