(Gas concentration below 10% LIE) the fault condition will be canceled anyway.It is therefore advisable to check that the solenoid valve is
not blocked and that the connecting cables with the solenoid valve are not interrupted.
INSTALLATION
The control unit and detectors should be installed
according to the national disposition in force on the matter.
Positioning:
The control unit must be installed in an accessible location, easily visible and away from heat sources.
The control unit cannot be installed outdoors.
Please note that for safety, the control unit is to be installed in safe areas where there are present or can form
flammable atmospheres and concentrations exceeding 24 % volume oxygen.
The remote detectors:
it has to be installed as described in the specific instructions attached with it. After the in-
stallation and referred to the gas indicated on the testing label of the remote
gas detector
, apply on the
SE293K
, the
self-sticking label with the name of the detected gas inserted
in the package
.
Valve:
The
manually resetting
solenoid
valve
for the gas cut-off should be installed outside the room in a clearly in-
dicated position and should be protected
from direct sunlight and rain
.
Mounting
:
The Fig.2
shows the instrument size. It has to be wall-mounted by four screw anchors.
The housing
opens and closes with the 4 screws on the cover.
IMPORTANT:
T
O AVOID IRREVERSIBLE DAMAGE
,
DISCONNECT THE POWER SUPPLY TO THE CONTROL PANEL
,
DURING INSTALLATIO
(
WIRING
CABLES
)
OR BEFORE UNPLUG OR RE
-
CONNECT THE FLAT CABLE
.
Only if necessary, for maintenance or installation requirements, the housing cover can be separated from its base,
first remove power supply, then disconnect the flat cable, press on the two side tabs as shown
in Fig. 3
.
To recon-
nect it, push the flat cable into the connector, respecting the polarization, the two levers close automatically locking
it. Only then you can reconnect power supply.
Cable glands
: the lower side of the housing has 3 inputs designed for metric cable glands (
M20x1.5 that accept
external cables Ø 6÷12 mm
). These passages are closed, but they are not
manually breakable
, according to the in-
stallation requirements, they must be drilling. To facilitate the operation, they have a centering for the drill bit.
Electrical Connection:
The installation must be provided for the mains, a bipolar disconnect switch dedicated for
the gas detection system. The device, clearly identified, must act only on Phase and Neutral. If it is necessary, you
may install a surge or lightning protector, etc.
The instrument is supply with non-reversible and plug-in terminals. Therefore the cables should be anchored to the
case in order to avoid terminal overstress. The connection to the Control unit does not need any hearting. The remote
sensor can be placed at a max. distance of 100 meters from the Control unit with a cable of 3x1.5mm
2
or to a distance
of 200 meters using a 3x2.5 mm
2
cable. It is not necessary to use shielded cables.
Fig. 4
shows the 110÷230VAC powering connection with alarm siren and normally open manual resetting valve.
Fig. 5
shows the 110÷230VAC powering connection with alarm siren and normally closed manual resetting valve.
Fig. 6
shows the 24VDC powering connection with both 24VDC alarm siren and normally closed manual resetting
valve with, for example, our power supply unit PS180/24VDC (max load 2,5A) with No.2 internal 12V/7Ah Pb battery
to maintain the system powered on in absence of Main power supply.
Dip-Switch Setting
:
Before powering unit, you must configure the Dip-Switches SW1 and SW2 on the circuit in
the
housing
cover.
Enable/Disable
:
SW1 Dip Switches No.1, No.2, No.3 enable or disable the corresponding in-
put of the remote gas detector (
SENSOR-1
,
SENSOR-2
and
SENSOR-3
).
(
No. 4 is not used and its position does
not affect the control unit functioning
).
ON = Enabled input:
the detector is installed, the measurement and the Alarms and Fault relays
are in operation. (
FOR DEAULTS ARE ALL CONFIGURED
ON
)
OFF = Input DISABLE
The detector is absent, the display shows
Sx off
. Fault relays and alarms do
not intervene. (
can also be used to exclude a faulty detector or removed for maintenance
).
SW2 Dip-Switch No.1 (RANGE) It is not used and its position has no effect on the operation.
SET ALARM
:
the SW2 Dip-Switches / No.2 and No.3 set the alarm thresholds.
See Table 2
.
No.2 and No.3 both OFF
=
ALARM 1
set to 10%LEL and
ALARM 2
set to 20%LEL (
DEFAULT
SETTING
)
No.2 ON and No.3 OFF
=
ALARM 1
set to 15%LEL and
ALARM 2
set to 20%LEL
LOGIC of Relay
: SW2 Dip-Switch No.4 sets the function of the
ALARM 2
relay.
ON = Negative logic
, the relay is de-energized, it is used for normally open valves.
OFF = Positive logic
, the relay is normally energized, in case of power failure or relay failure, it au-
tomatically moves to the alarm
position. It is used for normally closed valves.
WARNING
C
ONFIGURE
D
IP
-S
WITCHES BEFORE POWERING THE CONTROL PANEL
.
I
F
SW1
D
IP
-S
WITCHES WERE ALL
OFF,
DIP
SWITCH
SW1
ERROR
WILL BE
DISPLAYED
.
THE YELLOW
LED
AND THE
FAULT
R
ELAY WILL ACTIVATE
.
I
N THIS CASE TURN OFF THE CONTROL UNIT
,
SET
ON,
AT LEAST ONE OF THE
CHANNELS AND SWITCH ON THE CONTROL UNIT AGAIN
The detector
doesn't need adjustments
after being installed.
During
preheating of the detectors
, which is of about 60 seconds, the alarm relays remain inhibited, while the Yel-
low LED and the
FAULT
relay are activated.
In case of
short circuit between the connection cables to a detector
, the protection circuit interrupts to it the
power supply.
Both the
FAULT
relay and the yellow LED will activate. T
urn off the
SE293K
, remove the cause of the
short circuit, and then turn on the unit.