8.2.

 

Sensitivity, inertia and electrical parameters testing of the FD. 

8.2.1. For the testing assemble the circuit setup shown at Fig. 8.1. Switch on the power 
supply and submit a constant voltage (10 ... 30) V to the FD. Check the absence of FD auto-
triggering. 

8.2.2. Close the FD censor with opaque object and check the consumable current of FD in 
standby mode with the ammeter A, which should be less than 0.25 mA 
8.2.3.  Set  up  the  paraffin  candle 

Ǿ

  25  mm  at  the  distance  of  (4  ±  0,1)  m  from  the  FD 

sensor. 
8.2.4 Switch the measurement limit of ammeter A for measuring current of up to 50 mA. 
8.2.5  Open  the  FD  sensor  while  starting  the  stopwatch.  At  the  moment  of  the  FD  LED 
triggering  stop  the  stopwatch.  Determine  the  inertia  (timing)  by  the  stopwatch,  which 

should be no more than 5 seconds. 
8.2.6. By voltmeters V determine the voltage supplied to the FD in worn condition, which 
should not be more than 8 V. 

8.2.7. Determine the current consumed by the FD in worn condition with the ammeter A, 
which should be 20 + 10.2 mA. 
8.2.8.  Extinguish  the  candle.  Then  switch  off  the  power  supply  after  at  least  3  seconds. 
Please re-enable PSU power supply and check the FD is not triggered. 

8.2.9. Set the incandescent lamp 100 W x 220V at the distance (4 ± 0,1) m from the FD 
sensor and connect it to the network. Keep the FD the light of the lamp for 5 minutes, and 
check the FD is not triggered. 
8.2.10. Turn off the power supply. Disconnect the FD from scheme. The test is finished. 

 
8.3. In case of the FD break down please contact the manufacturer for warranty repair, 
for  the  post-warranty  repair  contact  the  manufacturer  or  the  specialized  repair 

organizations. 
 
 

POINT TYPE FLAME DETECTOR "ALMAZ" 

www.technotrade.ua

 

                                                                                               Page 12 of 27 

 

9. POSSIBLE MALFUNCTIONS AND TROUBLESHOOTING 

 

9.1. List of possible simple malfunctions and troubleshooting, see table 9.1. 

Table. 9.1. 

Failure description, 

outward manifestation and 

additional signs of 

malfunction 

 

Possible cause 

 

Solution 

1. LED indicator is off in the 
triggered state.  

Improper connection of 
alarm system loop.  

No contact between the 
wires loop and terminal 
block. 

 

Check the connection 
schemes according to 

Annexes 2, 3, 4 and 5. Check 
contacts and tighten screws 
of terminal block. 

2. On the alarm system 
console the signal "Loop 
fault" is detected. 

Missing end resistor. 

Check contacts and tighten 
screws of terminal block. 
Check the R

OK

 connection. 

3. Reduced sensitivity of 

the FD. 

The sensor is covered 

with dust. 

Clear the FD with cloth, 

moisturized with 
technical alcohol (see p. 8.2) 

 

 

 

 

 

 

 
 

Summary of Contents for ALMAZ

Page 1: ...ATIONS 4 4 PRODUCT SET CONTENTS 5 5 DEVICE AND ITS OPERATION PRINCIPLE 6 6 SAFETY REQUIREMENTS 7 7 INSTALLATION AND MOUNTING 8 8 TECHNICAL MAINTENANCE 10 9 POSSIBLE MALFUNCTIONS AND TROUBLESHOOTING 12 10 HANDLING AND STORAGE 13 11 CERTIFICATE OF ACCEPTANCE 14 12 MANUFACTURER WARRANTY 14 APPENDIX A 15 APPENDIX B 17 APPENDIX C 18 APPENDIX D 19 APPENDIX E 20 APPENDIX F 21 APPENDIX G 26 APPENDIX H 27 ...

Page 2: ...R ALMAZ www technotrade ua Page 4 of 27 3 TECHNICAL SPECIFICATIONS Sensitivity and inertia of operation 3 1 The sensitivity of the FD meets the intensity of ultraviolet radiation caused by fire of normalized test fire source of methane gas burner B1 and n heptane flame C1 under the DSTU EN54 10 mounted on the optical axis of the sensor of FD at a distance of 25 m corresponding to class 1 according...

Page 3: ...5 case 1 rotary device 2 5 2 2 Base of FD 4 is inextricably connected to the FD unit 5 and rotary device 2 The fire alarm system wires are connected to the FD through the cable input on the base Connection is made to the lower PCB connector of FD unit see Appendix B On the front surface of the FD unit there is a sensitive element UV detector 6 and 7 LED operation indicator Inside the FD unit there...

Page 4: ... the FD to DC power supply with an output voltage 10 30 V and with load current at least 50 mA The contact FD plug positive contact and the contact negative contact of power supply 7 5 2 Switch on the power supply and check for at least 5 minutes if FD is not auto triggered 7 5 3 Light a paraffin candle of 25 mm diameter or portable gas lighter with a flame height 3 4 cm hold it at a distance of n...

Page 5: ...g the FD operation Failure to comply with this requirement manufacturer is not responsible for the operation 8 1 2 Clean the glass surface of the aperture element of FD from dust and wipe it with a cloth moistened with industrial alcohol on the basis of 3 g of industrial alcohol per 0 04 m2 of rags per 10 FDs Then check the FD operation in the fire alarm system in the following sequence Switch the...

Page 6: ...ble PSU power supply and check the FD is not triggered 8 2 9 Set the incandescent lamp 100 W x 220V at the distance 4 0 1 m from the FD sensor and connect it to the network Keep the FD the light of the lamp for 5 minutes and check the FD is not triggered 8 2 10 Turn off the power supply Disconnect the FD from scheme The test is finished 8 3 In case of the FD break down please contact the manufactu...

Page 7: ... must be stored indoor providing protection from moisture solar radiation harmful fumes and mold POINT TYPE FLAME DETECTOR ALMAZ www technotrade ua Page 14 of 27 11 CERTIFICATE OF ACCEPTANCE Point type flame detector Almaz meets the technical conditions of TU 31 6 32251835 001 2010 Point Type Fire Flame Detector Almaz and found fit for use Stamp 12 MANUFACTURER WARRANTY Manufacturer guarantees tha...

Page 8: ...lmaz General view of the FD Figure A 1 General view of the FD 1 case 2 rotary device 3 cable input 4 base 5 quartz glass 6 UV detector 7 LED operation indicator POINT TYPE FLAME DETECTOR ALMAZ www technotrade ua Page 16 of 27 FD Unit Top view Figure A 2 FD Unit Top view Bottom view Figure А 3 Bottom view ...

Page 9: ... 3 connected in parallel Pins 2 4 connected in parallel POINT TYPE FLAME DETECTOR ALMAZ www technotrade ua Page 18 of 27 APPENDIX C Example circuit connection of FD Almaz to two wire fire alarm system Рисунок С 1 Figure C 1 NOTES 1 FD base pin assignment pin 1 wire connection pin 2 wire connection pin 3 wire connection pin 4 wire connection 2 ROK the end element of the alarm system loop which type...

Page 10: ...given in the user manual of the control panel used ATTENTION It is recommended to use the control panel with the grounded of supply loop POINT TYPE FLAME DETECTOR ALMAZ www technotrade ua Page 20 of 27 APPENDIX E Example of connection circuit of FD Almaz to the four wire fire alarm system normally shorted contacts Figure E 1 NOTES 1 FD base pin assignment pins 1 3 wire connection pins 2 4 wire con...

Page 11: ... off by a wall where the FD is mounted thus the controlled area Scon S S1 where S1 area cut off by the wall Because the controlled premises usually have a rectangular shape the quality of evaluative value of the area you can use the square inscribed in an ellipse rectangle SP 2 a b S1P 1 2 where S1P is the cut off the by wall area Scon and Sr values of the area for the FD Almaz depending on the he...

Page 12: ...of mounting the FD on the ceiling the configuration controlled area will look like a circle see Fig F 2 The value of controlled area circle is calculated with the formula 2 1 SCON π Lmax 2 H 2 2 1 where Lmax 2 H 2 R 2 R the radius of circle SCON area value depending on installation height of FD H the maximum range of flame ignition source Lmax and radius R are shown in Table F 2 Figure F 2 ...

Page 13: ...AME DETECTOR ALMAZ www technotrade ua Page 25 of 27 1 1 FD Almaz Δ 90 Lmax 50 м Тable F 2 POINT TYPE FLAME DETECTOR ALMAZ www technotrade ua Page 26 of 27 APPENDIX G Certificate of compliance with DSTU EN 54 10 2004 ...

Page 14: ...POINT TYPE FLAME DETECTOR ALMAZ www technotrade ua Page 27 of 27 APPENDIX H Certificate for quality management system ISO 9001 2009 ...

Reviews: