![technoswitch TEC247 Installation & Operation Manual Download Page 5](http://html.mh-extra.com/html/technoswitch/tec247/tec247_installation-and-operation-manual_1070613005.webp)
TEC247 Fire & Extinguishant Control Panel
– INSTALLATION & OPERATION MANUAL
DOC NO. PRMAN-0003 TEC247 Rev 04.12 191209.docx
- 4 -
E. &O.E.
4.
POWER SUPPLY
The internal power supply is a high efficiency switch-mode power supply with an input AC voltage range of
100-250 V AC. The power supply provides the following:
▪
27.5 V DC to the fire control panel electronic circuits
▪
Battery charging and monitoring
▪
LED fault indication
▪
Two relay outputs, one for Common PSU Fault and the other for an AC Input Fault
FIGURE 2
PCB-PSU2A
– POWER SUPPLY BOARD
NB:
If an external power supply is used to power the panel, all warranty claims will be null and void.
NB:
Care must be taken to earth the panel correctly. An earth lug is located inside the enclosure for this
purpose. Appropriate lugs should be used to terminate all cables.
NB:
Terminal blocks should be opened counter-clockwise at least 5 turns before inserting a cable and
tightening the contact. Failure to do so could cause malfunction of the installation.