Technische Alternative UVR61-3 Supplementary Instructions Manual Download Page 11

11 

 

Application 5 

Room drying with room temperature monitoring and 
“comfort ventilation” for a wine cellar 

The humidity should be lowered in a wine cellar. In order to ensure room air quality to a large extent, 
the fan is switched on for one time window regardless of the room temperature 

(“comfort ventilation”) 

even on days with humid exterior air. 
The fan for 

room drying

 runs if: 

-

 

the absolute

 exterior humidity is lower than the interior one 

and

  

-

 

the relative

 interior humidity is higher than e.g. 60% 

and

  

-

 

the room temperature is above the required temperature (example: 10C) 

and

 

-

 

the optional interval switch ("Timer") is active. 

The fan for “

comfort ventilation

” runs 

-

 

daily according to the time window regardless of other settings (example: 10:00 to 10:30 a.m.), 
up to three time windows can be set 

Recommended settings for UVR61-3 

Menu 

ENTER Par 

Code: 

32

 

 

Menu 

ENTER Men 

Code: 

64

 

Program 

PR

 

512 

 

 

EXT DL 

 

Linking of out-
put 

LO

 

OFF 

 

  Ext. Sensor E1 

11 

max 1 

 / 

 

75/70 

no effect

 

  Ext. Sensor E2 

21 

max 2 

 / 

 

100/95 

no effect

 

  Ext. Sensor E3 

12 

max 3 

 / 

 

50/45 

no effect

 

  Ext. Sensor E4 

22 

min 1 

 / 

  

2/1 

Start threshold for inside 

absolute

 

humidity in g/m³ (display: °C)

 

  Ext. Sensor E5 

14 

min 2 

 / 

 

62/60 

Start threshold for 

relative

 humidity in 

% (display: °C)

 

 

Ext. Sensor E6 

24 

min 3 

 / 

 

11/10 

Start threshold for room temperature in 
°C

 

diff 1 

 / 

 

1,0/0,5 

Minimum differential, absolute humidity 
outside - inside

 

 

SENSOR

  

(value transfer) 

diff 2 

 

-- 

Set diff 2 and diff 3 to "unused" (setting 
over 98 °C, display: --)

 

  Sensor S1 

E5 

diff 3 

 

-- 

  Sensor S2 

E6 

Sensor S3 

E1 

TIME W 

Sensor S4 

E2 

Time window 1 

 

Within this time window, the fan runs 
independently of the humidity and 
temperature conditions. 

  Sensor S5 

E3 

Outputs  

OPO 123 

  Sensor S6 

E4 

Time on/off 

10:0/10:30 

   

 

Timer

 

optional

 

 

 

Outputs  

OPA 1 

The fan is switched ON and OFF 
alternately (ON and OFF time in 
minutes). 

   

 

Release time 

00:10 

   

 

Block time 

00:10 

   

 

 

 

 

O1 

Auto 

 

 

 

O2 

Auto 

 

 

 

O3 

Auto 

 

 

 

 

With 

time window

 setting 

OPO 12

, “comfort ventilation” takes place only if the room temperature has 

exceeded the temperature threshold. 

 

Summary of Contents for UVR61-3

Page 1: ...y Building drying can be carried out with all universal controllers that have a DL bus with the excep tion of UVR63 H Goal Lowering humidity through specific ventilation with dry air Improvement of ai...

Page 2: ...y sensor must not be directly subjected to insolation or rain If neces sary the sensor will be protected with a small shield Operation The large display contains the symbols for all important informat...

Page 3: ...navigation keys The value is saved pressing the arrow key in upward direction View of the display after the first start of controller UVR61 3 Display after switching on The sensor values initially sho...

Page 4: ...r values in the menu SENSOR Access to menu ENTER Par and definition of the parameters Controller version Program number Linking of output First parameter value max1 Second parameter value max1 Value b...

Page 5: ...inking of output LO OFF Ext Sensor E1 14 max 1 75 70 no effect Ext Sensor E2 24 min 1 2 1 minimum humidity inside SENSOR value transfer diff 1 1 0 0 5 minimum humidity differential outside inside TIME...

Page 6: ...2 min3 9 If the temperature falls below this room temperature the fan is blocked diff1 1 0 0 5 minimum humidity differential outside inside SENSOR value transfer TIMER optional Sensor S1 E1 Outputs OP...

Page 7: ...runs Daily according to time window Recommended settings for UVR61 3 Menu ENTER Par Code 32 Menu ENTER Men Code 64 Program PR 129 EXT DL Linking of output LO OFF Ext Sensor E1 14 max 1 75 70 no effect...

Page 8: ...4 Interior room temperature Electrical connection UVR61 3 Output 3 must be made potential free For this the red jumper on the rear of the detacha ble upper controller part is removed Meaning of the lu...

Page 9: ...f the room temperature is high enough Recommended settings for UVR61 3 Men ENTER Par Code 32 Menu ENTER Men Code 64 Program PR 129 EXT DL Linking of output LO OFF Ext Sensor E1 14 max 1 75 70 no effec...

Page 10: ...ure Electrical connection UVR61 3 Output 3 must be made potential free For this the red jumper on the rear of the detachable upper controller part is re moved Meaning of the luminous digits 1 Fan oper...

Page 11: ...DL Linking of out put LO OFF Ext Sensor E1 11 max 1 75 70 no effect Ext Sensor E2 21 max 2 100 95 no effect Ext Sensor E3 12 max 3 50 45 no effect Ext Sensor E4 22 min 1 2 1 Start threshold for insid...

Page 12: ...he red jumper on the rear of the detachable upper controller part is re moved An external auxiliary relay whose contact is arranged in series with both other outputs is connected to output 2 We reserv...

Reviews: