![Technische Alternative RAS-PLUS Programming Installation Instructions Download Page 13](http://html1.mh-extra.com/html/technische-alternative/ras-plus/ras-plus_programming-installation-instructions_1069683013.webp)
13
ESR21, ESR31, UVR61-3, UVR63 and UVR63-H
:
Adjustment of the measurements takes place in the menu
EXT DL
(external sensors)
Example:
The external sensor 1 has address 1, the measured room tem-
perature is imported without offset values (index 2).
In the controllers ESR31, UVR61-3, UVR63 and UVR63-H (version 5.0 up
to 7.1), only the measured room temperature can be evaluated without off-
set values (index 2); the slider switch and the rotary knob have no purpose for these control-
lers. This value can subsequently be allocated to a sensor value (menu ENTER/Men – SEN-
SOR).
The room humidity value (only RAS-PLUS/F) is indicated in these controllers as a dimension-
less value without a decimal point (e.g. 35.5% -> Controller display: 355).
The values of indices 1 and 5 would be indicated with "999 and therefore cannot be used.
The menu option "
EXT DL
" is only available in the following controllers:
UVR 63-H from version 5.0
UVR 63 from version 1.0
UVR 61-3 from version 5.0
ESR 31 from version 1.0
ESR 21 from version 5.0
Entry of an offset value for sensor correction OFFSET
Entry COR 0.0 = no offset value selected,
therefore no sensor correction
Factory setting: COR 0.0
After a long key press "0.0" flashes
Selection of the desired offset value by
a short key press.
Confirmation of the desired value by a long
key press.
Entry COR +0.7 = The room temperature
value displayed and transmitted to the con-
troller is increased by 0.7 K.
Adjustment range
: - 5.0K to +5.0K
Example
: If there is an offset value of 0.7K and a measured temperature of 21.0°C, 21.7°C is
indicated (index value 1 and 2). This corrected value is used in the sequence for all calcula-
tions and forwarded to the controller.
Amongst those controllers that have no bidirectional data link (e.g. HZR65), i.e. amongst
those for which the
RAS-PLUS
can only be used as a
remote display
, this menu option is
still displayed but has no effective function and must therefore not be observed.