12
A still unused network input variable must be selected for each new value. The values of the
indices 1 and 5 displayed at the network input do not correspond to the temperatures and are
only correctly displayed in the controller in the measured values overview and in the func-
tions.
ESR21, ESR31, UVR61-3, UVR63 and UVR63-H
:
Adjustment of the measurements takes place in the menu
EXT DL
(external sensors)
Example:
The external sensor 1 has address 1, the measured room tem-
perature is imported without offset values (index 2).
In the controllers ESR31, UVR61-3, UVR63 and UVR63-H (version 5.0 up to
7.1), only the measured room temperature can be evaluated without offset
values (index 2); the slider switch and the rotary knob have no purpose for these controllers.
This value can subsequently be allocated to a sensor value (menu ENTER/Men
–
SENSOR).
The room humidity value is indicated in these controllers as a dimensionless value without a
decimal point (e.g. 35.5% -> Controller display: 355).
The values of indices 1 and 5 would be indicated with "999
”
and therefore cannot be used.
The menu option "
EXT DL
" is only available in the following controllers:
UVR 63-H from version 5.0
UVR 63 from version 1.0
UVR 61-3 from version 5.0
ESR 31 from version 1.0
ESR 21 from version 5.0
Entry of an offset value for sensor correction OFFSET
Offset values can be set for the measured values for temperature, room humidity and ambi-
ent air pressure.
Entry T 0.0 = no offset value selected, there-
fore no sensor correction
Factory setting: T 0.0
After a long key press "0.0" flashes
Selection of the desired offset value via
a short key press.
Confirmation of the desired value via a long
key press.
Entry T +0.7 = The room temperature value
displayed and transmitted to the controller
is increased by 0.7 K.
Adjustment range
: - 4.0K to +4.0K
Further short presses of the button will dis-
play the offset values for room humidity
and air pressure (P).