5.3.2 - CTN TYPE TEMPERATURE PROBE
• 10 k
Ω
at 25° C.
5.4 - OPERATING MODES
• The machine only operates in heating mode.
5.5 - STARTING
The unit is factory configured for remote control by contacts (see other possibilities in paragraph 4.3.3).
• Initial condition
:
- machine hydraulically and electrically connected ready to operate,
- the remote stand-by contact is open (= stand-by).
•
Turn the installation on
:
- the display comes on and shows the water temperature (read by the control probe
SD1
). The mode indicator lamps (
4
)
and (
5
) flash to signal remote stand-by,
- the unit's circulating pump starts.
•
To start the unit
:
- close the remote stand-by contact (not supplied) if connected (see paragraph 4.3.3),
- the Heating (
5
) indicator lights up.
- The compressor "ON" indicator light (
6
) comes on if necessary (see diagram paragraph 5.4). If the light flashes, it means
that the compressor is starting required but that a safety delay is in progress. This light stays on when the compressor
has started.
•
To stop the unit
:
- open the remote stand-by contact,
- the compressor operation indicator lamp (
6
) goes out and the operating mode indicator lamps (
4
) and (
5
) flash,
- the unit's circulating pump remains in operation.
•
Complete stop
:
- the unit can be completely stopped with the circulating pump shut-down by pressing
and holding the
ON/OFF
button (
1
) for 2 seconds. The display unit goes blank, only the
decimal indicator lamp (
9
) remains illuminated. This shut-down takes priority.
Note:
Shut-down of the circulating pump is delayed 1 minute after the compressor stops.
Temperature (°C)
Ohmic value (Ohm)
-20
67 740
-10
42 450
0
27 280
10
17 960
20
12 090
25
10 000
30
8 313
40
5 820
50
4 161
60
3 021
70
2 229
Compressor
control
Water temperature
Hysteresis heating mode (factory set at 4k)
Heating setpoint
Heating
2 seconds