5.3.2 - CTN TYPE TEMPERATURE PROBE

• 10 k

at 25° C.

5.4 - OPERATING MODES

• The machine only operates in heating mode.

5.5 - STARTING

The unit is factory configured for remote control by contacts (see other possibilities in paragraph 4.3.3).

• Initial condition

:

- machine hydraulically and electrically connected ready to operate, 
- the remote stand-by contact is open (= stand-by).

Turn the installation on

:

- the display comes on and shows the water temperature (read by the control probe 

SD1

). The mode indicator lamps (

4

)

and (

5

) flash to signal remote stand-by,

- the unit's circulating pump starts.

To start the unit

:

- close the remote stand-by contact (not supplied) if connected (see paragraph 4.3.3),

- the Heating (

5

) indicator lights up.

- The compressor "ON" indicator light (

6

) comes on if necessary (see diagram paragraph 5.4). If the light flashes, it means

that the compressor is starting required but that a safety delay is in progress. This light stays on when the compressor
has started.

To stop the unit

:

- open the remote stand-by contact,
- the compressor operation indicator lamp (

6

) goes out and the operating mode indicator lamps (

4

) and (

5

) flash,

- the unit's circulating pump remains in operation.

Complete stop

- the unit can be completely stopped with the circulating pump shut-down by pressing

and holding the 

ON/OFF

button (

1

) for 2 seconds. The display unit goes blank, only the

decimal indicator lamp (

9

) remains illuminated. This shut-down takes priority.

Note:

Shut-down of the circulating pump is delayed 1 minute after the compressor stops.

Temperature (°C)

Ohmic value (Ohm)

-20

67 740

-10

42 450

0

27 280

10

17 960

20

12 090

25

10 000

30

8 313

40

5 820

50

4 161

60

3 021

70

2 229

Compressor

control

Water temperature

Hysteresis     heating mode (factory set at 4k)

Heating setpoint

Heating

2 seconds

Summary of Contents for PHTJ 14/19

Page 1: ...aldamento Fluido refrigerante R 407 C Bomba de calor de alta temperatura con equipamiento hidr ulico s lo calefacci n Fluido refrigerante R 407 C Hochtemperatur W rmepumpe mit Hydraulikmodul Nur Heize...

Page 2: ...18 R 407 C Fluid R 407 C is not a pure fluid but a blend composed of 23 R 32 25 R 125 52 R 134 A The compressors approved for operation with this fluid are filled beforehand with polyalcohol oil Contr...

Page 3: ...on the installation check that its power supply is disconnected and locked out 1 4 USE OF EQUIPMENT This device is designed for heating buildings This appliance is not designed to be used by people i...

Page 4: ...t not be directed towards surrounding windows vibrations and noise must not be transmitted to a nearby building avoid exposure to salty air or sulphuric gas the proximity of the extractor fan projecti...

Page 5: ...devices not supplied See ratings in the table below Note The unit is designed to be connected to a power supply having a TT neutral regime neutral to ground or TN S regime to neutral as per NF C 15 10...

Page 6: ...is light flashes if a safety delay is in progress It stays on when the compressor is operating The control probe SD1 is located on the water inlet in the factory The controller is connected on a print...

Page 7: ...paragraph 5 4 If the light flashes it means that the compressor is starting required but that a safety delay is in progress This light stays on when the compressor has started To stop the unit open t...

Page 8: ...s 1 and above are accessed Note 2 The normal display level 0 returns automatically after 5 minutes if no buttons are pressed Level 0 Normal display Level 1 Level 2 Level 3 Level 4 Temperature S1 Alarm...

Page 9: ...ection in the menu Briefly and simultaneously press buttons 1 and 2 The message appears Enter the password using buttons 1 and 2 and validate it by simultaneously pressing buttons 1 and 2 It is now po...

Page 10: ...ilation can restart after defrosting is completed to prevent excessive pressure build up For special climatic conditions the factory set time counter value of 30 minutes can be adjusted To do this mod...

Page 11: ...or lamp flashes The stand by mode is indicated by the extinction of the heating mode indicator lamps Pre ventilation Generally speaking in order to condition the air heat exchanger the fan always star...

Page 12: ...55 The functions and display are exactly the same as those on controller The only difference concerns the buttons and which are separated by the ON OFF and Mode buttons Reminder the parameters are acc...

Page 13: ...ssure 2 bar That there are no leaks That the machine is stable That the power cables are well fixed to their connection terminals Terminals that are poorly tightened may cause overheating and malfunct...

Page 14: ...e cleaning and protection of condensate tanks Treating odours and the disinfection of room surfaces and volumes also contributes to the cleanliness of the air breathed by users Carry out the following...

Page 15: ...er use oxygen or dry air as the risk of fire or explosion is present Use dehydrated nitrogen or a nitrogen and refrigerant mix indicated on the manufacturer s plate For units equipped with pressure ga...

Page 16: ...3 00 27 89 13 4 43 4 61 4 93 18 99 22 94 27 87 14 4 50 4 68 5 06 18 95 22 89 27 85 15 4 57 4 76 5 19 18 92 22 83 27 83 16 4 64 4 84 5 32 18 88 22 77 27 82 17 4 71 4 92 5 45 18 84 22 72 27 80 18 4 79 5...

Page 17: ...11 4 43 18 99 22 64 25 60 14 4 12 4 18 4 56 18 95 22 59 25 58 15 4 19 4 26 4 69 18 92 22 53 25 56 16 4 26 4 34 4 82 18 88 22 47 25 55 17 4 33 4 42 4 95 18 84 22 42 25 53 18 4 41 4 50 5 08 18 80 22 36...

Page 18: ...ink N Black R Red W White Colours of the wires M3 1 U N 45 1 3 2 4 KM3 M2 1 S R C M N B L1 L3 L1 B B 46 N C1 32 31 P3 56 55 J1 E2 BP 54 53 L L BP G R1 HP G HP 52 51 A1 SD 4 SD 3 SD 2 SD 1 U2 U1 N1 N2...

Page 19: ...2 R1 W3 26 25 24 23 KM2 W2 W1 21 22 22 21 7 5 6 4 2 3 1 P1 P2 N XP PE XP U XP M M1 1 P W G M G 2 1 5 4 3 CX1 M11 1 P W G M G 2 1 5 4 3 CX2 C11 M B E1 U1 N1 N B U SD1 SD2 SD3 P4 P5 CN1 I CN1 II A3 SD4...

Page 20: ...F GB D P I E...

Page 21: ...F GB D P I E...

Page 22: ...dificarli senza preaviso En el inter s de mejoras constantes nuestros productos pueden modificarse sin aviso pr vio Unsere Produkte werden laufend verbessert und k nnen ohne Vorank ndigung abge ndert...

Reviews: