30
6. ELECTRICAL DATA
6-1. Electrical Characteristics
Indoor Unit
Outdoor Unit
Complete Unit
Fan Motor
Fan Motor
Compressor
Performance at
230V 1-phase 50Hz
Rating Conditions Running Amps. A 0.13 0.28 6.09 6.5
Power Input kW 0.031 0.062 1.287 1.38
Full Load Conditions Running Amps.
A
0.13
0.28 7.09 7.5
Power Input
kW
0.031
0.062
1.507
1.60
Rating Conditions
: Indoor Air Temperature 27°C D.B. / 19°C W.B.
Outdoor Air Temperature 35°C D.B.
Full Load Conditions : Indoor Air Temperature 32°C D.B. / 23°C W.B.
Outdoor Air Temperature 43°C D.B.
Indoor Unit MCAV127C5VAB
Outdoor Unit GRV121L5VAA
Indoor Unit
Outdoor Unit
Complete Unit
Fan Motor
Fan Motor
Compressor
Performance at
230V 1-phase 50Hz
Rating Conditions Running Amps. A 0.12 0.24 4.04 4.4
Power Input kW 0.027 0.055 0.858 0.94
Full Load Conditions Running Amps. A 0.12 0.24 4.54 4.9
Power Input kW 0.027 0.055 0.998 1.08
Rating Conditions
: Indoor Air Temperature 27°C D.B. / 19°C W.B.
Outdoor Air Temperature 35°C D.B.
Full Load Conditions : Indoor Air Temperature 32°C D.B. / 23°C W.B.
Outdoor Air Temperature 43°C D.B.
Indoor Unit MCAV97C5VAB
Outdoor Unit GRV91L5VAA
Indoor Unit
Outdoor Unit
Complete Unit
Fan Motor
Fan Motor
Compressor
Performance at
230V 1-phase 50Hz
Rating Conditions Running Amps. A 0.11 0.24 2.85 3.2
Power Input kW 0.025 0.055 0.6 0.68
Full Load Conditions Running Amps. A 0.11 0.24 3.15 3.5
Power Input
kW
0.025
0.055
0.681
0.76
Rating Conditions
: Indoor Air Temperature 27°C D.B. / 19°C W.B.
Outdoor Air Temperature 35°C D.B.
Full Load Conditions : Indoor Air Temperature 32°C D.B. / 23°C W.B.
Outdoor Air Temperature 43°C D.B.
Indoor Unit MCAV77C5VAB
Outdoor Unit GRV71L5VAA