GB
6
4.4 - ELECTRICAL CONNECTION
4.4.1 - Generals
• The electrical connection conduits must be fixed.
• Class 1 appliance.
• The electrical installation must be carried out in compliance with the rules in force (especially NF C 15-100
CEI 364).
4.4.2 - Detail of the connection
• Remove the cover of the electrical box.
• Cable clamps are provided to maintain the cable at their
entry point into the box.
• Connect the cables to the terminals provided.
• Make sure that the wires are correctly connected to the
terminals. Incorrect connection can cause operating
problems as well as overheating which can cause fires.
• When replacing the box's cover, be sure not to pinch the
cables.
4.4.3 - Power supply
• 230V / 1 + Earth / 50Hz power supply from a power supply and protection device (not included) in accordance with the rules
in force. The protection must be ensured by a
two-pole circuit breaker
(not supplied).
Note:
The unit is designed to be connected to a power supply having a TT neutral regime (neutral to ground) or TN.S regime
(to neutral) as per NF C 15-100.
For a IT neutral point connection (isolated neutral),
provide ground fault protection.
• The acceptable voltage variation is ± 10% during
operation.
• Wire sizes are given for informational purposes only. Wire
sizes must be checked and adapted, as required,
according to the installation conditions and with regard to
current standards.
• The power supply is connected to terminal strip X1
(terminals U, N, and PE) of the printed circuit board
located in the electric box (see drawing opposite).
4.4.4 - Remote controls (accessories)
• 2 types:
- Code 70250076 ("RAB 30")
With manual change / over
(cooling / heating switching).
- Code 70250051 ("RCC 10")
With automatic change / over
(cooling / heating switching)
.
PE
N
U
N
Ph
230V / 1 / 50Hz
Printed circuit board
Electrical box
Electrical cable
passage
Cable inlet into
the unit
Electrical box cover
Models
Max. current consumption (A)
Section (mm
2
)
CWX 6/8
0.65
1.5
CWX 10
0.95
1.5
70250076
70250051
Operating switch
with fan speed selection
Temperature setting knob
Heating / cooling selector switch
Heating on indicator light
Ventilation on indicator light
Cooling on indicator light
Temperature setting knob
Operating switch with fan speed selection
Summary of Contents for CWX 10
Page 13: ...F 13 CWX 6 10 CWX 8...
Page 25: ...GB 13 CWX 6 10 CWX 8...
Page 37: ...I 13 CWX 6 10 CWX 8...
Page 49: ...13 E CWX 6 10 CWX 8...
Page 61: ...D 13 CWX 6 10 CWX 8...
Page 62: ...F GB I E D...
Page 63: ...GB I E D F...