13

EG

ERROR

LEDS

OPERA

TION       

TIMER            ST

ANDBY

POSSIBLE CAUSE

SYSTEM BEHA

VIOUR

SOLUTION

E3

F

F

F

Communication error between the out-

door unit and the indoor unit

Fan is stopped and flap is closed

after 30 seconds of missing com-

munication.

The system restarts automatically

as soon as the communication is

recovered.

Check that connections between C1

and C2 on outdoor and indoor terminal

block are correct (C1 terminals con-

nected together

, C2 terminals connect-

ed together).

Check that a shielded communication

cable has been used.

Check that the dip-switch SW2 for com-

munication address setting is in the

correct position.

Check that all earth cables are proper-

ly connected to every terminal.

Check that the shield of the communi-

cation cable is properly connected to

every terminal.

Check the communication fuse on out-

door and indoor unit.

Check that the outdoor unit has power

supply and that it is working.

Check that all PCBs are powered on.

Be sure that power supply has not

been connected to the communication

terminals.

Check that there are no burnt signs on

the PCBs, in particular close to commu-

nication cables.

Check that the fan motor is not dam-

aged and it doesn’t create short circuit

on the indoor PCB.

O = LED OFF

= LED ON

F  = Flashing LED

Summary of Contents for CA10FICR5I

Page 1: ...A14FIDR5I OPERATING INSTRUCTIONS ISTRUZIONI D USO NOTICE D UTILISATION BEDIENUNGSANLEITUNG INSTRUCCIONES DE USO Split air conditioner system Condizionatore d aria split system Climatiseurs split Split...

Page 2: ...NERGY SAVING 11 TROUBLESHOOTING 11 EXPLANATION AND USE OF THE REMOTE CONTROL UNIT S MICROSWITCHES 15 NOTE PRODUCT INFORMATION If you have problems or questions concerning your Air Conditioner you will...

Page 3: ...t it is in STANDBY it doesn t operate or it is waiting to start The OFF position does not disconnect the power Use the main power switch to turn off power completely OFF LAMPS FUNTION It is possible t...

Page 4: ...n NOTE SWITCHES SAFETY INSTRUCTIONS l Read this booklet carefully before using this air conditioner If you still have any difficulties or problems consult your dealer for help l This air conditioner i...

Page 5: ...button to modify the active setting for room temperature detection from remote controller to air conditioner and viceversa FAN BUTTON fan speed Fan speed is automatically selected by the microcomputer...

Page 6: ...h this air conditioner use another heating appliance in conjunction with it Example of operation diagram in the Auto mode with the set room temperature at 23 C NOTE The air conditioner changes the ope...

Page 7: ...operation mode cooling or heating for all the other units that will be switched on after the first one when the system has been switched on in cooling mode and one unit is activated in heating mode an...

Page 8: ...ton to turn the air conditioner off l Wait for the indoor unit to stop operating l Press the ON OFF button again to turn the air conditioner on SETTING THE 1 HOUR TIMER This function causes the unit t...

Page 9: ...n adjust the air flow direction using the 4 flaps of the grille frame Chose the best position according to the operation mode and the recommended flap position Press the FLAP button to select the flap...

Page 10: ...ild liquid detergent When cleaning the grille be careful not to force the vanes out of place HOW TO REMOVE THE FILTER EG The air intake grille can be removed in order to wash it with water HOW TO REMO...

Page 11: ...Shut them to keep the heat or cold out 4 Remove it to ensure good airflow 5 Set the right temperature on the remote control unit 6 Try to use a back up heater 7 Consult your dealer Trouble Clicking so...

Page 12: ...and flap is closed The system restarts automatically as soon as the problem on the out door unit is solved Check the error code using the appro priate LEDs on the PCB of the outdoor unit Follow the in...

Page 13: ...sed Check that the dip switch SW2 for com munication address setting is in the correct position Check that all earth cables are proper ly connected to every terminal Check that the shield of the commu...

Page 14: ...ical wiring diagram Check that the sensor is not damaged and if necessary replace it E6 O F F Fan motor error Fan is stopped and flap is closed The system restarts automatically after some seconds Che...

Page 15: ...ler providing this service Disposing of a battery separately avoids possible negative ef fects on the environment and human health deriving from an inappropriate disposal and enables its components to...

Page 16: ...S A C Printed in italy Z I Route d partementale 28 01600 Reyrieux France T l 33 4 74 00 92 92 Fax 33 4 74 00 42 00 Technibel is a trademark of NIBE ENERGY SYSTEM FRANCE...

Reviews: