6. CHECKING ELECTRICAL COMPONENTS
6-1 Measurement of Insulation
Resistance
The insulation is in good condition if the
resistance exceeds 2M
Ω
6-1-1. Power supply wires
Clamp the grounding terminal of the power plug
with a lead clip of the insulation resistance tester
and measure the resistance by placing a probe
on both the two power terminals. (fig.1)
Then, also measure the resistance between the
grounding and other power terminals. (fig.1)
6-1-2. Indoor Unit
Clamp a metallic part of the unit with the lead
clip of the insulation resistance tester and measure
the resistance by placing a probe on each terminal
screw where power supply lines are connected on the
terminal plate. (fig.2)
6-1-3. Outdoor Unit
Clamp an aluminium plate fin or copper tube with
the lead clip of the insulation resistance tester
and measure the resistance by placing a probe
on each terminal screw on the terminal plate. (fig.2)
Note that the ground line terminal should be skipped
for the check.
6-1-4. Measurement of Insulation
Resistance for Electrical Parts
Disconnect the lead wires of the desired electric
part from terminal plate, capacitor, etc.
Similary disconnect the connector.
Then measure the insulation resistance. (fig.3 and 4)
NOTE: Refer to electric wiring diagram
If the probe cannot enter the poles because the
hole is too narrow then use a probe with a
thinner pin.
Ground
power plug
(Local supply)
probe
Insulation
tester
Terminal plate
Copper
tube or
metallic part
Clip
Insulation
tester
Probe
Copper
tube or
metallic part
Clip
Insulation
tester
Probe
Clip
Insulation
tester
Probe
Metallic
part
From fan motor,
compressor and
other parts
Fig. 2
Fig. 3
Fig. 4
The shape of the power plug may differ from that
of the air conditioner which you are servicing.
NOTE
Fig. 1
32
Summary of Contents for 387005960
Page 11: ...2 DIMENSIONAL DATA Unit mm Unit mm 11...
Page 12: ...3 ELECTRICAL DATA 3 1 Electric Wiring Diagrams KPAF124R5 KPAF185R5 KPAF225R5 12...
Page 13: ...4 1 Cool Mode Operation 4 FUNCTION 13...
Page 14: ...4 2 Heat Mode Operation 14...
Page 15: ...4 3 Auto Cool Heat Mode Operation 15...
Page 16: ...4 4 Dry Mode Operation 16...
Page 18: ...2 Outdoor Coil High Pressure Protection 18...
Page 19: ...4 7 Protection Operations in Heat Mode 1 Outdoor Coil Deice Protection 19...
Page 20: ...20...
Page 21: ...2 Indoor Coil High Pressure Protection in Heat Mode 21...
Page 22: ...4 8 Sleep Function 4 9 Daily Timer Function 4 10 IFEEL Function 22...