background image

NOTE

For additional charge of various
tubing lengths, refer to outdoor
unit nameplate.

The indoor unit contains a small quantity of refrigerant. Do not
unscrew the nuts from the unit until you are ready to connect the
tubing. The outdoor unit is supplied with sufficient refrigerant charge.
Refer to outdoor unit nameplate.

To prevent crushing, bend tubes using a bending tool.

Use refrigeration type copper tubing only.

1. Use tubing diameter that corresponds to the tubing diameter of

the indoor and outdoor units. Note that the liquid and suction tubes
have different diameters. (See tube size, torque tightening table.)

2. Place flare nuts on tube ends before preparing them with a flaring

tool Use the flare nuts that are mounted on the supplied outdoor
and indoor units.

3. Connect the four ends of the tubing to the indoor and outdoor

units.

4. Insulate each tube separately, and their unions, with at least

6mm. of insulation. Wrap the refrigerant tubing, drain hose and
electric cables together with a vinyl tape (UV protected).

CONNECT THE INDOOR TO THE OUTDOOR UNIT

NOTE:

REFRIGERANT TUBING

Fig.21
1.INDOOR UNIT
2.Liquid tube (small dia.)
3.Suction tube (large dia.)
4.Plugs
5.Flare nuts
6.Tubing between units
7.Suction tube
8.Liquid tube
9.OUTDOOR UNIT
10.Flare nuts
11.Suction valve (larger)
12.Liquid valve (small)

Caution!
When unscrewing the
valve caps, do not
stand in front of them
or the spindles at any
time, as the system is
under pressure.

Tightening
torques of unions
and valve caps:

Fig.22
1.Wrench
2.Torque wrench
3.Union

Fig.23
To prevent refrigerant
leakage, coat the flared
surface with
refrigeration oil

Fig.24
1.Suction valve
2.Service port
3.Liquid valve

Fig.24a
1.Charging set
2.Vacuum pump
3.OUTDOOR UNIT
4.Service valve

TUBE SIZE
Liquid line 1/4"
Suction line 3/8"
Suction line 1/2"
Suction line 5/8"

TORQUE
15-20 N.M.
30-35 N.M.
50-54 N.M.
75-78 N.M.

7

5.Cap
6.Suction valve
7. Service valve*
8.Cap

9.Liquid valve

10.INDOOR UNIT
11.Suction flare connection
12.Liquid flare connection
*In some models only

Fig.23

1

2

3

Fig.24

1

2

3

Fig.22

1

2

3

4

5

6

7

8

9

10

11

12

Fig 4a

2

1

2

3

4

5

6

7

8

9

10

11

12

Fig 21

EVACUATION OF THE REFRIGERATION TUBES AND
THE INDOOR UNIT

After connecting the unions of the indoor and outdoor units, purge
the air from the tubes and indoor unit as follows:
1. Connect the charging hoses with a push pin to the low and high

sides of the charging set and the serice port of the suction and
liquid valves. Be sure to connect the end of the charging hose
with the push pin to the service port.

2. Connect the center hose of the charging set to a vacuum pump.
3. Turn on the power switch of the vacuum pump and make sure

that the needle in the gauge moves from 0MPa(0cm Hg)to -0.1MPa
(-76cm Hg). Let the pump run for fifteen minutes.

4. Close the valves of both the low and high sides of the charging

set and turn off the vacuum pump. Note that the needle in the
gauge should not move after approximately five minutes.

5. Disconnect the charging hose from the vacuum pump and from

the service ports of the suction and liquid valves.

6. Tighten the service port caps of both suction and liquid valves.
7. Remove the valve caps from both valves, and open them using a

hexagonal Allen wrench.

8. Remount valve caps onto both of the valves.
9. Check for gas leaks from the four unions and from the valve caps.

Text with electronic leak detector or with a sponge immersed in

soapy water for bubbles.

Summary of Contents for GRF124C5TAA

Page 1: ...2 Tube flaring tool 13 Torque wrench 14 Adjustable wrench 15 Reamer for reburring 16 Hex key Tools required for installation not supplied OPERATING LIMITS Cooling Maximum conditions Outdoor temperatur...

Page 2: ...ing to touch the refrigerant tubing compressor or any moving parts of the fan Do not use multi core cable when wiring the power supply and control lines Use separate cables for each type of line When...

Page 3: ...ect sunlight 3 The location must allow convenient electrical draingage and tubing connections 4 Installation site should provide an easy passage to outdoors 5 The unit must be mounted on a strong wall...

Page 4: ...Direction of tubing Fig 4 Fig 6 Fig 6 1 Mounting pads x4 950mm 1800mm Fig 5 50 mm n mi 50 mm n mi 2300 mm n mi 400 mm n mi 80 mm min 2 1 1 100 mm n mi 100 mm n mi 500 mm n mi 100 mm n mi AUTO c F AM...

Page 5: ...ere are five possible routes for installing the refrigeration tube as shown 2 For route 6 cut the bottom notch in the rear 3 For routes 5 or 7 cut the side notches in the rear and in the front panel F...

Page 6: ...es long horizontal sections a vent must be provided at the top of the hose to prevent overflow of the unit drain pan 7 Upon completing the installation test the water drain by pouring at least two lit...

Page 7: ...wire cable 6 connector instead 7 connect the other end of the twin wire cable 6 to the outdoor unit twin wire terminal 9 8 Secure the multiple wire power cable with the cable clamps 9 Fasten the twin...

Page 8: ...oil Fig 24 1 Suction valve 2 Service port 3 Liquid valve Fig 24a 1 Charging set 2 Vacuum pump 3 OUTDOOR UNIT 4 Service valve TUBE SIZE Liquid line 1 4 Suction line 3 8 Suction line 1 2 Suction line 5...

Page 9: ...between hole sides and tubing with sealer 3 Attach wiring and tubing to the wall with clamps where necessary 4 Operate the air conditioner together with the customer and explain all functions 5 Expla...

Reviews: