OUTDOOR UNIT:
GRF188L7TAA
COOLING
Indoor Unit
Complete Unit
Fan Motor
Fan Motor
Compressor
performance at
Rating conditions
Running Amps.
A
0,37
0,41
2,62
3,40
Power input
Kw
0,070
0,087
1,493
1,650
Full load conditions
Running Amps.
A
0,37
0,41
3,32
4,10
Power input
Kw
0,070
0,087
1,943
2,100
NOTE: Data referred to indoor unit
MPAF188C5T
model.
For other indoor unit models there could be some differences.
OUTDOOR UNIT:
GRF228L7TAA
COOLING
Indoor Unit
Complete Unit
Fan Motor
Fan Motor
Compressor
performance at
Rating conditions
Running Amps.
A
0,40
0,67
3,13
4,20
Power input
Kw
0,086
0,144
1,850
2,080
Full load conditions
Running Amps.
A
0,40
0,67
3,93
5,00
Power input
Kw
0,086
0,144
2,370
2,600
NOTE: Data referred to indoor unit
MPAF228C5T
model.
For other indoor unit models there could be some differences.
OUTDOOR UNIT:
GRF258L7TAA
COOLING
Indoor Unit
Complete Unit
Fan Motor
Fan Motor
Compressor
performance at
Rating conditions
Running Amps.
A
0,77
0,67
3,66
5,10
Power input
Kw
0,175
0,144
2,261
2,580
Full load conditions
Running Amps.
A
0,77
0,67
4,76
6,20
Power input
Kw
0,175
0,144
3,081
3,400
NOTE: Data referred to indoor unit
CAF258C5T
model.
For other indoor unit models there could be some differences.
Rating Conditions:
Indoor Air Temperature 27°C D.B. / 19°C W.B.
Outdoor Air Temperature 35°C D.B.
Full Load Conditions: Indoor Air Temperature 32°C D.B. / 23°C W.B.
Outdoor Air Temperature 43°C D.B.
Outdoor unit
230V 1-Phase 50 Hz
Outdoor unit
230V 1-Phase 50 Hz
Outdoor unit
230V 1-Phase 50 Hz
44