1-3 Other Component Specifications
Trasformer
Rating
Primary
Secondary 1
Secondary 2
Secondary 3
Thermal cut-off temp.
Thermistor ( Coil sensor E1, E2)
Resistance
k
Ω
Thermistor ( Room sensor TA)
Resistance
k
Ω
Drain pump
Model
Rating
Voltage
Input
Total head / capacity
Safety float switch
Model
Contact rating
500 mm / 400 cc/min.
FS-0218-102 (ASR425HG)
DC 12V - 25W
FS-0218-103 (ASR436/448HG)
WP20SL-21
230V
12W
ATR-IIJ225A
VAC 230V, 50Hz
AC 20V - 0.2A
AC 14V - 0.3A
PBC-41E-S26
AC 10,2V - 1.4A
136°C
0 °C 15,0 ± 5%
25 °C 5,0 ± 4%
DHKTEC-35-S85N