1-4 Indoor Fan Performance
If external static pressure is too great (due to long extension of ducts, foe example), the air flow volume may drop too low at
each air outlet. This problem may be solved by increasing the fan speed using the following procedure:
(1)
Remove the screw on the electrical component box
and remove the cover plate.
(2)
Disconnect the fan motor sockets in the box.
(3)
Take out the booster cable (sockets at both ends)
clamped in the box.
(4)
Securely connect the booster cable sockets between
the disconnected fan motor sockets in step 2
as shown in the Fig. 1-1
(5)
Place the cable neatly in the box and reinstall the cover plate.
Fig. 1-1
HH:
Using the booster cable
H:
At shipment
How to read the diagram
The vertical axis is the external static pressure (Pa)
while the orizzontal one is the AIR FLOW RATE (m3/h).
The characteristic curves for HH, H, M and L fan speed
are shown. The nameplate values shown are based on the
H air flow rate. For the type 7/9/12 flow rate is 600 m3/h
while the external static pressure is 49 Pa at H position.
If external static pressure is too great (due, for example,
to long duct extension), the air flow rate may drop too
much at each air outlet.
This problem can be solved increasing the fan speed
with the booster cable.
NOTE
EXTERNAL STATIC PRESSURE
m3/h
7/9/12000
16/18000
22000
EXTERNAL STATIC PRESSURE
m3/h
m3/h
EXTERNAL STATIC PRESSURE
11
Summary of Contents for 38.7106.982
Page 12: ...2 DIMENSIONAL DATA DSAFM75 95 125R5I 12...
Page 13: ...DSAFM165 185 225R5I 13...
Page 16: ...4 FUNCTIONS 4 1 Room temperature control 16...
Page 17: ...4 2 Automatic control for heating and cooling 17...
Page 19: ...5 2 How to replace PCB 19...
Page 20: ...5 3 How to replace EEPROM with EEPROM included in PCB service pack 20...
Page 21: ...21...
Page 22: ...5 4 Table of settings 22...
Page 23: ...6 SERVICING AND MAINTENANCE FUNCTIONS 23...
Page 24: ...7 TROUBLE DIAGNOSIS 7 1 Contents of remote controller switch alarm display 24...
Page 25: ...25...
Page 26: ...7 2 Outdoor unit control panel LED display 26...
Page 27: ...7 3 Trouble indications and inspection points 27...
Page 28: ...28...
Page 29: ...7 4 Remote controller servicing functions 29...
Page 30: ...7 5 Multiset alarm codes 30...
Page 31: ...31...
Page 32: ...32...
Page 33: ...33...
Page 34: ...34...
Page 35: ...35...
Page 36: ...36...
Page 37: ...37...
Page 38: ...38...
Page 39: ...39...
Page 40: ...40...
Page 41: ...41...
Page 42: ...42...
Page 43: ...43...
Page 44: ...44...
Page 45: ...45...
Page 46: ...46...
Page 47: ...47...
Page 48: ...48...
Page 49: ...49...
Page 50: ...50...
Page 51: ...51...
Page 52: ...52...
Page 53: ...7 6 Inspection of parts 53...
Page 54: ...54...
Page 55: ...55...