5-2 Cool Mode Operation
In Cooling Mode, the operation of the compressor (CM), Outdoor Fan (FMO) and Indoor Fan (FMI) are
determined by:
1) the difference between the room air temperature (RAT) and the set point temperature (SPT)
2) the protection level at which the system is operating
NOTES
In addition to the temperature difference of above, the operation of the main components (CM, FMO,
FMI) is also controlled by protection function.
The minimum off time of compressor is 3 minutes.
The indoor fan can change speed only after it has operated at the same speed for 30 sec if in AUTO
and 1 sec for the other settings (High, Med, Low).
5-3 Heat Mode Operation
The Heating mode operation is similar to the Cooling mode operation. The CM, FMO and FMI are controlled
by the same parameters.
NOTES
1. After the CM has stopped, the FMI runs for 30s in order to purge heat from the indoor coil.
2. The FMI will not be turned on until the indoor coil temperature is warm enough to prevent the supply of
cold air (see COLD DRAFT PREVENTION feature for details).
The indoor fan can change speed only after it has operated at the same speed for 30 sec if in AUTO and
1 sec for the other settings (High, Med, Low).
14
Summary of Contents for 38.7104.050
Page 9: ...2 DIMENSIONAL DATA MRAF98R5IAA MRAF128R5IAA 9...
Page 12: ...4 ELECTRICAL DATA 4 1 Electric Wiring Diagrams MRAF98R5IAA MRAF128R5IAA 12...
Page 27: ...6 3 SYSTEM DOES NOT RUN 27...
Page 29: ...6 4 OUTDOOR UNIT DOES NOT RUN AND NO FAULT IS DISPLAIED 6 5 ONLY OUTDOOR UNIT IS OFF 29...
Page 30: ...6 6 OUTDOOR UNIT FAULT SIGNALING 30...
Page 32: ...32...
Page 33: ...6 8 NOISY PROBLEM 33...
Page 34: ...7 CHECKING ELETRICAL COMPONENTS 7 1 34...
Page 35: ...7 2 35...