Technalogix Ltd
.
VIII-2
Heating and Cooling Requirements
The environment’s temperature will contribute greatly to the length of the power amplifier’s life. Refer to the
specifications in Section 3.0 for humidity and temperature specifications. Technalogix recommends that the
building’s filtered air intake must have capacity for all air-flow in the building plus an additional 20%. The TAV-
1000 uses (10) ball bearing fans – (4) for each power amplifier, (1) for the power supply enclosure, and (1) for the
combiner. Keep the intake below the roofline to avoid intake of solar heated air. Please ensure that the intake
and exhaust areas are on the same side of the building to avoid pressure differentials during windy conditions.
Also, do not position intake near exhaust’s preheated air. If air conditioning is required to cool the shelter,
discuss the situation with a qualified HVAC technician. Under average conditions, 12,000 BTUs will cool
approximately 500 square feet to a comfortable level.