Technalogix Ltd
.
VIII-3
Electrical Service Recommendations
Technalogix recommends that a qualified, licensed local electrician be consulted for the required
electrical service. We suggest local electricians because:
•
The personnel knows the local codes
•
The personnel can be on site readily
•
You are apt to get better overall support if you give what business you can to local suppliers
Technalogix recommends that proper AC line conditioning and surge suppression be provided on the
primary AC input to the power amplifier. All electrical service should be installed with your national
electrical code in your area, any applicable provincial or state codes, and good engineering practice.
Special consideration should be given to lightning protection of all systems in view of the vulnerability
of most transmitter or translator sites to lightning. Lightning arrestors are recommended in the service
entrance. Straight and short grounds are recommended. The electrical serviced must be well
grounded. Do not connect the unit to an open delta primary power supply, as voltage fluctuations could
harm the unit. Branch your circuits. Do not allow your lights, your workbench plugs, and your
transmitting or translating equipment to operate on one circuit breaker. Each transmitter or translator
should have its own circuit breaker, so a failure in one does not shut off the whole installation.