IDS control function 

The special function of the reader is a 

simple IDS control

 with a use of a 

WIO 22 relay module

The function description follows. 

8.1  IDS connection 

The 

IDS control function

 is performed by the 

second relay

 of the 

WIO 22 relay module

, which 

is connected to the reader module using the 

WIEGAND interface

 (the first relay of the WIO 

22 module still copies the status of the reader module door lock relay). 

The IDS can be controlled either by the 

status

 of the IDS control relay, or by an 

impulse

 of 

the  IDS  control  relay.  The  width  of  the  impulse  is  configurable  (see 

chapter  6.7.3

).  The 

function of the IDS control relay is described in 

table 15

Rel

ay

 

Status control 

Relay active 

Disarm IDS 

Relay inactive 

Arm IDS 

Impulse control 

Relay active impulse 

Switch IDS status (armed / disarmed) 

Table 15: IDS control relay function 

The IDS status is indicated by the third LED of the MREP 78 reader module (located on the 
right). In the status control mode the indication is based only on the control relay status, in 
the impulse control mode it is given by the I/O Port status. The meaning of the LED color and 
the logic of IDS signal at the I/O Port are described in 

tables 16 and 17

LE

D

 

D3 

Green 

Indicating IDS disarmed status 

Red 

Indicating IDS armed status 

Yellow 

Indicating IDS arming / disarming status 

Table 16: IDS status indicated at the reader module 

 

I/O

 P

ort

 

0 V (GND) signal from the IDS connected to the I/O Port 

IDS armed 

Other signal (or I/O Port not used) from IDS 

IDS disarmed 

Table 17: Logic of the IDS signal at the I/O Port 

Proper connection of the reader module I/O Port with the IDS status signal is required for 
the correct function in the impulse control mode! 

8.2  IDS operation 

8.2.1  IDS disarmed 

If the 

IDS is disarmed

 (indicated by the LED indicator 

– 

green color

), a standard door open 

function is performed after a valid identification. 

To arm the IDS

, the 

#

 (hash) key must be 

pressed 

before identification

. The action of the reader and connected WIO 22 relay module 

depends on the IDS control mode: 

 

Status control mode

 

– the control relay is switched off to arm the IDS and the IDS status 

LED indicator turns red. 

Summary of Contents for APS mini MREP 78 Series

Page 1: ...ll mounting for BPT Xolid panels nad for OEM use in own applications User s guide 2004 2019 TECH FASS s r o V t nsk 1611 19 153 00 Prague Czech Republic www techfass cz techfass techfass cz Date of re...

Page 2: ...eters of the reader module 9 5 1 Configurable parameters 9 5 2 Reader module parameters setting 9 6 Reader module functioning 10 6 1 Door Open function description 10 6 2 Function permanent door lock...

Page 3: ...e used for a simple IDS control 2 1 MREP 78 module The reader module pic 1a is intended for wall mounting in both indoor and outdoor environment 2 2 MREP 78X module The reader module pic 1b is designe...

Page 4: ...odule features 2 TF EM MREP 78 TF Wall mounted 53478400 MREP 78X TF Xolid panel 53478410 MREP 78E TF OEM solution 53478420 MREP 78 EM Wall mounted 53478401 MREP 78X EM Xolid panel 53478411 MREP 78E EM...

Page 5: ...r protection Opening the cover Against tearing off Opto electronic Communication interface RS 485 Alternative data input output WIEGAND configurable Table 2 Technical features 3 3 Special accessories...

Page 6: ...pply 2 Blue 0 V pow supply 3 Yellow Input 1 4 Grey brown 0 V 5 Grey Input 2 6 Black A RS 485 7 White B RS 485 8 Violet NO lock relay 9 Grey pink NC lock relay 10 Brown C lock relay Table 5 Terminal de...

Page 7: ...inuously lit GREEN Indicating IDS disarmed status Continuously lit RED Indicating IDS armed status Continuously lit YELLOW Indicating IDS arming disarming status Table 8 LED indicators description 4 3...

Page 8: ...plies generate enough noise to cause reader malfunction it is recommended to use linear system power supplies Radiated noise is transmitted through the air It can be caused by computer monitors or oth...

Page 9: ...30 s Acoustic signalization time Forced door 0 255 s 30 s Acoustic signalization time Door ajar 0 255 s 0 s Acoustic signalization time APB alarm 0 255 s 0 s Signalization time Card alarm 0 255 s 30 s...

Page 10: ...ase time has elapsed see configuration table In case the toggle function of the door lock relay is set the door lock relay status is switched and the beeper is activated when not disabled when the Doo...

Page 11: ...es with setting of the signaling timer 0 occurs the alarm output is activated It can control any alarm device directly or it can be processed further After terminating all alarm conditions the alarm o...

Page 12: ...ID media format can be changed into selected 24 32 or 40 bits length of ID code The default length is 40 bits This setting is only used when unifying of the ID media codes length is required in combi...

Page 13: ...he interpretation of its status is I O Port active status 0V signal from the IDS at the I O Port IDS armed The IDS can be controlled with one of the following modes Status control the IDS is controlle...

Page 14: ...09 the reading synchronization of a couple of TECHFASS readers is implemented enabling to cancel the mutual disturbance of the modules The reader module offers the Wiegand data interface synchronizati...

Page 15: ...ogramming mode by reading one of the two programming cards cards and The programming mode cannot be entered while the module is in hardware address setting mode for modules with HW address setting via...

Page 16: ...st card code the reader module goes back into standard operating mode Pic 4 a Inserting cards codes 6 8 2 Deleting cards codes from the reader s memory For deleting the cards from the reader module s...

Page 17: ...ated by slow flashing of yellow LED Read the programming card for inserting 5 times in a row or enter the programming code the reader will go into Deleting cards above or below mode indicated by fast...

Page 18: ...reader module memory All operations adding and deleting cards should be stored in the table Following example shows correct usage of the programming cards and proper filing of the actions Inserting 5...

Page 19: ...ange a PIN code in the reader s memory by pressing the key sequence Esc 1 Enter at a reader in a mode with a keypad for PIN entering The reader enters PIN changing mode In this mode the user attemptin...

Page 20: ...ant input is disconnected 6 11 1 Time Antipassback The Time Antipassback is defined by the ABP timer initial value in minutes which is set to the ID after passing at the reader module If the users use...

Page 21: ...the third input output port The logic of the function is individually configurable The function is active whenever one or both of the configured inputs are active The module behavior is as described...

Page 22: ...evaluation can be seen on Pic 5 Pic 5 Simplified access rights evaluation VALID INVALID PIN UNKNOWN ID FOUND ACCESS DRIVEN BY TIME SCHED ACCESS ALWAYS GRANTED HOLIDAY ACCESS GRANTED FOR HOLIDAY AND A...

Page 23: ...the indication is based only on the control relay status in the impulse control mode it is given by the I O Port status The meaning of the LED color and the logic of IDS signal at the I O Port are des...

Page 24: ...LED indicator turns yellow the reader starts to indicate disarming process with short beeping and awaits the IDS to change its status signal at the I O Port If the status is changed the LED indicator...

Reviews: