background image

Assembly in the ball valve

  Close the ball valve.

  Unscrew the sealing plug from the ball valve.

  Place an O-ring from the enclosed set on the assembly 

pin (1). The second O-ring is a spare part.

  Screw the O-ring with the assembly pin into the ball 

valve‘s sealing plug bore hole (2).

  Place the O-ring in its fi nal position using the other end 

of the assembly pin (3).

  Put the assembly pin over the temperature sensor with 

the sleeve end – as far as it will go (4). 

  Clasp the temperature sensor with both halves of the 

plastic screw directly over the assembly pin. Press both 
halves together so that both pins from one half fi t in the 
bore holes in the other half.

  Remove the assembly pin from the temperature sensor (5).

  Insert the temperature sensor with the plastic screw in the 

ball valve and tighten the plastic screw hand-tight (6).

  Check the leak tightness.

M-bus module connection

  Remove the user locking device from the calculator casing 

and open the lid.

Slot 1 is intended for the M-bus module:

The M-bus module is a serial interface with the following 
properties:
–  M-bus module standardised according EN 1434-3
–  Capability of connecting 2 x 2.5 mm²
– Galvanic 

isolation

–  Maximum voltage: 50V DC,
–  Current consumption: one M-bus load
–  Primary or secondary addressing
–  Baud rate 300 or 2400 bauds.

A 2-pole connector block is at-
tached to the circuit board with 
the marked connections 24 and 
25. They must be connected to 
the M-bus master.

  Push the plugs onto the cir-

cuit board carefully (see fi g. 
on the right-hand side).

  Insert the circuit board into 

the upper locking point and 
position it between it and the 
lower installation point as far as it will go. Screw it down 
tight with 2 cross slot screws:

 

  Close the lid.

  Check the function by pressing the push button.

  Seal the calculator.

Connecting the pulse output module

Slot 2 is intended for the pulse output module

Properties of the pulse output module:
– External 

power 

supply 

V

ex

 = 3-30 V DC

– Output 

current 

 20 mA with a residual voltage 

 0.5 V

– Open 

collector 

(drain)

–  Pulse values 100-150 ms
– Potential-free 

contact

–  Energy pulse valence according to the display unit (last 

digit in the display),

–  Volume pulse valence = last digit of the on-screen volume 

display (standard: 1L/pulse).

A 4-pole connector block is attached 
to the circuit board with the mar-
ked connections („A“ for energy 
pulse output and „B“ for volume 
output).

  Push the plugs onto the circuit 

board carefully (see fi g. on the 
right-hand side).

Summary of Contents for ultra S ll

Page 1: ...ruhi gungsstrecken vor oder hinter dem Z hler sind nicht erforderlich Innerhalb einer Liegenschaft m glichst einheitlich montieren Die Anzeige muss jederzeit zug nglich und ohne Hilfsmittel ablesbar s...

Page 2: ...Bus Modul genormt nach EN 1434 3 Anschlussm glichkeit 2 x 2 5 mm galvanischeTrennung maximale Spannung 50V DC Stromaufnahme Eine M Bus Last Adressierung prim r oder sekund r Baudrate 300 oder 2400 Bau...

Page 3: ...ifschleife 6 Monatsschleife Zur schnellen visuellen Erfassung sind die Schleifen im Dis playmitdenZiffern1bis6gekennzeichnet DieHauptschleife ist mit den aktuellen Daten wie z B f r Energie Volumen un...

Page 4: ...erscheinen Fehler Codes 1 4 7 im Wechsel mit der Grundanzeige Ausnahme Die Fehler anzeige C 1 wird st ndig angezeigt C 1 1 Grundparameter im Flash oder RAM zerst rt Err1 2 FehlerhafteTemperaturmessun...

Page 5: ...m or downstream of the meter are not required If possible use the same installation method within one property The display must be accessible at all times and readable without further aids Install a d...

Page 6: ...ity of connecting 2 x 2 5 mm Galvanic isolation Maximum voltage 50V DC Current consumption one M bus load Primary or secondary addressing Baud rate 300 or 2400 bauds A 2 pole connector block is at tac...

Page 7: ...oop 2 Due date loop 3 Information loop 4 Pulse input loop 5 Tariff loop 6 Monthly loop The loops are marked in the display with the numbers 1 to 6 in order to enable quick visual recording The major l...

Page 8: ...ormity TheHYDROMETERGmbHasmanufactureroftheultrasound compact heat meter ultra S ll herewith declares that this device meets the basic requirements and relevant regula tions of the following guideline...

Reviews: