User’s manual
16
in the CH boiler controller (Menu>> Fitter’s menu>>Internet module).
1.
DHCP parameter (ang.Dynamic Host Configuration Protocol ) must be disabled.
2.
IP address should be set as unique for the network by changing the IP digits freely e.g.
192.168.1.200. If necessary, the user may check it the IP address has not been already taken by entering
the command: ping 192.168.1.200 in cmd.exe.
„Destination host unreachable” means that the IP address has not been taken yet and it may be used.
Otherwise it is necessary to use a different IP address.
5.
MAC address is default: 12:12:12:12:12:18 and it must be unique.
6.
IP mask, Gate address and DNS address should be copied from the downloaded data.
7.
After the controller has been configured successfully, go back to the beginning of the manual –
part IV. How to log in to the module (local network) and enter the previously set IP address in
the Internet browser.