Instruction Sheet

SOLARLOK* Combiner Box Assemblies

408--10271

LOC B

E

2011 Tyco Electronics Corporation, a TE Connectivity Ltd. Company

All Rights Reserved

*Trademark

TE Connectivity, TE connectivity (logo), and TE (logo) are trademarks. Other logos, product and/or Company names may be trademarks of their respective owners.

TOOLING ASSISTANCE CENTER 1--800--722--1111

PRODUCT INFORMATION 1--800--522--6752

This controlled document is subject to change.

For latest revision and Regional Customer Service,

visit our website at

www.te.com

1

of 5

03 MAY 11 Rev D

1954283- 1 and 1954283- 2

Figure 1

Mounting Slot

(4 Places)

Front Top

Front Top

Knockout

(4 Places)

Lock

Tab

Cover Screws

(4 Places)

Cover

Negative SOLARLOK Connector

with Seal Cover (5 Places)

Positive SOLARLOK Connector

with Seal Cover (5 Places)

Hinge

(2 Places)

Box

Front Bottom

Y

B

Ground Assembly

1. INTRODUCTION

SOLARLOK Combiner Box Assemblies 1954283--1

and 1954283--2 are used to combine up to five strings

in a pre--terminated connectorized weather--resistant

enclosure to meet National Electric Code (NEC)

requirements for series fusing of photovoltaic (PV)

modules.

All numerical values in this instruction sheet are

in metric units [with U.S. customary units in

brackets]. Figures are not drawn to scale.

Combiner Box Assembly Specifications

System Voltage (DC):

600 V Maximum

Output Current (DC):

75 A Maximum

Continuous Current (DC):

60 A Maximum

Current Per String (DC):

15 A Maximum

Accepts Fuse Rating (DC):

15 A Maximum

Module Short Circuit Rating (Isc) Per String: 9.6 A Maximum
Weatherability Enclosure Type: NEMA Type 3
Ambient Temperature:

50

_

C [122

_

F] Maximum

Torque:

Negative Output Terminal

4 Nm [35 in.--lbs]

Positive Output Terminal

Wire Sizes 14--10 AWG 4 Nm [35 in.--lbs]

Wire Size 8 AWG

4.5 Nm [40 in.--lbs]

Wire Sizes 6--4 AWG

5.1 Nm [45 in.--lbs]

Ground Terminal Block

4 Nm [35 in.--lbs]

NEMA, National Electrical Code, and NEC are trademarks of their respective owners.

The combiner box assemblies meet the standards of

Underwriters Laboratories Inc. (UL) 1741 to be used

as an accessory for inverters.
Reasons for reissue of this instruction sheet are

provided in Section 5, REVISION SUMMARY.

IMPORTANT

SAFETY INSTRUCTIONS

SAVE THESE INSTRUCTIONS

This instruction sheet contains important instructions

for Assemblies 1954283--1 and 1954283--2 that must

be followed during installation and maintenance of the

power system.
Read and understand the following safety precautions

before

installing or working with the combiner box

assembly.

— Wiring methods must comply with the National

Electric Code (NEC) and American National

Standards Institute (ANSI)/National Fire Protection

Association (NFPA).
— The DC input and DC output circuits are isolated

from the enclosure. System grounding, if required

by Section 250 of the NEC and ANSI/NFPA 70, is

the responsibility of the installer.
— The photovoltaic system grounding must be

installed according to the requirements of Sections

690.41 through 690.47 of the NEC, ANSI/NFPA

70, and is the responsibility of the installer.
— DO NOT work with the combiner box assembly

if it is attached to any live electrical source.

NOTE