6.2 Input Wiring and Fusing
8.3 Three phase four wires
Choose fuses of a type and with a breaking capacity appropriate
to the supply and in accordance with local regulations.
7.2 Appearance
A switch or circuit breaker allowing isolation of supplies to the unit
must be provided where practical. In primary metering
applications, ensure the supply is isolated before any
maintenance on the product. Tampering with the product seals
may contravene local laws.
6.3 Wire Size
Voltage and current terminal blocks will accept 2.5mm² stranded
cable.
6.4 Maintenance
The front of the case should be wiped with a dry cloth only, using
minimal pressure. If necessary wipe the rear case with a dry
cloth.
No user serviceable parts.
8 Wiring Diagram
8.1 Single phase two wires
7 Meter
Explanation of Symbols
7.1 Dimensions
Refer to manual
Danger of electric shock
Do not discard
8.2 Three phase three wires
While TE has made every reasonable effort to ensure the accuracy of the information in this catalogue, TE
does not guarantee that it is error-free, nor does TE make any other representation, warranty or guarantee
that the information is accurate, correct, reliable or current. TE reserves the right to make any adjustments to
the information contained herein at any time without notice. TE expressly disclaims all implied warranties
regarding the information contained herein, including, but not limited to, any implied warranties of
merchantability or fitness for a particular purpose. The dimensions in this catalogue are for reference
purposes only and are subject to change without notice. Specifications are subject to change without notice.
Consult TE for the latest dimensions and design specifications. TE connectivity (logo), TE (logo) and TE
Connectivity are trademarks of the TE Connectivity Ltd. family of companies. Crompton is a trademark of
Crompton Parkinson and is used by TE Connectivity under a licence. Other logos, product and company names
mentioned herein may be trademarks of their respective owners
TE Energy – innovative and economical solutions for the electrical power industry: cable
accessories, connectors & fittings, insulators & insulation, surge arresters, switching
equipment, street lighting, power measurement and control.
Tyco Electronics UK Ltd
TE Energy
Freebournes Road
Witham, Essex CM8 3AH
Phone: +44 (0)870 870 7500
Fax: +44 (0)870 240 5289
Email: [email protected]
www.crompton-instruments.com
Project 2305. Drawing No. CI-3L32301 Rev.2
10/12/19
Rate
can be set to generate 1 pulse per:
0.01 = 10 Wh/VArh
0.1 = 100 Wh/VArh
1 = 1 kWh/kVArh
10 = 10 kWh/kVArh
100 = 100 kWh/kVArh
Pulse width
200/100/60 ms.
5.4.2 RS485 Output for Modbus RTU
For Modbus RTU, the following RS485 communication
parameters can be configured from the set-up menu:
Baud rate
2400, 4800, 9600, 19200, 38400
Parity
none (default) / odd / even
Stop bits
1 or 2
RS485 network address
nnn
– 3-digit number, 1 to 247
Modbus™ Word
order Hi/Lo byte order is set automatically to
normal as defined by IEEE 754. It cannot be configured from the
set-up menu.
5.5 Reference Conditions of Influence Quantities
Influence Quantities are variables that affect measurement errors
to a minor degree. Accuracy is verified under nominal value
(within the specified tolerance) of these conditions.
• Ambient temperature
• Input waveform
• Input waveform
23°C ±1°C
50 or 60Hz ±2%
Sinusoidal (distortion
factor < 0·005)
factor < 0·05)
Terrestrial flux
(if AC)
• Magnetic field of
external origin
5.6 Environment
• Operating temperature
• Storage temperature
• Relative humidity
-25°C to +55°C*
-40°C to +70°C*
0 to 95%,
non-condensing
Up to 3000m
1 minute
10Hz to 50Hz, IEC
60068-2-6, 2g
30g in 3 planes
• Altitude
• Warm up time
• Vibration
• Shock
*Maximum operating and storage temperatures are in the context
of typical daily and seasonal variation.
5.7 Mechanics
• DIN rail dimensions
76 x 100 mm (WxH)
per DIN 43880
DIN rail (DIN 43880)
IP51 indoor
UL 94 V-0
Self-extinguishing
• Mounting
• Sealing
• Material
6 Installation and Maintenance
6.1 Installation notes
Units should be installed in a dry position, where the ambient
temperature is reasonably stable and will not be outside the
range -25 to +55
⁰
C.
Vibration should be kept to a minimum.
Preferably, mount the Integra so that the display contrast is not
reduced by direct sunlight or other high intensity lighting.
8.4 Additional Connections
5.4.3 Tariff Input
The energy can be measured for two tariffs. The tariff is
changed by applying 230v to terminals 2T.