TE Connectivity 549 AC Installation And Operating Instructions Download Page 3

 
 

A

B

C

D

H

E

I

J

K

in

mm

A

1.86
47.3

B

1.60
40 .8

C

0 .47

12.0

D

1.74
44.4

E

0 .70

17.8

F

0 .87

22.1

G

0 .99

12.0

H

0 .51
13.0

I

0 .16

4.0

J

K

1.0 8
27.5

1.18

30 .0

PAN EL CU T-O U T 2

PAN EL CU T-O U T 1

D

A

E

B

C

(U SE AD APTO R RIN G)

AD APTO R RIN G

F

G

in

mm

A

1.20

30 .5

B

0 .57

14.5

C

0 .25
6.40

D

1.0 9

27.8

E

0 .15

3.9

GU ID E N O TES FO R U SIN G SU PPLIED  FITTIN G KIT.

1) PLACE IN STRU M EN T IN  PAN EL CU TO U T.
2) FIT AD APTO R RIN G , IF U SIN G CU TO U T 1.
3) FIT RETAIN IN G RIN G, EN SU RIN G TABS ARE ALIGN ED  AS SH O W N .
    (APPRO X 45 D EGREE AN GLE RELATIVE TO  GRO O VES IN  CASE)
4) IM PO RTAN T - N U T 'A' IS U SED  FO R FACTO RY ASSEM BLY O N LY AN D
    M U ST N O T BE TAM PERED  W ITH  D U RIN G IN STALLATIO N .
5) FIT N U T 'B', EN SU RIN G A N O M  3mm GAP IS LEFT BETW EEN  IT AN D  N U T 'A'
6) FIT W ASH ERS PRIO R TO  AN D  AFTER CO N N ECTIO N  W IRES.
7) FIT N U T 'C'.
8) EN SU RE N U T 'B' IS REFRAIN ED  FRO M  M O VEM EN T.
9) N U T 'C' SH O U LD  N O W  BE TIGH TEN ED .

RETAIN IN G RIN G

RETAIN IN G RIN G

AD APTO R RIN G

A BC

IM PO RTAN T

SEE N O TES 4 - 9

 

 
 
Connection Diagram 
 

N

L

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
                       
 
 
 
 
 
 
 

 
Reference Conditions of Influence Quantities 

Influence Quantities are variables that affect measurement errors 
to  a  minor  degree.    Accuracy  is  verified  under  nominal  value 
(within the specified tolerance) of these conditions. 

Ambient temperature 

23°C ±2°C 

Input waveform 

60Hz ± 0.5% 

Input waveform 

Sinusoidal 
(distortion factor <0·005) 

Magnetic field of external 
origin 

Terrestrial flux 

Environment 

Operating temperature 

-10°C to +55°C

*

 

Storage temperature 

-30°C to +85°C

*

Maximum operating and storage temperatures are in the context 

of typical daily and seasonal variation. 

Relative humidity 

0 to 95%, non-condensing 

Altitude 

Up to 2000m 

Vibration 

10Hz to 50Hz, IEC 60068-2-6, 2g 

Shock 

30g in 3 planes 

Mechanics 

Dimensions 

40.80x47.25x59.25mm (h x w x d) 

1.60”x 1.86”x2.33” (h x w x d) 

Depth (behind panel)  2.36” (60 mm) maximum 

Case protrusion 

(front of panel) 

0.48” (12.2 mm) maximum 

Sealing 

IP52 (front panel), IP30 (case) (minimum) 

 

 

Approval, Certification, and Standards Compliance 

EMC, Emissions 

FCC Part 15 

Safety 

UL 61010-1:2

nd

 edition. 

 
 
 
 

 

While TE Connectivity (TE) has made every reasonable effort to ensure the accuracy of the information in this catalogue, TE does not guarantee that it is error-free, nor does TE make any other 
representation, warranty or guarantee that the information is accurate, correct, reliable or current.  TE reserves the right to make any adjustments to the information contained herein at any time 
without notice.  TE expressly disclaims all implied warranties regarding the information contained herein, including, but not limited to, any implied warranties of merchantability or fitness for a 
particular purpose.  The dimensions in this catalogue are for reference purposes only and are subject to change without notice.  Specifications are subject to change without notice.  Consult TE 
for the latest dimensions and design specifications.  TE Connectivity and TE connectivity (logo) are trademarks.  CROMPTON is a trademark of Crompton Parkinson Limited and is used under 
licence.  Other products or company names mentioned herein may be trademarks of their respective owners. 

Tyco Electronics UK Ltd 

Registered office: 

A TE Connectivity company 

Faraday Road, Dorcan 

Freebournes Road, 

Swindon, SN3 5HH 

Witham, CM8 3AH, UK 

Reg. No. 550 926 

Tel: +44 (0) 1376 509509 
Fax: +44 (0) 1376 509511 
www.crompton-instruments.com

 

www.energy.te.com 

Project 2208. Drawing No. CI-3K68901 Rev.K DMR 2777 28/02/13 

Reviews: