background image

Revision H : December 2009

Page. 6

LZS-A

A1000-33  Power  Supply

Protection Features

Table      9

Output Voltage Range

V

18-29.4V

Nominal Factory Set Point

V

24V

Overvoltage Protection (adjustable)

V

20-34V (Factory set to 31.0V)

Overcurrent Protection

-

Factory set to 110% min. and 130% max.

Thermal Protection

-

Self-resetting thermostat.*

Fusing

-

Internal

Isolation Voltages

-

4242 VDC, Input to Output

2121 VDC, Input to Chassis Ground

500 VDC, Output to Chassis Ground

Regulatory Agency Compliance

-

UL 60950-1/CAN CSA C22.2 No. 60950-1-03, First Edition

UL 508, Seventeenth Edition

EN 60950-1:2001+A11, IEC 60950-1:2001,

IEC61000 2nd Edition

FM 3600, FM 3611, FM 3810, Semi F47

Leakage current (AC line to 

µA

Less than 500 µA @ 265 VAC, 60 Hz

chassis ground)

Mechanical Features

Units

Table    10

Storage Temperature (non-operating)

°C

-40°C - +85°C

Weight 

lbs

8.1 lb net

Size

inches

5.62” x 4.75” x 10.5”

Finish

-

Textured gray - painted

Mounting

-

One mounting surface (mounting position not restricted)

Maximum allowable penetration into power supply is 

1/4”.  Requires No. M4 (metric) hardware - supplied

with unit.)

Input and Output Connections

Table    11

Input

Heavy duty terminal block

Chassis Ground

Tapped hole and screw provided in chassis.

DC Output

Heavy-duty bus bars with 1/4” clearance holes for load connections.

(Connection hardware supplied with unit.)

Local/Remote voltage sensing, Four-position lugless connector (TB201), see Fig. 1.

Remote on/off, Parallel operation. (Accepts up to #14 AWG size stripped wire).

Auxiliary Control and Alarm Signals Connections for remote and local sensing, remote on/off, parallel operation

current sharing, input power good signal, OV alarm, UV alarm, inverter 

good signal and chassis are available via chassis mounted, 15-pin, 

female, sub-miniature “D” connector (see Fig. 1).

Other Features

Table    12

Warranty

5 years

Cooling

Variable speed, Ball Bearing Fan

Fungus Inert

All LZS power supplies are inherently fungus inert.

Humidity

10%-90% Non-condensing

Altitude

0-10,000 Ft (Operating); 40,000 Ft (Non-Operating)

* See “Overtemperature and Overvoltage Shutdown” on page 7

Summary of Contents for LZS-A1000-3

Page 1: ...LZS A1000 3 POWER SUPPLY Installation Operation and Maintenance Manual IM L LZSA1000 3 3 December 2009 Revision H...

Page 2: ......

Page 3: ...Practices 2 1 1 General safety instructions 2 1 2 Safety Agency Approvals 2 2 RATINGS AND SPECIFICATIONS 4 3 FEATURES 5 4 GUIDE TO APPLICATION 7 4 1 Safety Notice 7 4 2 Input Voltage 7 4 3 Output Vol...

Page 4: ...Therefore screws at the case must not be removed or loosened 7 The output power taken from the power supply must not exceed the rating stated on the power supply label 8 Openings in the product case a...

Page 5: ...cal Fast Transients IEC61000 4 4 2 kV AC Line Criteria A 1 kV I O Line 3m Criteria A Lightning Surge IEC61000 4 5 2 kV line to GND CM Criteria A 1 kV line to line DM Criteria A Conducted RF Common Mod...

Page 6: ...ode Input EMI Conducted Emissions FCC Class B CISPR 22 Class B Efficiency at max output power 83 typical 110VAC line Output Performance Specifications Units LZS A1000 3 Table 4 Voltage Line Regulation...

Page 7: ...able output via TTL compatible signal connected between pins 6 and 7 of D connector see Fig 9 Signals Isolation Pins 6 and 7 are fully isolated from all other power supply terminals Signal Logic Logic...

Page 8: ...urface mounting position not restricted Maximum allowable penetration into power supply is 1 4 Requires No M4 metric hardware supplied with unit Input and Output Connections Table 11 Input Heavy duty...

Page 9: ...point When adjusting the output voltage above 24 0V ensure that there is sufficient OVP margin with respect to the output voltage to avoid nuisance tripping 4 4 OVERVOLTAGE PROTECTION CIRCUIT ADJUSTM...

Page 10: ...Revision H December 2009 Page 8 LZS A A1000 3 3 Power Supply Figure 1 PIN Assignments for TB201 and chassis mounted D connector 5 Figures...

Page 11: ...CA 92154 1 800 LAMBDA 4 LZS A A1000 3 3 Power Supply Revision H December 2009 Page 9 Figure 3 Typical Remote Sense Connection Figure 2 Typical Local Sense Connection LS Local Sense S Remote Sense LS...

Page 12: ...igure 5 Remote Voltage Control with an External Programming Resistor or Voltage Source Remote Sensing Figure 4 Remote Voltage Control with an External Programming Resistor or Voltage Source Local Sens...

Page 13: ...3055 Del Sol Blvd San Diego CA 92154 1 800 LAMBDA 4 LZS A A1000 3 3 Power Supply Revision H December 2009 Page 11 Figure 6 Parallel Operation...

Page 14: ...LZS A A1000 3 3 Power Supply Revision H December 2009 Page 12 Figure 7 Series Operation...

Page 15: ...3055 Del Sol Blvd San Diego CA 92154 1 800 LAMBDA 4 LZS A A1000 3 3 Power Supply Revision H December 2009 Page 13 Figure 8 Outline Drawing AIR FLOW...

Page 16: ...LZS A A1000 3 3 Power Supply Revision H December 2009 Page 14 Figure 9 Remote Output On Off Control Figure 10 Input Good Inverter Good Output Good Signals...

Reviews: