TDK-Lambda HWS ME Series Instruction Manual Download Page 5

 

TDK-Lambda 

HWS 

30A-150A/ME

 Series 

INSTRUCTION MANUAL

 

 

3. Connecting method 

Pay attention to the input wiring. If it is connected to wrong terminal, the power supply will be damaged. 

·

 

Input must be off when making connections. 

·

 

Connect FG terminal to earth (frame ground of the equipment etc.) by thick wire for safety and improvement of 
noise sensitivity. 

 

HWS30A/ME, HWS50A/ME 

 
 
 
 
 
 
 
 

 
 
 
 
 

 
 

 

HWS100A/ME, HWS150A/ME

Basic connection (Local sensing) 

Connect “+S” terminal to “+V” terminal, and   
“-S” terminal to “-V” terminal with the attached   
short pieces .   
(Short pieces are mounted at time of shipment.) 

 

Remote sensing connection 

Connect “+S” terminal to “+” terminal of load, and   
“-S” terminal to “-” terminal of load with wires.   

If remote sensing terminals are opened, the output will rise   
and OVP may be triggered.

 

 

 

 

 

                 

 

 

 

 

 

 

 

 
 

Recommended torque : HWS30A/ME - HWS150A/ME 

    M3.5 screw    1.0N

m(10.2kgf

cm) - 1.6N

m(16.3kgf

cm) 

 
 
 

+

Load

-

Summary of Contents for HWS ME Series

Page 1: ...Output power ambient temperature and ambient humidity should be kept within specifications otherwise the product will be damaged Do not operate and store this product in an environment where condensa...

Page 2: ...g parameters Material Group IIIb Pollution Degree 2 Overvoltage Category II Class I earthed Indoor use as part of an overall equipment such that the product is accessible to service engineers only EMC...

Page 3: ...xygen or with nitrous oxide No 3 These products are classed as ordinary equipment according to IEC EN ES CSA60601 1 and are NOT protected against the ingress of water 4 The output circuit has not eval...

Page 4: ...stment trimmer Output monitoring indicator Green LED All screws size is M3 5 HWS100A ME HWS150A ME V Output terminal 30A max terminal V Output terminal 30A max terminal FG Frame Ground L Input termina...

Page 5: ...nt of noise sensitivity HWS30A ME HWS50A ME HWS100A ME HWS150A ME Basic connection Local sensing Connect S terminal to V terminal and S terminal to V terminal with the attached short pieces Short piec...

Page 6: ...Power thermistor method so that higher current will flow at higher ambient temperature or re input condition Please select input switch and fuse carefully with the high temperature and re input the p...

Page 7: ...e load terminal 2 Between S terminal and V terminal 3 Between S terminal and V terminal If remote sensing terminals are opened the output will rise and OVP may be triggered 4 7 Output Ripple Noise The...

Page 8: ...he power supply output voltage higher by the amount of forward voltage drop VF of the diode 2 Please adjust the output voltage of each power supply to be the same 3 Please use within the specification...

Page 9: ...o frame ground Some of the withstand voltage tester may generate high voltage at the matching with monolithic ceramic capacitor and may cause the unit damage So please check the waveform of test volta...

Page 10: ...of mounting screws is 6mm 4 Recommended torque for mounting screw HWS30A ME HWS150A ME M3 screw 0 49 N m 5 0 kgf cm 5 2 Output Derating according to the Mounting Directions Recommend standard mounting...

Page 11: ...WS30A ME HWS50A ME HWS100A ME Ta Load Mounting A B C D 10 50 100 60 60 70 40 Ta Load Mounting A Mounting B D Mounting C 10 45 100 100 100 50 100 100 86 60 70 65 58 70 40 30 30 Ta Load Mounting A Mount...

Page 12: ...minal M3 5 Screws 1 0N m 10 2kgf cm 1 6N m 16 3kgf cm 6 8mm 0 8mm 2 piece HWS100A ME AWG12 22 Output terminal M3 5 Screws 1 0N m 10 2kgf cm 1 6N m 16 3kgf cm 8 1mm 1 0mm 1 piece 0 8mm 2 piece AWG14 22...

Page 13: ...ME 3 15A HWS150A ME 5A 9 Before concluding that the unit is at fault Before concluding that the unit is at fault make the following checks 1 Check if the rated input voltage is connected 2 Check if t...