2.2 SERIES OPERATION
•
Up to 2 units with the same rating (voltage and current) can be used in series to increase the output voltage:
•
Connect Main Output in series (as shown);
•
Diodes should be connected in parallel with each unit output to prevent reverse voltage. Each diode should be rated to at least
the power supply rated output voltage and output current.
•
Connect as shown : +Sense of positive unit and –Sense of negative unit (twisted pair) to Load point, or to +V and –V accordingly
for Local Sense;
•
Output Voltage can be adjusted independently for each unit.
•
Controls Monitoring signals and +12V AUX are referenced to “SIGNAL RETURN” and may be connected in parallel.
Fig 2.2 HFE1600 series connection (remote sense configuration)
-V
A6~10
-V
A1~5
B1
+V
A6~10
HFE1600
B1
SIGNAL RETURN
-SENSE
B4
-V
A1~5
+SENSE
B9
B4
-SENSE
+SENSE
B9
+V
SIGNAL RETURN
ENABLE
B7
LOAD
ENABLE
B7
+V
HFE1600
*
Diodes rated for at least Vout max and lout max
are supplied by user.
IA688-04-01-R
ev I
12