Product HANDBOOK
DPX Series
Cooling for unit
The unit must be mounted on a DIN rail and must not be inverted, the output connection uppermost.
Installation orientation:
TOP
The ventilation openings on these products must not be impeded. Ensure that there is at least 50mm
spacing
between any obstruction and the ventilation openings. Do not obstruct vents.
The unit cover/chassis is designed to protect skilled personnel from hazards. They must not be used as part
of the external covers of any equipment where they may be accessible to operators, since under full load
conditions, part or parts of the unit chassis may reach temperatures in excess of those considered safe for
operator access.
Ventilation slots located top and bottom of product
.
Higher temperature limits (in brackets) may be used but product life may be reduced.
EMC Performance:
Test
Standard
Passed
Comments
Criteria
Conducted emissions
EN55022
Class B
Electrostatic discharge
EN61000-4-2
Level 3
Level 2
Air discharge 8kV
Contact discharge 6kV
A
A
Electromagnetic field
EN61000-4-3
Level 3
Tested to 10V/m
A
Fast / burst transient AC
Input
EN61000-4-4
Level 3
Tested to 2kV
A
Surge immunity
EN61000-4-5
Level 3
Common mode to 1kV
A
Conducted RF immunity
EN61000-4-6
Level 3
Tested 10Vr.m.s
A