TDK-Lambda DPP480-XX-3 Installation And Operation Download Page 2

Connection / Internal fuse

External circuit breaker

    recommended circuit breaker: Mitsubishi, Type  NF30-CS, rated 

    20A max or equipollent of TUV/VDE/UL approved sources.

     For input line  protection observe national  regulations; recommended 

Connection (See Fig. 3)

    Data for permitted loads, cable cross-sections and stripping:
    Use only commercial cables designed for the indicated
    voltage and current values!
    With flexible cables: make sure that all stranded cable are
    secured in the terminal.
    Ensure proper polarity at output terminals!

Grounding

    

Do not operate without PE connection!

 To comply with

    EMC and safety standards (CE mark, approvals), the unit
    must only be operated if the PE terminal      is connected to
    the non-fused earth conductor.
    Secondary side is not earthed; if necessary the       or       
    terminal can be earthed optionally.

Internal fuse

    The internal input fuse serves to protect the unit and must
    not be replaced by the user. In case of an internal defect, the
    unit must be returned to the manufacturer for safety reasons.

+

-

DM172-A2

Technical Data

All specifications are typical at norminal line, full load,
25

; Unless otherwise noticed.

o

C

Eff.

[typ.]

Inrush Current

400/500Vac

480

VO [V]

24

48

Io [A]

20

10

90%

91%

< 20A

Output

Wattage

General Specification

Isolation ................................ 3000 Vac / 4242 Vdc
Isolation Resistance................. 100 M ohm
Operation amb. Temperature .... -25 ~ +71 
Storage Temperature ............... -25 ~ +85 
Derating................................. +61 ~ +71 
Relative Humidity.................... 20 ~ 95% RH
Cooling ..................................  Free  air convection
Temperature Coefficient ........... 0.03% / 
Dimension.............................. L124 x W150 x D118.8 [mm] 
Weight................................... 1720g

o

C

o

C

o

C (see Fig. 5)

o

C

Input Specification

Rated Input Voltage ................. 3

    4

  00 - 500 V

  ac

Input Voltage Range................ 3   340 ~ 575 Vac
Rated Input Current................ 1.4A
Line Frequency.......................   47 -  63 Hz
Power Factor..........................  0.6

Fig. 5 Derating

0

100

o

 Temperature [  C ]

71

-25

P

o

w

e

o

u

%

 ]

61

75

Output Specification

Output Accuracy.................... -0%, +1%
Line  Regulation .....................  +/-  1%
Load Regulation.................... +/- 1% for single mode

                                                5%  for parallel mode

Ripple &  Noise ...................... 100  mV
Voltage Trim Range ............... 22.5 ~ 28.5 Vdc for 24V model
                                             47 ~ 56 Vdc for 48V model
DC ON Indicator.................... Green LED
DC LOW Indicator.................. Red LED
Parallel Operation.................. 2 unit max.
Turn on time......................... <1000ms
Fall time............................... <150ms
Rise time.............................. <150ms
Hold Up Time........................ >20ms
Case m

 aterial. ....................... Metal

Control And Protection

Input Internal Fuse............... T3.15A / 500 Vac internal / phase
Output Short Circuit ............. Continuous : Fold Forward
                                            Discontinuous : Delay 3S shut-down, 
                                             After  30S Auto-restart
Output Over Load................. 110 % ~ 135 %

Approvals And Standard

UL / cUL.............................. UL 508 Listed, UL 60950-1 Recognized
TUV. ................................... EN 60950-1
CE...................................... EN 61000-6-3, EN 55022 class B 
                                             EN  61000-3-2,  EN61000-3-3
                                             EN  61000-6-2,  EN  55024
                                             EN  61000-4-2,  -3,  -4,  -5,  -6,  -8,  -11
                                             EN  61204-3
                                            
                        

Application

  

 

     

 

 

 

 

This unit is a primary switched-mode power supply designed

  

 

 

 

 

 

 

for use in panel-board installations or building-in

  

    

 

   

 

 

applications

where access to the supply is restricted (shock-

  

 

   

 

 

 

 

 

 

hazard protection). It must only be installed and put into service

  

 

 

 

appropriately by qualified personnel.

Installation

Mounting

Operation indicator

  

 

 

 

 

  

 

 

Indicates whether the unit is working properly. Green LED is

  

  

 

  

 

 

 

   

 lit on if the voltage at the output terminal is more than 75%.

  

 

DC output low indicator

  

 

 

  

 

 

Red LED is lit when the voltage at the output terminal is 70%

  

 

 

 to 90% of the rated output voltage.

Potentiometer

 Used to set the output voltage.

Front elements

Mounting (See Fig. 1)

  

 

 

 

 

 

 

 

Permissible mounting position: keep free ventilation hole, leave

  

 

  

 

 

 

  space for cooling! Recommended to have 25mm free space
  

 

 

 

 

   

at all sides for ventilation / cooling:

  

   

   

Snap on support rail (See Fig. 2)

    

 

 

 

 

 

 

Fit the unit over top hat rail.

    

   

 

   

 

 

Slide it downward until it hits the stop.

    

 

 

 

 

 

 

 

Press against the bottom front side for locking.

   

 

 

 

 

Tilt the unit slightly rearwards.

 

    

 

 

 

 

 

 

 

 

Shake the unit slightly to check the locking action.

Disconnect system from supply network

  Before any installation, maintenance or modification work:

  Disconnect your system from the supply network. Ensure that

it cannot be re-connected inadvertently!

In operation: No modifications!

  As long as the unit is in operation: do not modify the
  installation! The same applies also to the secondary side.
  Risk  of electric arcs and electric shock (fatal)!

 

Only (dis) connect plug connectors when

 the power is off!

Convection cooling (See Fig. 1)

  

Do not cover

 any ventilation holes!

  

Leave sufficient space

 around the unit 

for cooling!

Warning: High voltage! Store energy!

  The unit contains unprotected conductors carrying a lethal
  high voltage, and components storing substantial amounts 
  of energy. Improper  handling may result in an electric shock  
  or serious burn!

    personnel!

    The unit must not be opened except appropriately trained

    Do not introduce any object into the unit!
    Keep away from fire and water!

Safety notes

Before start of operation
Ensure appropriate installation

Warning! Improper installation / operation impair safety and
result in operational difficulties or complete failure of the unit.
The unit must be installed and put into service appropriately
by qualified personnel. Compliance with the relevant
regulations must be ensured.Before operation is begun the
following conditions must be ensured, in particular: 

    Connection to main power supply in compliance with
    VDE01000 and EN50178.
    With stranded wires: all strands must be secured in the
    terminal blocks (Potential danger of short circuit).

     necessary a manually controlled disconnecting element  must be 

   used to disengage from supply mains.

    Unit and power supply cables must be properly fused; if 

    All output lines must be rated for the power supply output
    current and must be connected with the correct polarity.
    Sufficient air-cooling must be ensured.

    The non-fused earth conductor must be connected to the 
    "     " terminal (protection class 1). 

    pollution degree 2 environment.

Read Instructions!

  Before working with this unit, read these instructions carefully
  and completely. Make sure that you have understood all the
  information!

Removal

 

from DIN Rai

 (See Fig. 4)

Removal

    Insert a flat screwdriver into the slot in the clamp. Pull the
    clamp down until it clicks off the Din rail, then, from the
    bottom, lift the power supply up and away.  