Installation
No Communication with RS-485 Ports (COM 1 and 2), Ubiquity Time-out, or No Data
Each port on the QD2040b has the proper biasing resistors as specified by TCSbus and Modbus standards. Each port is
also optically isolated, which cleans up the signal and also protects the unit from taking stray voltage off the RS-485 lines.
A set of LEDs on each of the RS-485 ports on the QD2040b allow the building occupant to view operational status of the
serial communication integrated board:
•
GREEN – blinking indicates transmitting (Tx)
•
YELLOW – blinking indicates receiving (Rx)
If neither of these lights are functioning, there could be a bad connection, a bad cable, a bad ground, or a bad component.
Contact TCS Technical Support (800-288-9383, ext. 2)
for assistance
.