TCS TrainSpeed 4 Operating Manual Download Page 4

 

Sensor placement 

All four sensor pairs of the TrainSpeed 4 must use the same 
spacing.  The sensors are designed to use available ambient 
light.  Mounting them in tunnels or dark corners of the layout 
is not recommended.  It is best to pick a well lit section of the 
layout where the light source comes from above and ‘inside’ 
the layout.  If the light source is ‘outside’ the layout a person 
walking by may trigger the unit.  The included sensor cables 
are ten feet long.  Cable extensions can be purchased or made.  
The TrainSpeed 4 display unit will work with cables as long as 
30 feet.  See the appendix for cable extension construction. 
 
Note that you do not need to use all four sensors if you do not 
need them.  The unit will figure out which sensors are missing 
and only use the sensors that are connected. 
 
Using a #20 drill bit (5/32” also works but is a bit tighter), 
drill the sensor holes through your roadbed and sub-roadbed to 
the chosen spacing (watch out for switch machines and the 
like under the layout when choosing the location of the 
sensors).  Make sure that the edges of the holes are ‘clean’, 
especially on the bottom as this will make sensor insertion 
much easier.  The sensors should then be inserted into the 
holes from the bottom and pushed up until the top of the 
sensor is flush with the top of the ties.  

Warning:  Power to 

the rails should be off when inserting the sensors, 
especially if you are using DCC.

  An insertion tool can be 

made out of small tubing by cutting a slot in the tubing to 
provide clearance for the wires.  This tubing can then be used 
to push the sensor up through the hole to avoid damaging the 
wires.  If you are having trouble getting the sensor through the 
roadbed use a larger drill bit (the #20 and/or 5/32” bits provide 
a ‘press fit’ for the sensors that will usually hold them in place 
without any adhesive or tape).  Make sure the sensors do not 
exceed the railhead height as you will damage them the next 
time you clean the rails with an abrasive rail cleaner.  If 
needed the ribbon cable can be split easily for wider sensor 

Summary of Contents for TrainSpeed 4

Page 1: ...TrainSpeed 4 Four separate train speed indicators Model Railroad Speedometer Operating Manual TCS Inc 215 453 9145 Main Number 215 257 0735 Tech Number www tcsdcc com SKU 1548...

Page 2: ...ng with four 4 screw clearance holes If you are using a clear plexiglass control panel then you can mount the unit behind a clear window instead of cutting a hole in the panel The layout for these hol...

Page 3: ...99 11 49 5 75 cm OO 76 1315 78 52 62 26 31 13 16 6 58 cm O 48 2083 33 83 34 41 67 20 83 10 42 cm S 64 1562 50 62 5 31 25 15 63 7 81 cm G 24 4166 67 166 66 83 33 41 67 20 83 cm TT 120 833 33 33 34 16 6...

Page 4: ...chosen spacing watch out for switch machines and the like under the layout when choosing the location of the sensors Make sure that the edges of the holes are clean especially on the bottom as this w...

Page 5: ...old the cables in place as they can cut the insulation and cause shorts If you must anchor the cables to the benchwork staple a cable tie to the benchwork and then wrap the cable tie around the sensor...

Page 6: ...wall transformer specifications The unit needs at least 6V to operate correctly and the supply voltage should not exceed 18V AC or DC The unit requires less then 100ma current to function The wires f...

Page 7: ...7 6v 18v AC or DC Input polarity does not matter Figure 1 Sensor 1 Pin 1 Sensor 2 Pin 1 Sensor 3 Pin 1 Sensor 4 Pin 1 Power Connector J5 Test jumper Option Jumpers...

Page 8: ...talled then there is a problem with that sensor pair For example if sensor pair 2 was not connected or connected incorrectly the display would look like this 43 1 At power up the unit will scan the fo...

Page 9: ...t digit of the display with the rest of the display blank Once the second sensor is tripped you will see the scale speed displayed on the unit 2 30 This shows that sensor 2 was activated and the train...

Page 10: ...ut two minutes on the 1 100 jumper setting for this message to be displayed The unit will display normal speed for the next train whenever any of these errors occur If the message Er 1 is displayed it...

Page 11: ...e you will need to power down and power up the TrainSpeed board to initialize it correctly One common occurrence with the connector used is that only one row of pins is covered by the connector If you...

Page 12: ...y H the display would look like this L3H When a sensor is covered in the dark the test display for that sensor should read H When the sensor is lit you should see an L in the test display For the unit...

Page 13: ...ensor in question as outlined above and cover the sensor completely and tightly with a dark opaque material usually a hand pressed down firmly will do If you see a change in the display from L to H th...

Page 14: ...P x followed by Sn E then one of the sensor cables has been damaged Plug them in one at a time until you isolate the problem cable Inspect this cable for damage and contact TCS Inc for a replacement i...

Page 15: ...he connector Wall transformers Radio Shack AC adaptors NTE 57 9D 600 4 or NTE 57 9D 600 2 will work with this unit Cut the circular connector off that comes with the adapter strip and tin the wires an...

Page 16: ...16 TCS Inc 215 453 9145 Main Number 215 257 0735 Tech Number www tcsdcc com...

Reviews: