COOL MINIMUM POSITION:
0%
29.
COOL MAXIMUM POSITION:
80%
30.
HEAT MINIMUM POSITION:
10%
31.
HEAT MAXIMUM POSITION:
100%
32.
AO1 MOTOR
TIME: 1.5 MIN
33.
AO2
ACTION: DIRECT
34.
AO2
CHOICE: MOD
ULATING
35.
AO2 MODE
IS: COOL
36.
AO2 SETPOINT
OFFSET 0.0
37.
AO2 PROP
BAND: 10%
38.
AO2 OUTPUT
RANGE: 0-20mA
39.
AO2 MOTOR
TIME: 1.5 MIN
40.
STAGE 1
DIFF: 2F
43.
STAGE 2 MODE
AS: COOL
44.
STAGE 2
OFFSET: 0F
45.
STAGE 2
DIFF: 2F
46.
Pressure Dependant Screen.
Enter in %
the min cooling damper position.
Pressure Dependant Screen.
Enter in %
the max cooling damper position.
Pressure Dependant Screen.
Enter in %
the min heating damper position.
Pressure Dependant Screen.
Enter in %
the max heating damper position.
Enter floating motor time in min.
Anolog Output 2 Action Screen.
Choose whether the output will be direct
or reverse acting.
Anolog Output 2 Choice Screen.
Choose whether the output will be modu-
lating (AO2) or floating (NO7/NO8).
Anolog Output 2 Mode Screen.
Choose
whether the output will be used for heat-
ing or cooling.
Anolog Output 2 Setpoint Screen.
Enter the number of degrees you wish to
offset the output from setpoint.
Anolog Output 2 Proportional Band
Screen.
Enter in % of input span (40 to
90) the number of degrees away from
se deadband the offset that the
device will be fully open.
Anolog Output 2 Output Range Screen.
Choose wether the output range will be
0-20mA or 4-20mA.
Enter floating motor time in min.
Stage 1 Mode Screen.
Select wether the
relay control: HEAT, COOL, or FAN.
Stage 1 Offset Screen.
Enter an offset
valve for Stage 1.
Stage 1 Differential Screen.
Enter a dif-
ferential value for Stage 1.
Stage 2 Mode Screen.
Select wether the
relay control: HEAT, COOL or TCLK.
Stage 2 Offset Screen.
Enter an offset
valve for Stage 2.
Stage 2 Differential Screen.
Enter a dif-
ferential value for Stage 2.
STAGE 1 MODE
AS: HEAT
41.
STAGE 1
OFFSET 0F
42.