 CONFIGURATION 

GUIDE

202308

Communicating Thermostat

SuperSTAT SZ1053

Summary of Contents for SuperSTAT SZ1053

Page 1: ...2800 Laura Lane Middleton WI 53562 800 288 9383 www tcsbasys com CONFIGURATION GUIDE 202308 Communicating Thermostat SuperSTAT SZ1053 ...

Page 2: ...Keypad Access 4 Navigating Via Keypad 4 Program Setup Mode 5 Basic Setup 5 System Mode 5 Occupancy Settings 6 Heat Cool Digital Outputs 7 Time Clock 8 Modulating Outputs 8 Digital Inputs 10 Energy Saving 10 Keypad Access Code 11 Setting Clock and Schedule 11 Time and Date 11 Occupancy Schedules 12 Holiday Occupancy Schedules 12 Daylight Saving 13 Contents ...

Page 3: ...ing the device wiring the communications network and connecting other devices to the SuperSTAT Your configuration settings will be uploaded to Ubiquity Cloud the first time you make a connection to the site Alternatively you can skip configuring the SuperSTAT via the keypad and perform all configurations via Ubiquity Cloud or via a PC running TCS Insight software which is available for download on...

Page 4: ... times when enabled OVERRIDE Press when OCCUPIED LED is off to restore occupied temperature settings clock setup service status Press to review service screens Keypad service status fan switch system switch program setup clock setup OVERRIDE COOLER WARMER Occupied Heating Cooling Fan Service Data Program Navigating Via Keypad All settings on the SuperSTAT can be made via the keypad Each screen wil...

Page 5: ...ings TUE 07 04 23 9 00 AM 72F ENTER ACCESS CODE 000 If the SuperSTAT has been configured to require an access code to enter PROGRAM SETUP Mode this screen will appear see Keypad Access Code on page 11 If you enter the wrong code the screen will revert to the main screen Basic Setup STEP 1 Controller Address Select a unique address between 0 and 255 excluding 248 each controller on a network must h...

Page 6: ...is occupied period OCCUPIED COOL SETPOINT A 75F STEP 8 Occupied Cool Setpoint A Set the cooling setpoint for this occupied period UNOCCUPIED HEAT SETPOINT 60F STEP 7 Unoccupied Heat Setpoint Set the Unoccupied Mode s heating setpoint OCCUPIED HEAT SETPOINT B 70F STEP 4 Occupied Heat Setpoint B Set the heatpoint for the occupied period OCCUPIED HEAT SETPOINT C 70F STEP 5 Occupied Heat Setpoint C Se...

Page 7: ...t value normally 0 NOTE This screen will only display if Stage Output Step 1 is enabled STAGE 1 DIFF 01F STEP 3 Stage 2 Differential Enter a stage 1 differential value NOTE This screen will only display if Stage Output Step 1 is enabled STAGE 2 OFFSET 00F STEP 4 Stage 2 Offset Enter a stage 2 offset value normally 0 NOTE This screen will only display if Stage Output Step 1 is enabled STAGE 2 DIFF ...

Page 8: ...er will be fully open MOD OUT 1 UNOCC ACTION MOD STEP 9 Output 1 Unoccupied Action Select whether the unoccupied action will be 0mA 4mA 20mA or modulating MO1 SETPOINT OFFSET 00F STEP 3 Output 1 Setpoint Offset Enter the number of degrees below the heating setpoint before the output begins to modulate MO2 SETPOINT OFFSET 00F STEP 4 Output 2 Setpoint Offset Enter the number of degrees below the hea...

Page 9: ...ge air sensor function is enabled Step 11 MOD OUT 1 BASED ON DISCHARGE STEP 14 Output 1 Control Select whether to control the modulating output based on DISCHARGE air reset or SPACE temperature MOD OUT 2 BASED ON DISCHCHARGE STEP 15 Output 2 Control Select whether to control the modulating output based on DISCHARGE air reset or SPACE temperature ENABLE HEATING LOW LIMIT NO STEP 16 Heating Low Limi...

Page 10: ...s set to Monitor Step 2 DI3 USED FOR FILTER SERVICE STEP 4 DI3 Select FILTER SERVICE EXTERNAL OVERRIDE or EXTERNAL TIMECLOCK If DI3 is unused select EXTERNAL OVERRIDE Digital Inputs STEP 1 DI1 Select either FAN PROVING or MONITOR If DI1 is unused select MONITOR DI1 USED FOR MONITOR ENABLE OUTDOOR AIR FUNCT YES STEP 21 Outdoor Air Sensor Function Select whether you are using an outdoor air sensor T...

Page 11: ...age 4 Keypad Access Code STEP 1 Programming Access Select whether an access code is required to access Programming Setup NOTE Use dip switch settings to lock out access completely see Programming Keypad Access on page 4 REQUIRE CODE FOR PROGRAMMING YES Setting Clock and Schedule NOTE Access to the Clock and Schedule Mode can be completely disabled via dip switch settings see Programming Keypad Acc...

Page 12: ...FOR TUE NO STEP 5 Copy Schedules Select whether to copy the occupancy time periods from the previous day If you select YES the settings from the previous day s Steps 2 and 3 will be copied to the day shown and you will skip to the next day If you select NO the screens for Occupancy Time Periods will appear allowing you to enter different schedules for that day Repeat this process for each day of t...

Page 13: ...cupancy Time Periods 2 of 2 Set hours and minutes military time for start and stop times for occupancy periods C and D A 08 00 TO 17 00 B 00 00 TO 00 00 STEP 4 Occupancy Time Periods 1 of 2 Holiday 2 does not give you the opportunity to copy occupancy time periods from a regular day Set hours and minutes military time for start and stop times for occupancy periods A and B NOTE Occupancy time perio...