Installation
QWL2040 Panel at end of the
network.
QWL2040 Panel in middle of the
network.
1
3
2
Shielded, twisted two-conductor
communications wiring with one end
earth grounded. (120 Ω balancing
resistors provided.)
Shielded, twisted two-conductor
communications wiring with one end
earth grounded. (120
Ω
balancing
resistors provided.)
4
NOTES:
1. If using more than 64
controllers, use the second
RS485 port or additional QD1010
adapters.
2. Each controller must use the
same baud rate and be assigned
a unique address.
Two-Wire Network Wiring
Follow this wiring diagram for two-wire (Modbus) wiring systems (this is not common).
Two-wire diagram
A
B
Shield
A
B
A
B
Earth Ground
Only at one end
Drain
Wire
Last in Daisy Chain
120Ω
Terminating
Resistor
COM 1
REF
A
B
Drain
Wire
120Ω
Terminating
Resistor
A
B
A
B
A
B
Last in Daisy Chain
Shield
Last in Daisy Chain
Earth Ground
Only at one end
120Ω
Terminating
Resistor
A
B
A
B
A
B
Shield
Drain
Wire
COM 1
REF
REF
A
A
B
B
120Ω
Terminating
Resistor
1
2
3
3
4
4
4
COM 1
REF
A
B
COM 1
REF
A
B