TCS QD3041 Installation Manual Download Page 6

2800 Laura Lane  •  Middleton, WI 53562  |  800.288.9383  |  www.tcsbasys.com  

6

7

6

7

Installation

Startup

1. 

Verify all RS-485 connections from the controller network to the QD3041 are complete.

NOTE: 

Refer t

“QD3041 Power and Communication Connections” on page 

4

 for steps 2 through 5 below.

2. 

Verify that all 24V power wiring to the controller network has been completed; all controllers are powered on and 

each controller has been programmed with a unique BACnet MS/TP address and device ID.

3. 

Connect one end of the Ethernet cable to the Ethernet port (C) on the QD3041, and the other end to the network port 

provided by the customer, or to a cell modem (if utilized).

4. 

Connect the power source to the QD3041 and apply power. If your QD3041 shipped preconfigured, it will automatical

-

ly go online and contact Ubiquity Cloud. 

5. 

You MUST call TCS Technical Support (800-288-9383 ext. 2) to verify connection and activate the unit. 

6. 

If your QD3041 was not ordered preconfigured: You can configure it at this time. See the 

Configuration Section on 

page 8

.

Troubleshooting

Power LED Does Not Light Up

Be sure that the power supply module included with the QD3041 is plugged in to a 120VAC outlet that has power and 

the 12V, 5A tip positive barrrel socket is plugged into the unit. Press the power button on the front of the unit; a blue light 

should come on, indicating the unit ispowereed up.

No Communications with Controllers on the Network 

Make sure the baud rate selection for the QD3041 is set to match the baud rate of all the controllers on the network. All 

controllers on the network must have a unique MS/TP address and BACnet Device ID. Each port must be properly config

-

ured.

Check the network wiring, making sure to follow polarity; the wire that goes to A must go to A in all devices, as well as the 

wire that goes to B and REF.

No LAN Link to the Internet

Verify the network cable is connected correctly and make sure the LEDs next to the Ethernet jack are properly illuminat-

ed. For example, a solid green LED at the RJ-45 LAN connector usually indicates that the QD3041 is either connected or 

receiving a signal. If the green light is flashing, this is an indication of data being sent or received. 
If there are no lights, the QD3041 may not be connected properly, or may not be receiving a signal from the network. If, 

after checking the connections, the LED indicators are still off, the network adapter, port, or cable may be defective.

If there are lights but there is still no communication, this could be because the network communication is not set proper

-

ly or there is a bad firewall proxy setting. Contact your IT department for support, or contact TCS Technical Support (800-

288-9383, ext. 2) for assistance.

Summary of Contents for QD3041

Page 1: ...800 288 9383 www tcsbasys com 202112 Installation Manual The QD3041 BACnet Building Manager connects the local site BACnet controller network with Ubiquity Cloud QD3041 BACnet Building Manager BACnet...

Page 2: ...D Does Not Light Up 6 No Communications with Controllers on the Network 6 No LAN Link to the Internet 6 No Communication with RS 485 Ports COM 1 and 2 Ubiquity Time out or No Data 7 Configuration 8 In...

Page 3: ...ay also be set on a shelf or table If mounting on a wall do not allow the mounting screws to contact the circuit board inside the enclosure When selecting a location to mount the QD3041 be sure to all...

Page 4: ...RS 485 connection Place a 120 terminating resistor at each of the two ends of the network directly across the A and B wires If the QD3041 will be at one end of the network hard wire a 120 terminating...

Page 5: ...uctor com munications wiring with one end earth grounded 120 terminating resistors provided Shielded twisted three conductor com munications wiring with one end earth grounded 120 terminating resistor...

Page 6: ...he unit Press the power button on the front of the unit a blue light should come on indicating the unit ispowereed up No Communications with Controllers on the Network Make sure the baud rate selectio...

Page 7: ...nit from taking stray voltage off the RS 485 lines A set of LEDs on each of the RS 485 ports in the QD3041 allow the building occupant to view operational status of the serial communication integrated...

Page 8: ...stomers upon request It is the custom er s responsibility to configure a custom login and password Contact TCS Technical Support 800 288 9383 ext 2 for information on managing login credentials QD3041...

Page 9: ...on to save the setting Network Information This section contains settings which control how the QD3041 connects to the Internet All of these settings are deter mined by your local network administrato...

Page 10: ...roxy check box and enter all the related details in the fields that appear When you are finished entering information in this section click the Update Communication Info button Application Information...

Page 11: ...the local MS TP address Default is set to 1 which may need to be changed if another device is using that address Max Master This refers to the upper limit of addresses that the unit will communicate...

Page 12: ...er You have three options for the message that will appear here 1 Error No Route to Host The unit does not currently have an Ethernet connection 2 Connected The unit is able to communicate to the Ubiq...

Page 13: ...te patch QD3041 Configuration via Command Line Interface CLI When you connect a keyboard and monitor to the QD3041 See Appendix C Monitor and Keyboard on page 25 you can configure it for your site by...

Page 14: ...2800 Laura Lane Middleton WI 53562 800 288 9383 www tcsbasys com 14 14 Configuration Command Line Interface Screens Configuration Screen 1 Device ID Network Options Proxy Options...

Page 15: ...2800 Laura Lane Middleton WI 53562 800 288 9383 www tcsbasys com 15 15 Configuration Application Options Serial Options Security Options View Device Properties...

Page 16: ...Ethernet cable Connection Setup Ethernet Cable Connect one end of the Ethernet cable to the Local Management Ethernet Port on the QD3041 see QD3041 Power and Communication Connections on page 4 and t...

Page 17: ...ptions 3 On the Network Connections panel locate the Ethernet interface that is connected to the cable Right click on the item and select Properties Properties 4 On the Ethernet Properties panel locat...

Page 18: ...2800 Laura Lane Middleton WI 53562 800 288 9383 www tcsbasys com 18 18 Appendices TCP IPv4...

Page 19: ...s com 19 19 Appendices 5 On the Internet Protocol Version 4 TCP IPv4 Properties change the IP schema to IP Address 10 248 248 2 Subnet Mask 255 0 0 0 Default Gateway 10 248 248 2 DNS Blank 6 Click on...

Page 20: ...ppendices 7 Launch any web browser and type https 10 248 248 1 in the address field Device Address 8 Depending on your browser s configuration you may get the following screen Privacy Error Warning Sc...

Page 21: ...sys com 21 21 Appendices 10 Click on the Proceed link to take you to the next screen Proceed Screen 11 Enter the Login user name and password Login Screen 12 Configure the Gateway as needed See QD3041...

Page 22: ...t on page 16 and wish to revert back to its previous configuration follow the steps below Windows 10 1 Search for Ethernet Settings and click the Open link Ethernet Settings 2 On the Ethernet Settings...

Page 23: ...leton WI 53562 800 288 9383 www tcsbasys com 23 23 Appendices Properties 4 On the Ethernet Properties panel locate the Internet Protocol Version 4 TCP IPv4 Select that option then click on the Propert...

Page 24: ...24 24 Appendices 5 On the Internet Protocol Version 4 TCP IPv4 Properties General tab 6 Click on the Obtain an IP address automatically radio button 7 Click on the Obtain DNS server automatically rad...

Page 25: ...nd to the QD3041 matching up the corresponding ends HDMI DP See QD3041 Power and Communication Connections on page 4 Power on the monitor and switch to the proper input based on the cable used 2 Plug...

Reviews: